Every Boolean under Server/ServerCapabilities/HistoryServerCapabilities read
false (the SDK default) even though data and event history were served, so a
spec-following client skipped HistoryRead entirely.
Each backend now declares what it serves through its own interface:
- IHistorianDataSource.ReadCapabilities (Data / Events / ServerTimestamps):
Gateway Data|Events; SqlServer + QuestDb add ServerTimestamps (they store
ServerTimeUtc, the Gateway stamps read time); Null declares None. A
reflection guard requires every production source to declare it itself.
- IHistorianDataUpdater.Capabilities (required member): SqlServer and QuestDb
declare Insert/Replace/Update/DeleteRaw/DeleteAtTime; the Gateway provider
has no updater.
The node manager writes the flags on every source/updater assignment
(AdvertisedHistoryCapabilities), and the same declarations drive dispatch:
an update the updater does not declare is BadHistoryOperationUnsupported
without reaching it, the HistoryWrite AccessLevel bit follows a non-empty
declaration, and event-history notifier promotion follows the Events flag.
Event and annotation update flags stay false (nothing dispatches them).
Tests: booted-server wire test per backend + Null + a SqlServer->Gateway
rewire pairing on one session; dispatch gating unit test; the #801 live
gate now asserts the Gateway flags (not run here).
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Adds scripts/validation/opcua-windows-service/: a phased PowerShell gate (Invoke-ServiceGate.ps1)
that installs the known-good build as the real OtOpcUaHost service via Install-Services.ps1, seeds
LocalDb through the production cache API (Seeder, built against the baseline tree), upgrades in
place with config/PKI/LocalDb carried with their ACLs, starts/stops through the SCM, runs a strict
SDK 2 probe matrix (Sign + SignAndEncrypt, valid/wrong/unknown/disabled/anonymous keys, untrusted
client and server), exercises the ScriptWorker isolation, rolls back and cleans up.
windev 2026-11-12 (efb9197a -> 438484fd -> efb9197a): app cert CEF9D91F... reused byte-for-byte
with identical PKI SDDL on every start, all gating checks pass, 0 secrets in logs. Findings filed:
#879 (None endpoint cannot be dropped), #880 (SDK 2 client 65-char key vs SDK 1.5 server:
rollback/QA risk), #883 (Install-ScriptWorkerIsolation.ps1 fails on pwsh 7 and 5.1; runtime
isolation proven with the patch in the evidence directory).
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Console helper that mints and revokes OPC UA API keys through the same IApiKeyAdminService the AdminUI
/apikeys page calls, edits NodeAcl grants in the rig ConfigDb, and holds one OPC UA session open per node
(Client.Shared) with a subscription plus a read/write every 3 s, so a revocation, expiry or grant removal
can be observed landing on an ALREADY-OPEN session on both pair nodes next to a non-revoked control key.
Credentials go to a 0600 file and are never printed. LOCAL docker-dev only.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Every docker-dev node served the compiled default ApplicationUri "urn:OtOpcUa" with a one-entry
Server.ServerArray, so the two halves of a redundant pair were indistinguishable by URI and peer
discovery returned nothing. Each node now sets OpcUa__ApplicationUri = urn:OtOpcUa:<service> (its
seeded ClusterNode.ApplicationUri) and OpcUa__PeerApplicationUris__0 = its pair partner. Verified on
the central pair: ServerArray reads [self, partner] on both nodes.
RedundancySupport still reads None by design (#717). The pair's 255/255 ServiceLevel was not a rig
config problem: it is the SDK 2.0.1 session-headroom overwrite filed separately.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Both builds served HistoryRead from the real AVEVA Historian via the DEV
HistorianGateway (vd03, ea9f21c): 225 cases / 3,855 rows / events, 0 differences.
Raw also matches direct SQL on Runtime.dbo.History (6/6) and histgw-cli; simple
aggregates match a recomputation from raw (336/336). Modified, HistoryUpdate,
seven refused aggregates and HistoryServerCapabilities answer as before. No write
reached the historian. Findings (pre-existing, not SDK): all HistoryServerCapabilities
booleans false; AVEVA attribute-alarm events unreachable per source.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
AvevaGatewayHistoryLiveGateTests boots the server in-process, wires the production
Gateway backend (HistorianBackendRegistry -> GatewayHistorianDataSource) to a real
HistorianGateway and drives HistoryRead over a real SDK session: raw (all, paged,
reverse, bounds), modified, the ten served aggregates and seven refused ones, AtTime,
events (all, 1-event pages, reverse), a missing tag, HistoryServerCapabilities and
node metadata, and a HistoryUpdate that must be refused (sandbox-bound node only).
