docs(index): OtOpcUa #717 closed, #615 G9 PASS + G8 waived, Heidenhain accepted

This commit is contained in:
Joseph Doherty
2026-11-13 07:47:31 -05:00
parent 027eb354fd
commit 2717d7c23b
2 changed files with 26 additions and 1 deletions
@@ -631,3 +631,28 @@ on `MonitoredItemNotification.Message` validated by `(ClientHandle, DataValue)`;
touched); real 2-node handover test. **ScadaBridge consumer impact: none until a tier sets `Warm`** — that is gated on
ScadaBridge#138 (ServiceLevel-aware failover) being deployed, because a Warm Standby serves Bad data on a healthy session.
### 2026-11-13 — #717 closed, #615 G9 PASS + G8 waived, Heidenhain accepted (master `a59dbd4f`, `c9bc358d`)
- **#717 closed.** Every item under "Required work" is done: modes `Unset`/`None`/`Warm` (`7829b937`), the standard
metadata under `Warm`, the wire tests plus deferred depth (`687256d6`, 39 mutations killed), the T13 isolated-pair
live gate (every applicable leg passes after `c569f806`, which fixed two crash-failover defects) and the T13b
`Unset` failover re-check (no behaviour change). Turning `Warm` on in any tier is **lmxopcua#907**, blocked on
ScadaBridge#138.
- **#615 G9 PASS.** The owner approved `otopcua-cli` as the client. Run on an isolated 2-node pair (`otopcua-g9`,
`003c7f89`, `Mode` unset as deployed):
- ServiceLevel 250/240; a follower stop left the Primary at 250; ServerArray lists both URIs.
- Graceful Primary stop: the CLI `-F` sessions failed over with an ~11 s data gap.
- `docker kill` of the Primary: the CLI failed over within 1 s, ~2 s data gap, 0 Bad; the survivor reached 250 at +44 s.
- No failback after either run.
- A4/A5b are unmet under `Unset` and met under `Warm`.
Evidence: `docs/plans/evidence/2026-11-13-615-g9/RESULTS.md`. The run found the CLI printing arrays as
`System.String[]`; fixed by `ValueFormatter`. **G8 (CTT) waived by the owner for GA. G5 (Fleet Admin sign-off) is
the only open v2 GA exit criterion.**
- **Heidenhain LSV2 driver accepted (#829/#853 closed).** The ignitionoee CR capture (`6d2aec40`: 7 h read-only
sample of 34 production controls on the Java driver) did not change the code:
- ProgramState 0 coincided with axis motion in 11,865 of 11,869 sample pairs; 7 = idle.
- TNC 426/430: `BadNotSupported`.
- Overrides: `BadUserAccessDenied` under INSPECT.
- Alarm classes 1/7/8 seen; class 5 never seen (the condition-class mapping stays labels-only).
- **ScadaBridge impact:** none. No wire or behaviour change; the CLI fix is client-side only.
+1 -1
View File
File diff suppressed because one or more lines are too long