deploy(prod): CVD reactor content (Phase 7) — QA→PROD templates, API methods, BTDB, Z28061–Z28069 on site-par; mxgw SQL login + PAR NewJersey alarms
Plan docs/plans/2026-11-22-prod-cvd-content-copy.md with the QA findings, the hierarchical-name binding remap (QA and PROD reuse Galaxy suffixes for different machines), BT checks, the run status and the QA reactor disable. Generated inputs under docs/deploy/2026-11-22-prod-cvd-content/ (bindings, alarm-source overrides, mapping, QA export, BT preflight SQL, helper scripts; no secrets). PROD plan §0.1a rows for the content run and the mxgw changes. Claude-Session: https://claude.ai/code/session_01GT67AD5mc2BnaaAfY3hqqQ
This commit is contained in:
@@ -39,6 +39,8 @@ The Sunday run was brought forward by the owner; the soak gate (§0.2 item 3) wa
|
||||
| Secrets | Keychain `zb-prod/{sb-jwt-signing-key,sb-inbound-pepper,mxgw-pepper,sb-site-par-grpc-psk,sb-site-par-localdb-key,sql-wwpdsbrw}`; on-box value dirs deleted except vp03 `_values\seed\site-psk.txt` (for the retry) |
|
||||
| **Later 2026-11-20** | #59 indexes done by DBA (verified 104 = QA) → central store seeded, **centrals Running** (vp03 active, vp04 standby, Automatic); **Site `site-par` id 1** online (par-vp03 primary); mxgw key `scadabridge-prod` (Keychain `zb-prod/mxgw-apikey-scadabridge`) shared vp03→vp04; **DataConnection id 1 `MxGateway`** vp03 primary / vp04 backup, Connected; **Overview** on vp03/vp04 :5320 (5 Up, mxgw vp04 Down #60, PAR mxgw unreachable). Records: ScadaBridge cluster-config record, scadaproj `0a3c37a` |
|
||||
| **site-app 22:35Z** | Second site **`site-app` / APP (Site id 2)** co-located on app-vp03 (node-a, active) / vp04 (node-b, standby), owner request; Akka 8082, site gRPC 8086, health 8084 (central keeps 8081/8083/8085); PSK `sb-grpc-psk-site-app` in the central store; **DataConnection id 2 `MxGateway`** → vp03:5120 primary / vp04:5120 backup, Connected. Overview shows site-par + site-app. Record ScadaBridge `2026-11-20-prod-site-app-colocated.md` |
|
||||
| **Phase 7 CVD content 2026-11-22 16:37Z** | Templates 1–11 (CvdReactor 5), db-connection 1 `BTDB`, API methods 1–7, area 1 `CVDAisle_1`, instances Z28061–Z28069 (ids 1–9) deployed + Enabled on site-par, 244/244 Good each; `deploy artifacts --site-id 1` done 16:37:47Z; keys `MES_Key` + `delmia-notifier` (Keychain `zb-prod/sb-inbound-*`), smoke PASS on vp03 and standby vp04. Cutover (step 10) pending owner/teams. Record ScadaBridge `2026-11-22-prod-cvd-reactors-content.md` |
|
||||
| **mxgw 2026-11-22 16:54–17:02Z** | All four gateways' Galaxy connection is now the SQL login `wwpdgdbro` (`db_datareader` on ZB), so `/health/ready` is 200 on all four and **#60 is no longer needed**. PAR alarms are on: `\\WONDER-PAR-VP0x\Galaxy!NewJersey`, which includes the `CVDAisle_1` and `Gas_Service` sub-areas. 7 active `HeartbeatTimeoutAlarm`s are mirrored on their own instances. vp03/vp04 keep `Galaxy!ControlSystem`, set outside this run. Worker CPU on PAR ~0%. Record: mxaccessgw `docs/deploy/2026-11-22-prod-par-e74918cc.md` |
|
||||
| Not done | OTel collector; LDAP refusal probes (bogus / zero-role); alarm area; Phase 7 content; MxGateway connection re-pointed to par-vp03/par-vp04:5120 at 22:22Z (owner); Connected since the 2026-11-22 PAR mxgw install. **2026-11-22 12:31Z: every service on app-vp03/04 was restarted externally** (cause unknown, back at 12:34:30Z). An unreferenced connection is not rebuilt on site boot by design, so after any restart run `deploy artifacts --site-id 2` (site-app; done 12:43Z) until instances exist |
|
||||
|
||||
### 0.2 Go / no-go before anything runs on Sunday
|
||||
|
||||
@@ -0,0 +1,376 @@
|
||||
# PROD content: copy the CVD reactor templates and inbound API methods from QA, and configure Z28061–Z28069 (plan, 2026-11-22)
|
||||
|
||||
Owner, 2026-11-22: "investigate the templates in use on QA scadabridge. how the tags are mapped, etc. Then generate a plan
|
||||
on how to copy them to prod, copy the api methods used too, and configure the machine in the attached screenshot. note
|
||||
the template instances should run on the par server cluster, the api methods can run on the central server."