Every wire answer is compared with the backend's direct answer; the run is dumped as
JSON for cross-SDK and SQL comparison. Skips unless HISTGW_GATEWAY_ENDPOINT and
HISTGW_GATEWAY_APIKEY are set; read-only by construction.
scripts/validation/aveva-history-801: run/compare instructions, the SDK 1.5.378
baseline port patch (API spelling only), and the diff / SQL / aggregate / histgw-cli
comparison scripts.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Profiled the remaining lmxopcua#789 misses on windev, a VMware VM, using per-thread CPU and context-switch accounting
plus ETW CPU sampling.
- One blocking hand-off costs ~26 us of latency and ~18 us of CPU there, about 10x macOS.
- An idle evaluation makes four hand-offs in a row: host writer -> worker reader -> evaluation thread -> host reader
-> dispatcher.
- 48% of host CPU at 10k/s is in the kernel: the per-RunAsync NtWriteFile, thread-pool wakes, reads and waits.
Spin-before-block was measured at every hand-off and is not kept. It meets 150 us idle p50 (118 us) only by keeping
about two host cores and four worker cores busy for one stream. At 10k/s it reads +250 points.
Harness: new "paced 10,000/s, batched" row. It uses the same rate and keys, with each 1 ms tick submitted as one
RunBatch call, which is the production seams' shape. It runs after the original four phases, so their rows stay
comparable. On windev it halves host CPU, to +36..+45 points against +71..+84 unbatched. That is still above 25.
Design doc:
- 12.8: the record.
- 14 #15: the owner's decision on the Windows budgets. Recommended: measure on bare-metal Windows, then state the two
budgets per platform, with the batched row as the gate. The alternative is a shared-memory transport.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Probe 'failover <primary> <backup> <mode> <dir>' drives ScadaBridge's own DataConnectionActor
(production primary/backup machine, real DataConnectionFactory, default DataConnectionOptions,
FailoverRetryCount 3) against two servers; run.py loses the primary (SIGKILL or SIGSTOP) once the
probe reports a steady primary, and the probe requires Bad quality on loss, "Connected to backup",
the backup's own value, a fresh ConditionRefresh replaying the native condition, and a write via the
backup. rig-failover.sh runs the same probe against the local docker-dev central pair.
Matrix legs gain a UNS subscription case and a Server-object alarm subscription on the reconnected
session whose ConditionRefresh must replay the active condition (11 cases). run.py gains --versions,
--suites, --failover-modes and --failover-loss.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
A folder event item under enforcement withholds an event that names no live
condition; flag off, the SDK's own type + SourceNode check applies. Positive
controls: the same event reaches the item flag-off and a condition event
reaches it flag-on. Mutation-checked: IsNotifierEventVisibleTo returning true
for a non-condition event fails the test.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
Adds GatewayGalaxyStreamAttachedAckLiveTests (skip-gated on MXGW_ENDPOINT +
GALAXY_MXGW_API_KEY, like the other gateway live tests). Proves what the unit
suite cannot: the request flag reaches a real gateway and the sentinel comes back.
- live session advertises stream-events-attached-ack; GatewayGalaxySubscriber reports it
- raw stream: sentinel is the first message when requested (family Unspecified,
worker_sequence 0, live_after 0) and never sent when not requested (control,
with a data event as the positive control)
- real GalaxyDriver + EventPump + GatewayGalaxySubscriber behind a pass-through
recorder: exactly one sentinel, ack observed before the first SubscribeBulk,
pump StreamAttached completed, sentinel never dispatched nor counted as
received (galaxy.events.stream_attached=1, received == non-sentinel events),
no missing-ack warning within the production 1 s budget, and the static
attribute TestMachine_002.Tagname delivers its initial value
- control: a subscriber that opts out gets no sentinel and the pump never
reports one, while the #865 fallback still delivers
Run 2026-11-12 against windev 10.100.0.48:5120 (mxaccessgw 447070a5): 4/4.
Mutation checks, each caught: subscriber not requesting the ack (sentinel
count 0); driver skipping the ack wait (wire order became stream | subscribe |
ack, 2/2 runs, so the race is real on a live gateway); pump not intercepting
the sentinel (received=2 vs 1 non-sentinel).
