Adds the mbproxy service end-to-end. Phases 00-08 implement the production-ready single-listener / 1:1-backend transparent Modbus TCP proxy with bidirectional BCD rewriting for the ~54-PLC DL205/DL260 fleet. Phase 9 replaces the connection layer with a single backend socket per PLC plus MBAP TxId rewriting, lifting the H2-ECOM100's 4-concurrent-client cap as an operational ceiling. Phase 9 additions of note: - PlcMultiplexer + UpstreamPipe + TxIdAllocator + CorrelationMap - InFlightRequest with IReadOnlyList<InterestedParty> (load-bearing for Phase 10 read coalescing — do not collapse to a single field) - Per-request watchdog: surfaces Modbus exception 0x0B to upstream on BackendRequestTimeoutMs, defending against lost responses, dead-PLC paths, and pymodbus 3.13.0's concurrent-multiplexed- request bug (its ServerRequestHandler.last_pdu state race) - Status DTO + HTML gain inFlight / maxInFlight / txIdWraps / disconnectCascades / queueDepth (Tier 1.6 in docs/kpi.md) Tests: 263 unit + 38 E2E. Multiplexer correctness under truly concurrent backend traffic is proved against a stub backend in PlcMultiplexerTests; MultiplexerE2ETests paces requests so pymodbus 3.13's single-PDU framer stays in known-good mode. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
156 lines
7.4 KiB
JSON
156 lines
7.4 KiB
JSON
// mbproxy configuration template — copy to %ProgramData%\mbproxy\appsettings.json
|
||
// and edit before starting the service.
|
||
//
|
||
// The .NET configuration loader accepts // and /* */ comments in JSON files
|
||
// (JSONC semantics) when using the default Host.CreateApplicationBuilder path.
|
||
//
|
||
// IMPORTANT: This file is overwritten on each install ONLY if no appsettings.json
|
||
// already exists at the destination. An existing file is always preserved.
|
||
{
|
||
"Mbproxy": {
|
||
|
||
// ── Global BCD tag list ─────────────────────────────────────────────────────────────
|
||
// These tags apply to EVERY PLC by default.
|
||
// Each entry: Address (Modbus PDU address, decimal), Width (16 or 32 bits).
|
||
//
|
||
// Width 16 — one register holds 4 BCD digits (0–9999).
|
||
// Wire value 0x1234 decodes to decimal 1234.
|
||
//
|
||
// Width 32 — a CDAB-ordered register pair (Address = low word, Address+1 = high word).
|
||
// Decoded decimal = high * 10000 + low (DirectLOGIC CDAB word order).
|
||
//
|
||
// Per-PLC overrides (see Plcs[].BcdTags below):
|
||
// Add — appends extra tags beyond what Global defines, or overrides a
|
||
// Global entry's Width when the same Address appears in both.
|
||
// Remove — removes specific addresses from the effective set for that PLC.
|
||
// Effective set = (Global ∪ Add) − Remove, resolved per PDU.
|
||
"BcdTags": {
|
||
"Global": [
|
||
// V2000 (octal) = decimal address 1024. 16-bit BCD counter.
|
||
{ "Address": 1024, "Width": 16 },
|
||
|
||
// V2040 (octal) = decimal address 1056. 32-bit BCD total at 1056/1057.
|
||
{ "Address": 1056, "Width": 32 },
|
||
|
||
// V2100 (octal) = decimal address 1088. 16-bit BCD setpoint.
|
||
{ "Address": 1088, "Width": 16 }
|
||
]
|
||
},
|
||
|
||
// ── PLC list ────────────────────────────────────────────────────────────────────────
|
||
// Each entry maps one upstream proxy port → one backend PLC.
|
||
// Upstream clients connect to ListenPort; the proxy forwards to Host:Port.
|
||
//
|
||
// IMPORTANT: H2-ECOM100 modules accept at most 4 simultaneous TCP connections.
|
||
// With the 1:1 upstream↔backend model, a fifth upstream client to the same proxy
|
||
// port will cause a backend connect failure and an immediate upstream disconnect.
|
||
"Plcs": [
|
||
{
|
||
"Name": "Line1-Mixer", // Human-readable name (shown on status page and in logs)
|
||
"ListenPort": 5020, // Port the proxy listens on (upstream clients connect here)
|
||
"Host": "10.0.1.1", // PLC IP address or hostname
|
||
"Port": 502, // PLC Modbus TCP port (almost always 502)
|
||
"BcdTags": {
|
||
// Additional 32-bit tag specific to this PLC only.
|
||
"Add": [
|
||
{ "Address": 1200, "Width": 32 }
|
||
],
|
||
// Remove address 1056 from the Global list for this PLC
|
||
// (this mixer doesn't use the 32-bit BCD total).