|
||||
The screenshot shows Galaxy `NAM / NewJersey / CVDAisle_1 / Z28061…Z28069`.
|
||||
|
||||
This is Phase 7 of [`2026-11-19-prod-scadabridge-mxgw-install.md`](2026-11-19-prod-scadabridge-mxgw-install.md).
|
||||
**Status 2026-11-22 16:50Z: steps 0–9 DONE on PROD** (record ScadaBridge `docs/deployment/deployment-records/2026-11-22-prod-cvd-reactors-content.md`). Step 10 (cutover) is with the owner and the MES/Delmia teams. The keys are `MES_Key` with QA's grants minus IpsenMESMoveIn (so DelmiaRecipeDownload is included), and `delmia-notifier`. Delmia sends the plain `MachineCode` (`Z28063`).
|
||||
|
||||
Before the run, everything was read-only:
|
||||
- the QA management API (lists, `get`, `bundle export`, audit query);
|
||||
- QA Galaxy `ZB` over SQL as NAM\dohertj2;
|
||||
- PROD Galaxy browse through vp03's gateway with the `scadabridge-prod` key (`metadata:read`);
|
||||
- `bundle preview` on PROD, which does not apply anything.
|
||||
|
||||
The generated inputs are in [`../deploy/2026-11-22-prod-cvd-content/`](../deploy/2026-11-22-prod-cvd-content/).
|
||||
|
||||
## 0. Run status (2026-11-22, owner: "start the plan but wait to deploy to the par sites")
|
||||
|
||||
Steps 0–6 were done on the PROD central through the management API. **Nothing has been deployed to any site:**
|
||||
`deploy status` shows 0 deployments, and both sites' `artifactsDeployedAt` are unchanged. Run log:
|
||||
scratchpad `run/run-log.md`.
|
||||
|
||||
| Step | Result | IDs |
|
||||
|---|---|---|
|
||||
| 0 BT re-check | 9 machines + `CVD_Reactors` exist, no conflicts | n/a |
|
||||
| 1 Mapping | Galaxy re-read: 108 objects, identical to `mapping.md` | n/a |
|
||||
| 2 Templates | 11 imported (`--on-conflict skip`, 0 blockers) | ids 1–11; **CvdReactor = 5** |
|
||||
| 3 `BTDB` db-connection | created; **`deploy artifacts` held** | id 1 |
|
||||
| 4 API methods | 7 created; identical to the QA JSON | 1 MesMoveIn, 2 MesMoveOut, 3 DelmiaRecipeDownload, 4 SimpleAlarmStatusRequest, 5 MesSampleData, 6 MesIsMoveInReady, 7 MesIsMoveOutReady |
|
||||
| 5 Area | `CVDAisle_1` on site-par | area 1 |
|
||||
| 6 Instances | created with 244 bindings (connection 1) and 7 alarm-source overrides each; **Disabled, not deployed** | Z28063=1, Z28061=2, Z28062=3, Z28064=4, Z28065=5, Z28066=6, Z28067=7, Z28068=8, Z28069=9 |
|
||||
|
||||
**Held, waiting on the owner's go:**
|
||||
- `deploy artifacts --site-id 1`;
|
||||
- deploy and enable of the instances (steps 6/7);
|
||||
- API keys (step 8);
|
||||
- smoke test (step 9);
|
||||
- cutover (step 10).
|
||||
|
||||
**QA reactors disabled 2026-11-22 16:38Z** (owner: "disable the machines in qa"):
|
||||
- `instance disable` on QA ids 1, 2, 9, 11, 12, 13, 10, 14, 15 (Z28061–Z28069) all returned success; `instance list`
|
||||
shows state 2 (Disabled) for all nine.
|
||||
- The QA site no longer runs them: a `debug snapshot` of Z28063 returns `instanceNotFound`.
|
||||
- WarmCanary (still enabled) and ZIPSEN (already disabled) were not touched.
|
||||
- The last MES call to QA was at 2026-11-19 18:26Z. From now on, MES/Delmia calls to QA for these machines fail until
|
||||
the callers move to PROD.
|
||||
- To undo: `instance enable` + `deploy instance` for those ids on QA.
|
||||
|
||||
Notes from the run:
|
||||
- `template validate --id 5` reports 3 errors: alarms `Left/RightMTALockout` and `MantleTempHigh` reference
|
||||
`*ReactorSide.MTA_Lockout`/`MantleTemp`, which it calls "not in the flattened configuration". **QA's CvdReactor gives
|
||||
the same 3 errors, yet QA deployed Z28063 successfully on 2026-11-15**, after those alarms were created (09-30 and
|
||||
10-22). So this looks like a false positive in `template validate` for members of composed, derived templates; it is
|
||||
not a deploy blocker. Watch the first PROD deploy anyway.
|
||||
- QA's `RightMESReceiver` template is missing 14 inherited attribute rows and 2 inherited scripts. PROD's copy (id 9)
|
||||
is complete. This is a QA-side defect only.