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
mxaccessgw#227 (Contracts/Client 0.4.0) adds an opt-in attach acknowledgement on
StreamEvents: a StreamAttached sentinel MxEvent sent first, only after the
stream's subscriber is registered on the session. This closes the #865 attach
race that waiting for "stream requested" only narrowed.
- Bump vendored MxGateway.Client/Contracts 0.3.0 -> 0.4.0 (nuget-packages/,
pulled from the Gitea feed; local-mxgw stays the mapped source).
- IGalaxySubscriber.SupportsStreamAttachedAck (default false, so fakes and older
seams keep the fallback); GatewayGalaxySubscriber reads it from the live
session's capabilities (stream-events-attached-ack) and passes
emitStreamAttached accordingly; TracedGalaxySubscriber forwards it.
- EventPump: records AttachAckExpected before the stream opens (published
before StreamRequested completes); intercepts ev.StreamAttached ahead of the
ReplayGap check - completes StreamAttached and continues: never dispatched,
never counted as received, never a resume cursor (worker_sequence 0). The
signal also completes when the loop ends so no waiter hangs. One pump = one
stream, so a reconnect's new pump has a fresh signal. New counter
galaxy.events.stream_attached.
- AwaitCurrentEventStreamAsync: with the capability, waits on StreamAttached
within the same StreamRequestWait budget (1 s); a missing ack logs a
rate-limited Warning and proceeds instead of hanging. Without the capability
the old StreamRequested wait is the fallback.
Tests (StreamAttachedAckTests, 6): ack-gated subscribe gets its initial value;
capability absent uses the fallback; missing ack times out with a warning; the
sentinel is never dispatched; a dead stream releases ack waiters; reconnect
gives each stream a fresh signal. With the ack wait skipped, 3 of them fail.
Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
The rule fix itself landed in 1a08b4f7 (detail-0 failure rows route on
category); its test only exercised raw_detected_by = 3. Add per-source
coverage for every MxStatusSource value mxaccessgw's MapSource emits
(-1, 0..5, and an out-of-range value) across the failure categories, plus
the live-captured shape the old rule got wrong (OperationalError detected
by the responding automation object, mxaccessgw docs/AlarmProbeFindings.md)
and a RequestingLmx CommunicationError positive control. All 10 new cases
fail against the old 'detail 0 && raw_detected_by != 0 => comms' rule.
Comment in FromMxStatus now cites MapSource and says why NMX (2/3) is not
a transport signal. Item 1 (Warning/Pending) stays open pending a capture.
Co-Authored-By: Claude <noreply@anthropic.com>
Probe 'prepare' provisions the consumer identity via OpcUaApplicationIdentity.EnsureApplicationCertificateAsync
and exports the public DER; runner installs it in the server trusted store before start. Adds Sign
(OPCUA_MATRIX_SERVER_SECURITY=sign), untrusted-client / untrusted-server fail-closed controls per secure
mode, and OPCUA_MATRIX_ACL=off. Autoaccept stays false everywhere.
OpcUaApplicationHost left ServerConfiguration.MaxRegistrationInterval at the
SDK default (30000) with a null RegistrationEndpoint, so SDK 2.0.1's
StandardServer armed its registration timer against opc.tcp://localhost:4840,
which on an OtOpcUa node is the server itself (no LDS). It answered
BadServiceUnsupported and the SDK retried forever, visible since #874.
Registration is now opt-in: ApplyDiscoveryRegistration sets
MaxRegistrationInterval = 0 (the value that keeps StandardServer from arming
the timer) unless OpcUa:DiscoveryServerUrl is set, in which case the server
registers against that URL every OpcUa:DiscoveryRegistrationIntervalMs
(default 30000) over SignAndEncrypt/Basic256Sha256, like the SDK's own
default endpoint. The validator requires an absolute opc.tcp:// URL and a
positive interval when the URL is set. Documented in Configuration.md and
OpcUaServer.md.
Co-Authored-By: Claude <noreply@anthropic.com>
Measured on windev (3 alternated sessions) and macOS: a pool resume in place
of the dispatcher, and an inline-on-reader upper bound, with the harness as
committed and with its paced continuation made synchronous.
- pool: 10k/s host CPU unchanged, idle p50 and idle CPU worse (macOS idle CPU
x3 from pool spin); only the closed loop gains. Not kept.