|
||
"Remove": [ 1056 ]
|
||
}
|
||
},
|
||
{
|
||
"Name": "Line1-Conveyor",
|
||
"ListenPort": 5021,
|
||
"Host": "10.0.1.2",
|
||
"Port": 502
|
||
// No BcdTags override — uses the Global set as-is.
|
||
}
|
||
// Add one entry per PLC. Ports must be unique per host. Typical fleet: 54 PLCs.
|
||
],
|
||
|
||
// ── Admin port ──────────────────────────────────────────────────────────────────────
|
||
// Read-only HTTP status page.
|
||
// GET / → self-contained HTML (auto-refreshes every 5 s)
|
||
// GET /status.json → same data as JSON for monitoring scrapers
|
||
//
|
||
// Authentication is assumed at the network layer (trusted internal segment).
|
||
// Set to 0 to disable the admin endpoint.
|
||
"AdminPort": 8080,
|
||
|
||
// ── Connection timeouts ─────────────────────────────────────────────────────────────
|
||
"Connection": {
|
||
// Max time (ms) to wait for a TCP connect to the PLC backend.
|
||
// Each Polly retry attempt gets its own copy of this timeout.
|
||
"BackendConnectTimeoutMs": 3000,
|
||
|
||
// Max time (ms) to wait for the PLC to respond to a forwarded PDU.
|
||
// Non-idempotent FC06/FC16 writes are one-shot — the upstream client
|
||
// is disconnected immediately on timeout (no retry).
|
||
"BackendRequestTimeoutMs": 3000,
|
||
|
||
// Max time (ms) to wait for in-flight PDUs to complete during graceful shutdown
|
||
// (sc.exe stop / Windows Service stop signal). After this deadline the coordinator
|
||
// cancels remaining work and proceeds. Keep at or below the SCM wait-hint (30 s).
|
||
"GracefulShutdownTimeoutMs": 10000
|
||
},
|
||
|
||
// ── Resilience policies ─────────────────────────────────────────────────────────────
|
||
"Resilience": {
|
||
|
||
// Polly retry policy for backend TCP connect attempts.
|
||
// MaxAttempts: total connect tries (including the first).
|
||
// BackoffMs: delay between each attempt (must have MaxAttempts−1 entries).
|
||
"BackendConnect": {
|
||
"MaxAttempts": 3,
|
||
"BackoffMs": [ 100, 500, 2000 ]
|
||
},
|
||
|
||
// Polly recovery policy for listener bind failures.
|
||
// If a PLC's listen port can't be bound (in-use, bad IP, transient OS error),
|
||
// the supervisor retries according to this schedule.
|
||
// InitialBackoffMs: backoff per step (first N retries).
|
||
// SteadyStateMs: backoff for all subsequent retries (runs indefinitely).
|
||
"ListenerRecovery": {
|
||
"InitialBackoffMs": [ 1000, 2000, 5000, 15000, 30000 ],
|
||
"SteadyStateMs": 30000
|
||
}
|
||
}
|
||
},
|
||
|
||
// ── Serilog ─────────────────────────────────────────────────────────────────────────────
|
||
// Structured log output. Default: Information level, rolling-file under ProgramData.
|
||
// The EventLogBridge writes Error+ events to the Windows Application Event Log
|
||
// automatically when the service runs under the SCM (not under dotnet run).
|
||
"Serilog": {
|
||
"Using": [ "Serilog.Sinks.Console", "Serilog.Sinks.File" ],
|
||
"MinimumLevel": {
|
||
"Default": "Information",
|
||
"Override": {
|
||
"Microsoft": "Warning",
|
||
"System": "Warning"
|
||
}
|
||
},
|
||
"WriteTo": [
|
||
{
|
||
"Name": "Console",
|
||
"Args": {
|
||
"outputTemplate": "[{Timestamp:HH:mm:ss} {Level:u3}] {Message:lj} {Properties:j}{NewLine}{Exception}"
|
||
}
|
||
},
|
||
{
|
||
"Name": "File",
|
||
"Args": {
|
||
// Rolling log: one file per day, kept for 30 days.
|
||
// Survives uninstall — logs are archived to %ProgramData%\mbproxy.archived-<ts>\.
|
||
"path": "C:\\ProgramData\\mbproxy\\logs\\mbproxy-.log",
|
||
"rollingInterval": "Day",
|
||
"retainedFileCountLimit": 30,
|
||
"outputTemplate": "[{Timestamp:yyyy-MM-dd HH:mm:ss.fff zzz} {Level:u3}] {Message:lj} {Properties:j}{NewLine}{Exception}"
|
||
}
|
||
}
|
||
]
|
||
}
|
||
}
|