|
||||
|
||||
## 1. What QA runs (findings)
|
||||
|
||||
### 1.1 Templates (QA ScadaBridge `wonder-app-vq03:8085`, site `site-a` id 2, area `Aisle001`)
|
||||
|
||||
| Template | Role | Members |
|
||||
|---|---|---|
|
||||
| `CvdReactor` (id 1) | The machine. One instance per reactor | 16 attributes (machine UDAs: `ChlorineFlow`, `HydrogenFlow`, `TrunkPressure`, `Heartbeat*`, `LeakTest*`, `MachineCode/ID/Description`, …); 3 computed alarms; 8 scripts; 7 native alarm sources; 5 compositions |
|
||||
| ↳ `LeftMESReceiver` / `RightMESReceiver` | Derived from `MESReceiver` (id 3) | 26 attributes each: `MoveIn*` and `MoveOut*` handshake tags plus `ScanStateCmd`. The base carries the `MoveIn`/`MoveOut` scripts |
|
||||
| ↳ `LeftReactorSide` / `RightReactorSide` | Derived from `ReactorSide` (id 7, "Galaxy `$Reactor_Side`") | 60 attributes plus composed `LeakTest` (23 attributes) |
|
||||
| ↳ `DelmiaReceiver` | Derived from `DelmiaReceiver` (id 12) | 10 attributes: `ReadyFlag`, `RecipeDownloadFlag`, `RecipeProcessedFlag`, `RecipeProcessResult[Text]`, `DownloadPath`, `WorkOrderNumber`, `PartNumber`, `JobStepNumber`, `Username` |
|
||||
|
||||
Not copied, because they are QA test content: `IpsenSim` + its `MESReceiver` (instance `ZIPSEN`), `WarmCanary` (the OtOpcUa
|
||||
Warm monitor), and the standalone `LeakTest` base, which comes along anyway as a dependency.
|
||||
|
||||
**Scripts on `CvdReactor`.** All of them are `Call`-triggered: there are no timers and no value-change triggers.
|
||||
- `MesMoveIn`, `MesMoveOut`, `MesIsMoveInReady`, `MesIsMoveOutReady` and `MesSampleData` parse
|
||||
`<SAPID>_A|_B[_LT]` and pick `Children[side+"MESReceiver"]`.
|
||||
- `ProcessRecipeDownload` uses `Children["DelmiaReceiver"]`.
|
||||
- `AlarmStatus` is a stub that returns an empty list.
|
||||
- `IpsenMoveIn` is legacy.
|
||||
- `MesMoveOut` and `MesSampleData` also read BTDB on the site (`Database.Connection("BTDB")`, best-effort cycle data).
|
||||
|
||||
The computed alarms (`MantleTempHigh`, `Left/RightMTALockout`) only read values. **So a deployed instance is passive.**
|
||||
It reads tags and evaluates alarms, and writes nothing to the Galaxy until an inbound API call reaches it.
|
||||
|
||||
### 1.2 Tag mapping
|
||||
|
||||
Every template attribute's data-source reference is just its own name (e.g. `ChlorineFlow`). **Every Galaxy address
|
||||
comes from a per-instance connection binding** (`dataSourceReferenceOverride`) on data connection 1 `MxGateway`. The
|
||||
Galaxy shape is the same in both galaxies:
|
||||
|
||||
```
|
||||
Z2806x ($CVDReactor) → instance root attributes Z2806x.<attr>
|
||||
├─ DelmiaReceiver (DelmiaReceiver_0NN) → DelmiaReceiver.<attr> DelmiaReceiver_0NN.<attr>
|
||||
├─ Left ($Reactor_Side, Left_0NN) → LeftReactorSide.<attr> Left_0NN.<attr>
|
||||
│ ├─ LeakTest (LeakTest_0NN) → LeftReactorSide.LeakTest.<attr> Left_0NN.LeakTest.<attr>
|
||||
│ ├─ MESReceiver (MESReceiver_0NN) → LeftMESReceiver.<attr> MESReceiver_0NN.<attr>
|
||||
│ ├─ Setpoints, TableAlarms → (not bound; TableAlarms feeds a native alarm source)
|
||||
└─ Right (same as Left)
|
||||
```
|
||||
|
||||
There are 244 bindings per machine: 16 root, 2×26 MES, 2×83 side (including LeakTest), and 10 Delmia.
|
||||
|
||||
Native alarm sources mirror Galaxy alarms by object prefix:
|
||||
- `ReactorAlarms` = `Z2806x.`;
|
||||
- `Left/RightSideAlarms` = `Left_0NN.`;
|
||||
- `Left/RightLeakTestAlarms` = `LeakTest_0NN.`;
|
||||
- `Left/RightTableAlarms` = `TableAlarms_0NN.`.