- inline (unsafe for every seam; the ceiling for a VirtualTag-only opt-in):
~8 points of a core at 10k/s raw and ~50 us idle p50 on windev with a cheap
continuation, nothing with the harness as committed. Both budgets still
missed by a wide margin, so the opt-in was not built.
No code change. Records the remaining attribution (harness pool hop ~15
points raw; reader wake + syscalls; worker side untouched).
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
- Host reader: the frame read and its handling are caught separately. Only the
read's I/O exceptions mean the pipe ended; anything HandleFrame's inline
completion work throws now kills that worker as ProtocolFault (outstanding
runs -> worker restarted / BadResourceUnavailable) instead of escaping a
dedicated thread (process crash) or being swallowed as a clean end (an
InvalidOperationException used to be, leaving the worker unread until a Crash
2 s later).
- Worker reader: the same catch-all around HandleFrame (exit ProtocolFault).
- Worker: Cancel() runs on the pool, so a script's blocking
ctx.CancellationToken callback cannot stop the worker reading its pipe.
- Host write-stall check: ScriptWorkerFrameWriter.WriteInProgressFor; the
heartbeat monitor kills a worker whose pipe write has been blocked longer than
max(10 s, silence limit) as KilledUnresponsive, which fails the write and
releases the producer (seam submit, deploy load, Cancel). Fixes the wrong
'heartbeat monitor ends it' comment on the pipe buffer quota.
- StopAsync sends Shutdown off the caller so its 1 s budget holds on a full pipe.
- WindowsBlockingPipeStream refuses the async surface (Stream's base versions
serialise a write behind a waiting read).
- Tests: PipeFaultTests (throwing completion callback -> ProtocolFault and a
BadResourceUnavailable sibling, shard serves again; a worker that stops reading
but heartbeats is killed within the bound and the blocked producer returns,
via the Hello.test_stall_reader_on_diag seam); BlockingPipeStreamTests dispose
with a write blocked on a full pipe, and with a read and a write both pending;
Category=ScriptWorker on the protocol, handshake and pipe test classes.
Mutation checks: no stall kill -> stall test red; catch-all without the fault
-> callback test red (Crash).
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
With a zero quota an overlapped write stays pending until the peer has read the
bytes, so the new blocking writer waited out a peer wake-up per frame (windev
closed loop 54k -> 26k evals/s). With a quota the write completes once buffered.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
A .NET pipe opened Asynchronous completes even its synchronous Read/Write
through the thread pool's completion port, so every frame on Windows cost a
completion packet plus a pool work item (and the pool's spin-wait). New
WindowsBlockingPipeStream issues its own overlapped ReadFile/WriteFile with the
OVERLAPPED.hEvent low bit set (no completion packet) and waits on that event on
the calling thread; reads and writes stay concurrent, unlike a synchronous
handle. ScriptWorkerFrameCodec.BlockingStream picks it on Windows and the pipe
itself on Unix, so both ends now use the dedicated blocking reader + synchronous
combining writer on every OS (UseBlockingIo and the async read loops are gone).
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
Gate F (#761) against the VD03 gateway: Galaxy initialize (session open +
platform seed) took 4–5 s against Tier A's 5 s Initialize timeout, so 10 of 40
restarts failed, paid a 10 s retry and left a killed gateway worker.
DriverFactoryRegistry.Register takes optional capabilityDefaults per driver
type (GetCapabilityDefaults); DriverResilienceOptionsParser layers them over the
tier table and under the per-instance ResilienceConfig; the Host wires the
registry into DriverCapabilityInvokerFactory. Galaxy registers Initialize =
20 s (no retry, breaker 2), under the actor's 30 s pessimistic bound.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
PASS: gauge baseline 2, +2 with the rig's driver on both centrals, 4 after 20
config deploys (40 respawns; rig opened 39 / closed 37). Final drop after
removal not observed: the Mac's VPN to VD03 dropped right after the settle.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
Hosted v2-integration run 1224 got past the old fixture-host timeout and
failed one step earlier: "Bind for :::19000 failed: port is already
allocated" — the runner's docker daemon is shared. Fixtures now retry on the
next host port when one is taken (opc-plc keeps host == listen port, as its
advertised endpoint requires) and export the ports actually used; container
names carry the run id so a concurrent run's `down` can't remove them, and a
new `logs` subcommand replaces the workflow's hard-coded name list.
