feat(modbus): wire Family / MelsecSubFamily / DisableFC23, and the form's timing keys

U1: a tag's addressString (Modicon / mnemonic / DL205 V-memory / MELSEC
D-X-Y grammar) now resolves through ModbusAddressParser with the DRIVER's
Family and MelsecSubFamily at every initialize and is authoritative; the
family-unaware gates (deploy Inspect, AdminUI parse consult) accept what
some family resolves. The tag editor gets an address-text field that
resolves with the owning driver's family and persists both the string and
the resolved region/offset/type fields; a hand edit drops the string.
DisableFC23 now gates FC23: by default a 2..121-register holding write is
one FC23 write + read-back (a unit answering exception 01, or failing FC23 at
the transport, moves to FC16 for the rest of the generation); RTU framing
deframes the FC23 reply. Live-checked: the pymodbus fixture implements FC23.
Also: the AdminUI driver form serialises ModbusDriverOptions (TimeSpan
strings), which the factory DTO never read - every timing field on the form
was dead. The DTO now accepts both shapes (*Ms keys win).

Refs #741
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
This commit is contained in:
Joseph Doherty
2026-10-22 15:35:58 -04:00
parent 1adc9d65e1
commit 4a3d7a9361
13 changed files with 656 additions and 58 deletions
@@ -25,6 +25,17 @@ public sealed class ModbusRtuFramingTests
pdu.ShouldBe(new byte[] { 0x03, 0x02, 0x00, 0x0A }); // fc + byteCount + data, no addr/CRC
}
/// <summary>FC23 (Read/Write Multiple) replies like a read: byte count + data. It used to be sized as a
/// fixed 4-byte write echo and desync.</summary>
[Fact]
public async Task ReadResponse_FC23_returns_bare_pdu()
{
var body = new byte[] { 0x01, 0x17, 0x04, 0x00, 0x0A, 0x00, 0x0B };
await using var s = Canned(ModbusCrc.Append(body));
var pdu = await ModbusRtuFraming.ReadResponsePduAsync(s, 0x01, TestContext.Current.CancellationToken);
pdu.ShouldBe(new byte[] { 0x17, 0x04, 0x00, 0x0A, 0x00, 0x0B });
}
[Fact]
public async Task ReadResponse_exception_frame_throws_ModbusException()
{