|
||||
|
||||
### 1.3 ⚠ PROD reuses the same tag names for different machines
|
||||
|
||||
QA's and PROD's Galaxies number their contained objects differently, and the numbers collide. For example:
|
||||
- QA `Left_001` is Z28061's left side; PROD `Left_001` is **Z28065**'s;
|
||||
- QA `MESReceiver_023` is Z28061-Left; on PROD it is Z28061-Left by coincidence, but `MESReceiver_025` is Z28062-Left on
|
||||
QA and Z28069-Left on PROD.
|
||||
|
||||
**If QA's bindings were copied unchanged, every PROD instance would read and write another reactor's tags, with
|
||||
Good quality and no error.** For that reason no instance or binding is carried over from QA. The PROD bindings were
|
||||
generated by **hierarchical name** instead:
|
||||
1. resolve QA `tag` → QA `Z2806x.Left.LeakTest`;
|
||||
2. look up the PROD object with the same hierarchical name;
|
||||
3. keep QA's reference style (`Left_0NN.LeakTest.<attr>`).
|
||||
|
||||
Every one of the 9×244 attributes was checked against the PROD object's attribute list; all of them exist. PROD
|
||||
objects (read 2026-11-22 from the vp03 gateway):
|
||||
|
||||
| Instance | Left | Right | Left LeakTest | Right LeakTest | Left MESReceiver | Right MESReceiver | DelmiaReceiver | Left TableAlarms | Right TableAlarms |
|
||||
|---|---|---|---|---|---|---|---|---|---|
|
||||
| Z28061 | Left_005 | Right_005 | LeakTest_009 | LeakTest_010 | MESReceiver_023 | MESReceiver_024 | DelmiaReceiver_043 | TableAlarms_009 | TableAlarms_010 |
|
||||
| Z28062 | Left_004 | Right_004 | LeakTest_007 | LeakTest_008 | MESReceiver_021 | MESReceiver_022 | DelmiaReceiver_042 | TableAlarms_007 | TableAlarms_008 |
|
||||
| Z28063 | Left_003 | Right_003 | LeakTest_005 | LeakTest_006 | MESReceiver_019 | MESReceiver_020 | DelmiaReceiver_041 | TableAlarms_005 | TableAlarms_006 |
|
||||
| Z28064 | Left_002 | Right_002 | LeakTest_003 | LeakTest_004 | MESReceiver_017 | MESReceiver_018 | DelmiaReceiver_040 | TableAlarms_003 | TableAlarms_004 |
|
||||
| Z28065 | Left_001 | Right_001 | LeakTest_001 | LeakTest_002 | MESReceiver_015 | MESReceiver_016 | DelmiaReceiver_039 | TableAlarms_001 | TableAlarms_002 |
|
||||
| Z28066 | Left_009 | Right_009 | LeakTest_017 | LeakTest_018 | MESReceiver_031 | MESReceiver_032 | DelmiaReceiver_047 | TableAlarms_017 | TableAlarms_018 |
|
||||
| Z28067 | Left_008 | Right_008 | LeakTest_015 | LeakTest_016 | MESReceiver_029 | MESReceiver_030 | DelmiaReceiver_046 | TableAlarms_015 | TableAlarms_016 |
|
||||
| Z28068 | Left_007 | Right_007 | LeakTest_013 | LeakTest_014 | MESReceiver_027 | MESReceiver_028 | DelmiaReceiver_045 | TableAlarms_013 | TableAlarms_014 |
|
||||
| Z28069 | Left_006 | Right_006 | LeakTest_011 | LeakTest_012 | MESReceiver_025 | MESReceiver_026 | DelmiaReceiver_044 | TableAlarms_011 | TableAlarms_012 |
|
||||
|
||||
Re-run the generator before applying if the PROD Galaxy is redeployed in the meantime. Contained objects get
|
||||
renumbered when they are recreated.
|
||||
|
||||
### 1.4 QA defects found; not copied, reported only
|
||||
|
||||
- **Z28061 and Z28062 carry 38 stale bindings each**, from DEV-era module names (`DelmiaRecv`,
|
||||
`Left/RightDelmiaReceiver`, `*.DelmiaJobStep`, `*.PID_AlarmString`, `*.LeakTest.MESMoveIn/Out`). They point at
|
||||
another machine's objects (Z28061 → Z28062's sides; Z28062 → Z28069's) and at attributes that don't exist in either
|
||||
Galaxy. They are harmless, but they are noise.
|
||||
- **The template's native alarm sources are hard-coded to Z28061-era QA objects**: `Z28061.`, `Left_001.`, and
|
||||
`LeakTest_002.` for both LeakTest sources. **Z28063–Z28069 have no overrides, so on QA they mirror Z28061's alarms.**
|
||||
Z28062's overrides are also off by one (`LeakTest_005/006`, `TableAlarms_005/006`; its real objects are
|
||||
`LeakTest_004/003` and `TableAlarms_004/003`).
|
||||
- `MantleTempHigh` watches only `RightReactorSide.MantleTemp` and fires on equality with `"600"`, not on ≥ 600.
|
||||
It is copied as is; the owner should decide whether that is intended.
