0ca56cb1f6
Live read-only check against a production CompactLogix press: with one nonexistent tag
first in the read list, libplctag's create threw LibPlcTagException("ErrorNotFound"); the
driver counted it as a failed Forward-Open, opened the device's 05/STAB-8 connect-backoff
window, and every other cold tag on the device - all real (WW_InCycle, WW_ActualPress,
WW_WorkOrderNum) - read BadCommunicationError. In steady polling the bad tag re-opens
the window each attempt, so siblings ordered after it may never connect.
- A create that fails with a "controller answered" status (NotFound/NoMatch/BadDevice,
the probe's existing reachable classification) records backoff SUCCESS, not failure.
Genuine connection failures still open the window (falsification control test).
- Read exceptions map through the libplctag Status they carry: unknown tag ->
BadNodeIdUnknown, decode past the buffer -> BadOutOfRange, timeout -> BadTimeout,
instead of a blanket BadCommunicationError. One status-name parser
(AbCipStatusMapper.TryGetStatus) now serves both the read path and the probe.