Joseph Doherty b7b754fd98 fix(twincat): accept TwinCAT 2 leading-dot globals in TwinCATSymbolPath (ignitionoee 0.19.1)
A TC2 global is named with ONE leading dot (.OPC_HEARTBEAT) and the PLC
requires it (SYM_HNDBYNAME answers 0x710 without it). TryParse rejected the
dot, so the driver fell back to the raw string and lost bit-index parsing:
.X.WORD.3 went to ADS verbatim instead of reading .X.WORD and extracting bit 3.
The dot now stays on the root segment and round-trips through ToAdsSymbolName;
.., ., .[1] and .9x stay invalid.