|
||||
|
||||
### 1.5 Inbound API methods (central)
|
||||
|
||||
Inbound methods always run on the central. Each one looks up `SELECT TOP 1 Code FROM dbo.Machine WHERE SAPID=@s` on
|
||||
db-connection `BTDB`, then `Route.To(<Code>)` to the instance on whichever site hosts it, here site-par.
|
||||
|
||||
QA inbound traffic in the last 30 days (`audit query --channel ApiInbound`):
|
||||
|
||||
| Method | Calls (last) | Copy? |
|
||||
|---|---|---|
|
||||
| `MesMoveIn` | 103 by `MES_Key` (11-19) | yes |
|
||||
| `MesMoveOut` | 96 by `MES_Key` (11-19) | yes |
|
||||
| `SimpleAlarmStatusRequest` | 202 by `MES_Key` (11-19) | yes (returns an empty list today; `AlarmStatus` is a stub) |
|
||||
| `MesIsMoveInReady` / `MesIsMoveOutReady` | test key only | yes: read-only, and used as the PROD smoke test |
|
||||
| `DelmiaRecipeDownload` | none | yes: the Delmia path. PROD Delmia caller is `dnc-app-vp01` |
|
||||
| `MesSampleData` | none | yes (owner may drop it) |
|
||||
| `IpsenMESMoveIn` | none | **no** (recommended): legacy, superseded by `MesMoveIn`, routes to the legacy `IpsenMoveIn` script |
|
||||
|
||||
### 1.6 BTDB records (QA BT `wondersqlqa` = WONDER-SQL-VQ03, DB `BT`, read 2026-11-22)
|
||||
|
||||
`MesMoveIn` and the other methods resolve `SAPID → dbo.Machine.Code`, and `Code` must equal the ScadaBridge instance
|
||||
name. The reactors' own Galaxy scripts also open batches in BT by machine code (`StartMachineBatch` and the rest).
|
||||
So PROD BT needs the same records before any machine is used.
|
||||
|
||||
QA has one group and nine machines, and no `MachineAlarm` rows for them:
|
||||
|
||||
| MachineGroup | Name | Description | Parent | Members |
|
||||
|---|---|---|---|---|
|
||||
| `CVD_Reactors` | CVD Reactors | CVD Reactors in Parsippany, NJ | none | Z28061–Z28069 |
|
||||
|
||||
| Code | Name | ZTag | SAPID | Description |
|
||||
|---|---|---|---|---|
|
||||
| Z28061 | T5 | Z28061 | 103559 | Z28061 Table 5 |
|
||||
| Z28062 | T4 | Z28062 | 103563 | CVD Reactors in Parsippany, NJ |
|
||||
| Z28063 | T3 | Z28063 | 103564 | 〃 |
|
||||
| Z28064 | T2 | Z28064 | 103565 | 〃 |
|
||||
| Z28065 | T1 | Z28065 | 103566 | 〃 |
|
||||
| Z28066 | T9 | Z28066 | 103567 | 〃 |
|
||||
| Z28067 | T8 | Z28067 | 103568 | 〃 |
|
||||
| Z28068 | T7 | Z28068 | 103569 | 〃 |
|
||||
| Z28069 | T6 | Z28069 | 103570 | Z28069 Table 6 |
|
||||
|
||||
Common to all nine: TimeZone `Eastern Standard Time`, `MultipleBatch`/`MultipleCycle` 0, Active 1, `OtherData` `{}`.
|
||||
|
||||
`Name` is the table number. The two descriptions that differ (Z28061, Z28069) are copied as they are.
|
||||
|
||||
MES sends `<SAPID>_A|_B[_LT]`, e.g. `103564_A`. The inbound method uses the leading digits for the lookup, and the
|
||||
machine script uses the suffix to pick the side.
|
||||
|
||||
**PROD BT already has these records (checked 2026-11-22).**
|
||||
- **Database:** PROD BT is `wondersqlpd` = WONDER-SQL-VP03, DB `BT`. The SQL login `wonderapp` (from `~/.zshenv`,
|
||||
`HISTORIAN_SQL_USER`/`_PASSWORD`) works there with `db_datareader` + `db_datawriter`, INSERT on
|
||||
`Machine`/`MachineGroup`/`MachineGroupMembership`, and SELECT on `Runtime.dbo.Timezone`. NAM\dohertj2 and
|
||||
NAM\adm_dohertj2 cannot log in.
|
||||
- **Who created them:** marting4, on 2026-11-21 at 04:03Z: group `CVD_Reactors` (id 20) with all nine machines
|
||||
(MachineID 119–127) as members.
|
||||
- **Match with QA:** every field is identical to QA (Code, Name, ZTag, SAPID, Description, TimeZone, flags, Active,
|
||||
OtherData, group membership, and no `MachineAlarm` rows). There are no batches yet.
|
||||
- **Schema difference:** PROD BT's `MachineGroup` predates the DARS sprint-1 schema and has **no
|
||||
`ParentMachineGroupID`** column. The script was corrected so it doesn't name that column.