Verified locally: with 19000 squatted, QuestDB moved to 18813/19001 and every
fixture reached ready; logs/down found the suffixed containers.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
The host handed the SDK a provider-less telemetry context, so SDK-side
refusals — identity-token decryption (the SDK 2 RsaEncryptedSecret clock
window, #873), certificate validation, secure-channel faults — left no server
log line (found on windev during the #800 Windows validation). The hosted
service now creates one ServerSdkTelemetry context from its ILoggerFactory
(Warning and above, SDK categories, rate-limited 20/min per category) and
shares it between OtOpcUaSdkServer and the ApplicationInstance; released on
dispose. Test: an untrusted client's rejection reaches the captured log.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
Read-only ConfigDb preflight (scripts/preflight/vd03-preupgrade-b8b4c18f-configdb-checks.sql)
covering every deploy gate added since the deployed build: VirtualTag/Calculation effective
triggers (#783), VT->VT reads and VirtualTagDependencyCycle (#791), newly forbidden script
APIs (#792, E2), credential-reference namespace / other-instance / reserved-name rules
(#815#835#836#848#849#850), MTConnectMultipleDevices, Sql query/write gates (#781),
Heidenhain, UNS effective-name collisions and the FOCAS renames/value changes. Verified on a
throwaway b8b4c18f-schema database (every check fires on seeded rows) and clean against the
docker-dev config.
Upgrade notes (docs/deploy/vd03-upgrade-b8b4c18f-to-master.md): the EnableSnapshotIsolation
migration and how to apply it by hand, the env-var audit (Security:ApiKeys:Pepper is now
required and absent on the box; JWT key validated at start), SDK 2.0.1 / CA KeyUsage, the
ScadaBridge-visible changes, swap/rollback and post-deploy checks.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
The fixed name lives on the SQL Server shared by every checkout and CI, so a
concurrent run's create or finally-drop could collide (failed once in the
local pre-push suite, 3/3 green on rerun; cause plausible, not proven).
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
Since #855 condition events are queued to folder event items under the node
manager Lock. At a full DiscardOldest queue the SDK's EventQueueHandler
dequeues the head of EventMonitoredItemQueue, a List.RemoveAt(0) shift of the
whole queue (~1 us/item at QueueSize 1000, ~10 us at 10000).
OtOpcUaSdkServer.CreateMonitoredItemQueueFactory now wraps the SDK factory in
RingEventQueueFactory: event queues are RingEventMonitoredItemQueue (O(1)
discard), data-change queues, durable requests and disposal go to the SDK
factory unchanged. A factory set through StandardServer.MonitoredItemQueueFactory
is used as-is.
The SDK queue is storage only (decompiled 2.0.1): DiscardOldest, overflow-event
positions and discarded/overflow counters live in EventQueueHandler, which is
unchanged. The ring reproduces QueueSize 0 initial + BadInternalError enqueue,
drop-oldest at Count == QueueSize, FIFO dequeue, SetQueueSize keep-newest /
keep-oldest, the newest-1000 duplicate window via IsEventRaisedFor, no-op
Dispose. RingEventMonitoredItemQueueParityTests drive both queues, and the SDK
EventQueueHandler over both factories, with the same random sequences.
FolderEventDeliveryPerfTests gains Ring_vs_sdk_event_queue (A/B in one process
via the internal OtOpcUaSdkServer.RingEventQueues switch).
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
Every raw detected_by value names an MXAccess layer (requesting/responding
LMX, NMX, automation object); the gateway's own failures arrive as
ProtocolStatus. The 'non-zero source = transport failure' rule made a failure
the responding object detected a comms error. Item 1 of #872 (Warning/Pending
categories) stays open pending a captured row.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk
The gateway fills Statuses on every data change (live OnDataChange, value-cache
replay and session snapshot all carry Quality too), and EventPump used the status
row whenever one was present, so Quality was never read: an off-scan, Bad or
Uncertain attribute with an OK status row was published Good. A failure status
row still wins; otherwise the quality byte grades the value (legacy parity:
quality >= 192 Good).
Live, read-only on VD03 (DEV): healthy ScanState and _TestArea attributes stay
Good (0x00000000) via quality 192; the stopped JoePlatform/JoeAppEngine ScanState
now publish BadCommunicationError (0x80050000) instead of generic Bad, with no
"unrecognised quality byte" warning.
Claude-Session: https://claude.ai/code/session_01GT67AD99zQQqpLCVm3p7xk