|
||||
|
||||
[`../deploy/2026-11-22-prod-cvd-content/btdb/prod-bt-cvd-machines.sql`](../deploy/2026-11-22-prod-cvd-content/btdb/prod-bt-cvd-machines.sql)
|
||||
is kept as a re-check:
|
||||
- **Section 1** is a read-only preflight. It lists the server and database, rows that already exist, and conflicts:
|
||||
a Code with a different SAPID or ZTag, a SAPID or ZTag used by another machine, or a time zone missing from
|
||||
`Runtime.dbo.Timezone`.
|
||||
- **Section 2** sits behind a `RETURN` guard. It inserts only what is missing, in one transaction, never updates or
|
||||
deletes, and `THROW`s on any conflict.
|
||||
- **Result on 2026-11-22:** section 1 was run as `wonderapp` against PROD BT and QA BT, and the transaction was rolled
|
||||
back. Both show only "exists" rows (9 machines + the group) and no conflicts.
|
||||
- **No insert is needed.** The BTDB Manager's config import was not usable anyway: it writes only into the BT
|
||||
database it is connected to, which is DEV.
|
||||
|
||||
### 1.7 What PROD has today
|
||||
|
||||
PROD (`wonder-app-vp03:8085`) holds no templates, instances, API methods, db-connections, API keys or areas.
|
||||
|
||||
Sites:
|
||||
- `site-par` **id 1** on par-vp03/04; data connection **id 1 `MxGateway`** → par-vp03:5120 / par-vp04:5120, Connected;
|
||||
- `site-app` id 2 on the app boxes, connection id 2. **Not used here.**
|
||||
|
||||
### 1.8 The `BTDB` db-connection on QA, and what PROD gets
|
||||
|
||||
QA ScadaBridge has one db-connection, **`BTDB` (id 1)**. Its connection string is encrypted at rest. It was decrypted
|
||||
on the Mac on 2026-11-22 from the QA config DB (the key ring is stored unencrypted there) and read with the password
|
||||
redacted:
|
||||
|
||||
```
|
||||
QA: Server=wondersqlqa.zmr.zimmer.com;Database=BT;User Id=wonderapp;Password=***;TrustServerCertificate=True;MultiSubnetFailover=True
|
||||
PROD: Server=wondersqlpd.zmr.zimmer.com;Database=BT;User Id=wonderapp;Password=***;TrustServerCertificate=True;MultiSubnetFailover=True
|
||||
```
|
||||
|
||||
- **Login:** `wonderapp` on PROD BT is proven (§1.6).
|
||||
- **Encryption:** no `Encrypt` keyword is given. Microsoft.Data.SqlClient then defaults to encrypting, and
|
||||
`TrustServerCertificate=True` skips the CA check, exactly as on QA.
|
||||
- **Failover:** `MultiSubnetFailover=True` is required because `wondersqlpd` is an AG listener.
|
||||
- **Name:** the connection must be named **`BTDB`**. Every inbound method and both site scripts address it by that
|
||||
name (`Database.QuerySingleAsync("BTDB", …)` and `Database.Connection("BTDB")`).
|
||||
- **Helper:** [`apply-btdb-connection.sh`](../deploy/2026-11-22-prod-cvd-content/apply-btdb-connection.sh) builds the
|
||||
string in a 0600 temp file and passes it with `--connection-string-file`, so the password never appears on argv or
|
||||
in the repo.
|
||||
|
||||
## 2. Import path, tested with `bundle preview` on PROD
|
||||
|
||||
- **Templates:** `bundle export --templates CvdReactor --include-dependencies` on QA gives 11 templates. Previewed on
|
||||
PROD: **11 adds, 0 blockers**, no site or connection mappings, no QA hostnames. The bundle is stored at
|
||||
`../deploy/2026-11-22-prod-cvd-content/qa-export/cvdreactor-templates.scadabundle`
|
||||
(sha256 `6dcdc453…235e3`). The connection name `MxGateway` in the native alarm sources matches PROD.
|
||||
- **API methods:** the bundle **is blocked**. Every method gets a blocker on `System` (from `System.Func<…>`), and
|
||||
`SimpleAlarmStatusRequest` also gets one on `Array` (`Array.Empty`). The import reference scanner reads those as
|
||||
missing SharedScripts or ExternalSystems. This is a false positive in ScadaBridge (issue to be filed). The workaround
|
||||
is to create the methods with `api-method create`, using the definitions exported to
|
||||
`qa-export/api-methods.json`. Those definitions hold scripts and schemas only; there are no keys in them.
|
||||
- **Instances, bindings, API keys and the db-connection are created on PROD directly.** They are never imported from
|
||||
QA.
|
||||
|
||||
## 3. Decisions and inputs needed before running
|
||||
|
||||
| # | Item | Recommendation | Blocks |
|
||||
|---|---|---|---|
|
||||
| C1 | **ScadaBridge `BTDB` db-connection on PROD (§1.8):** mirror QA's, with only the server changed. It is used by the central (the SAPID lookup in every inbound method) **and** by site-par (`MesMoveOut`/`MesSampleData` cycle data). Still unverified: the path from par-vp03/04 → `wondersqlpd:1433`. The centrals already reach `wondersqlpd` for the ScadaBridge config DB. | Use the same login as QA (`wonderapp`, password from `~/.zshenv`). Ask the DBA for a read-only BT login later, since the scripts only `SELECT`. Prove the PAR path with the first `MesMoveOut`/`MesSampleData` call after cutover; a failure there is best-effort and does not fail the move-out | Steps 3 and 6 |
|
||||
| C2 | **PROD BT records:** ✅ already present and identical to QA (§1.6; created by marting4 2026-11-21) | Nothing to do. Step 0 only re-checks | none |
|
||||
| C3 | Area on site-par | `CVDAisle_1`, matching the Galaxy. QA's name is `Aisle001` | Step 5 |
|
||||
| C4 | **mxgw alarm area** (open since 11-20). Native alarm mirroring returns nothing while gateway alarms are off; computed alarms still work. | `NAM`, which covers CVDAisle_1. It is set on all four gateways, which needs a gateway restart and is its own deploy step | Native alarms only |
|
||||
| C5 | **Cutover (Q9).** QA's Galaxy has its own copy of these nine reactors, on `OI_WAR_PAR_MBTCP`, and MES `MES_Key` drives them through QA ScadaBridge today. | Deploy on PROD whenever convenient (the instances are passive). **Cut over by switching the MES and Delmia callers to PROD**, one stack per machine. After that, disable the QA instances, or leave them if MES no longer calls QA | Step 9 |
|
||||
| C6 | Which URL MES and Delmia call. There is no VIP in front of vp03/vp04:8085. | Owner/IT: a DNS alias or LB for the active central, or the callers fail over between both | Step 9 |
|
||||
| C7 | API key names | `MES_Key` (all copied methods except Delmia) and `delmia-notifier` (`DelmiaRecipeDownload`). Hand both over out of band; never put them in chat or a repo | Step 8 |
|
||||
|
||||
Not needed: #60. The mxgw `galaxy-sql` 503 only affects Galaxy browse; MXAccess reads and writes work, and site-par is
|
||||
Connected.
|
||||
|
||||
## 4. Steps (management API through the CLI, from the Mac; no WinRM; each step gets an owner go)
|
||||
|
||||
Use `sbp=(… --url http://wonder-app-vp03.zmr.zimmer.com:8085 --username dohertj2 --password-file <0600>)`. Pass
|
||||
secrets only through `--*-file`.
|
||||
|
||||
0. **BTDB records (C2): re-check only.** The records already exist on PROD BT.
|
||||
- Run section 1 of `btdb/prod-bt-cvd-machines.sql` as `wonderapp` on `wondersqlpd`/`BT`. Expect 9 machines and
|
||||
the group as "exists", and no `CONFLICT` rows.
|
||||
- Only if a row has gone missing: remove the `RETURN` guard and run the whole script. It inserts only the missing
|
||||
rows.
|
||||
1. **Re-validate the mapping.** Re-run the Galaxy read and generator. Stop if any PROD tag name changed since
|
||||
2026-11-22.
|
||||
2. **Templates.**
|
||||
- `bundle preview --input cvdreactor-templates.scadabundle` must still show 11 adds and 0 blockers.
|
||||
- Then `bundle import`, with conflict policy `fail`/`skip` (nothing exists).
|
||||
- Verify: `template list` shows the 11, and `template validate --id <CvdReactor>` passes.
|
||||
3. **BTDB db-connection (C1, §1.8).**
|
||||
- Run `apply-btdb-connection.sh <sbp wrapper>`.
|
||||
- `db-connection list` must show `BTDB`.
|
||||
- Then run `deploy artifacts --site-id 1`, which ships the db-connection to site-par for the two site scripts that
|
||||
read BT.
|
||||
- The central uses it directly for the inbound methods, so they need no deploy.
|
||||
- There is no built-in test-connection. The first proof is step 9: a ready-check call does the SAPID lookup
|
||||
through `BTDB`.
|
||||
4. **Inbound API methods (central, §1.5).**
|
||||
- First run `apply-api-methods.sh <sbp wrapper> --dry`, then the same without `--dry`.
|
||||
- It creates these from `qa-export/api-methods.json`, with the same script, parameter and return schemas,
|
||||
timeout and trace flag as QA:
|
||||
|
||||
| Method | Timeout | Required parameters | Used on QA by |
|
||||
|---|---|---|---|
|
||||
| `MesMoveIn` | 46 s | SAPID, JobSequenceNumber, WorkOrders, OperatorName | MES (`MES_Key`) |
|
||||
| `MesMoveOut` | 45 s | SAPID, WorkOrders, OperatorName | MES (`MES_Key`) |
|
||||
| `SimpleAlarmStatusRequest` | 30 s | (SAPID) | MES (`MES_Key`) |
|
||||
| `MesIsMoveInReady` | 30 s | SAPID | test key; read-only |
|
||||
| `MesIsMoveOutReady` | 30 s | SAPID | test key; read-only |
|
||||
| `MesSampleData` | 30 s | ContainerNumber | none |
|
||||
| `DelmiaRecipeDownload` | 45 s | (MachineCode, …) | none; the Delmia path |
|
||||
|
||||
- `--include-legacy` also creates `IpsenMESMoveIn`. Leave it out unless MES confirms it still calls that method.
|
||||
- Verify: `api-method list` shows all 7, and `api-method get` for each matches the QA JSON.
|
||||
- All 7 route with `Route.To(<Machine.Code>)` to the instances on site-par, so they work only after step 6/7.
|
||||
5. **Area.** `site area create --site-id 1 --name CVDAisle_1` (C3).
|
||||
6. **Instances, one machine first.** Pick an idle one, e.g. Z28063.
|
||||
- `instance create --name Z28063 --template-id <CvdReactor id> --site-id 1 --area-id <id>`.
|
||||
- `instance set-bindings --id <n> --bindings "$(cat bindings/Z28063.json)"`. That is 244 entries, connection 1.
|
||||
It upserts, and the instance is new.
|
||||
- `instance native-alarm-source import --instance-id <n> --file alarm-sources/Z28063.csv`. That is all 7
|
||||
sources, so the QA-era template defaults are never used.
|
||||
- `instance diff` shows 244 bindings and 7 overrides.
|
||||
- `deploy instance --id <n>`.
|
||||
- **Gate:**
|
||||
- `debug snapshot --id <n>`: attributes Good at the same rate as the Galaxy shows. An idle side shows some
|
||||
source-Bad, so compare with the gateway read, not with 100 %.
|
||||
- Spot-check 3 values against the Galaxy: a root UDA, a side attribute and a `LeakTest.*` attribute.
|
||||
- site-par active node logs clean.
|
||||
- QA unaffected.
|
||||
7. **Remaining eight.** Same as step 6, in two batches. Then `deploy artifacts --site-id 1` is no longer needed after
|
||||
restarts: the instances now reference connection 1, so it is rebuilt on boot.
|
||||
8. **API keys.** `security api-key create --name MES_Key --methods MesMoveIn,MesMoveOut,SimpleAlarmStatusRequest,MesIsMoveInReady,MesIsMoveOutReady,MesSampleData`
|
||||
and `--name delmia-notifier --methods DelmiaRecipeDownload`. Save each token straight to the Keychain
|
||||
(`zb-prod/sb-inbound-<name>`); it is shown only once.
|
||||
9. **Smoke test.** This step is read-only on the machines.
|
||||
- `POST /api/MesIsMoveInReady` with `{}` → 400 `VALIDATION_FAILED`, which proves the key and the route.
|
||||
- Then a real SAPID for each machine, `<SAPID>_A` and `_B` (e.g. `103564_A` for Z28063 Left; SAPIDs in §1.6) → 200 with `IsMoveInReady` true or false, matching the
|
||||
Galaxy `MoveInReadyFlag`. That proves BTDB lookup → `Route.To` → site-par → correct side, **with no write.**
|
||||
- `SimpleAlarmStatusRequest` → 200 with an empty list.
|
||||
10. **Cutover (C5/C6), owner and MES/Delmia teams.**
|
||||
- Point the MES and Delmia callers at PROD with the new keys.
|
||||
- Watch the first real `MesMoveIn`/`MesMoveOut` per machine in `audit query --channel ApiInbound`, and in the
|
||||
Flow Debugger.
|
||||
- Then disable the QA instances, or keep QA for testing against its own Galaxy.
|
||||
- **This is the point of no return for consumers. Before it, rollback means deleting the PROD content.**
|
||||
11. **Records.**
|
||||
- A deploy record in `ScadaBridge/docs/deployment/deployment-records/`.
|
||||
- Update the PROD plan §0.1a.
|
||||
- Memory note.
|
||||
|
||||
## 5. Rollback
|
||||
|
||||
- **Before step 10**, on PROD: `instance delete` ×9, then `api-method delete`, `template delete` (derived templates
|
||||
before bases), `db-connection delete`, `security api-key delete`, `deploy artifacts --site-id 1`. Nothing outside
|
||||
ScadaBridge's config DB changes, and QA keeps serving MES throughout.
|
||||
- **After step 10:** point the callers back at QA.
|
||||
- **BT records:** none to roll back. They existed before this plan (marting4, 2026-11-21) and are owned outside it.
|
||||
|
||||
## 6. Follow-ups to file
|
||||
|
||||
- ScadaBridge: the bundle import reference scanner flags `System.*` and `Array.*` in API method scripts as missing
|
||||
SharedScripts/ExternalSystems. That blocks every inbound method from bundles.
|
||||
- ScadaBridge QA config (§1.4): stale bindings on Z28061/Z28062; native alarm sources on Z28062–Z28069; check
|
||||
`MantleTempHigh`.
|
||||
- The open mxgw alarm-area decision (C4) now has a consumer.
|
||||
Reference in New Issue