Files
scadaproj/docs/plans/2026-11-22-prod-cvd-content-copy.md
T
Joseph Doherty 1ab2bca41d deploy(prod): CVD reactor content (Phase 7) — QA→PROD templates, API methods, BTDB, Z28061–Z28069 on site-par; mxgw SQL login + PAR NewJersey alarms
Plan docs/plans/2026-11-22-prod-cvd-content-copy.md with the QA findings, the hierarchical-name
binding remap (QA and PROD reuse Galaxy suffixes for different machines), BT checks, the run
status and the QA reactor disable. Generated inputs under docs/deploy/2026-11-22-prod-cvd-content/
(bindings, alarm-source overrides, mapping, QA export, BT preflight SQL, helper scripts; no secrets).
PROD plan §0.1a rows for the content run and the mxgw changes.

Claude-Session: https://claude.ai/code/session_01GT67AD5mc2BnaaAfY3hqqQ
2026-11-22 12:06:04 -05:00

26 KiB
Raw Blame History

PROD content: copy the CVD reactor templates and inbound API methods from QA, and configure Z28061–Z28069 (plan, 2026-11-22)

Owner, 2026-11-22: "investigate the templates in use on QA scadabridge. how the tags are mapped, etc. Then generate a plan on how to copy them to prod, copy the api methods used too, and configure the machine in the attached screenshot. note the template instances should run on the par server cluster, the api methods can run on the central server." The screenshot shows Galaxy NAM / NewJersey / CVDAisle_1 / Z28061…Z28069.

This is Phase 7 of 2026-11-19-prod-scadabridge-mxgw-install.md. Status 2026-11-22 16:50Z: steps 0–9 DONE on PROD (record ScadaBridge docs/deployment/deployment-records/2026-11-22-prod-cvd-reactors-content.md). Step 10 (cutover) is with the owner and the MES/Delmia teams. The keys are MES_Key with QA's grants minus IpsenMESMoveIn (so DelmiaRecipeDownload is included), and delmia-notifier. Delmia sends the plain MachineCode (Z28063).

Before the run, everything was read-only:

  • the QA management API (lists, get, bundle export, audit query);
  • QA Galaxy ZB over SQL as NAM\dohertj2;
  • PROD Galaxy browse through vp03's gateway with the scadabridge-prod key (metadata:read);
  • bundle preview on PROD, which does not apply anything.

The generated inputs are in ../deploy/2026-11-22-prod-cvd-content/.

0. Run status (2026-11-22, owner: "start the plan but wait to deploy to the par sites")

Steps 0–6 were done on the PROD central through the management API. Nothing has been deployed to any site: deploy status shows 0 deployments, and both sites' artifactsDeployedAt are unchanged. Run log: scratchpad run/run-log.md.

Step Result IDs
0 BT re-check 9 machines + CVD_Reactors exist, no conflicts n/a
1 Mapping Galaxy re-read: 108 objects, identical to mapping.md n/a
2 Templates 11 imported (--on-conflict skip, 0 blockers) ids 1–11; CvdReactor = 5
3 BTDB db-connection created; deploy artifacts held id 1
4 API methods 7 created; identical to the QA JSON 1 MesMoveIn, 2 MesMoveOut, 3 DelmiaRecipeDownload, 4 SimpleAlarmStatusRequest, 5 MesSampleData, 6 MesIsMoveInReady, 7 MesIsMoveOutReady
5 Area CVDAisle_1 on site-par area 1
6 Instances created with 244 bindings (connection 1) and 7 alarm-source overrides each; Disabled, not deployed Z28063=1, Z28061=2, Z28062=3, Z28064=4, Z28065=5, Z28066=6, Z28067=7, Z28068=8, Z28069=9

Held, waiting on the owner's go:

  • deploy artifacts --site-id 1;
  • deploy and enable of the instances (steps 6/7);
  • API keys (step 8);
  • smoke test (step 9);
  • cutover (step 10).

QA reactors disabled 2026-11-22 16:38Z (owner: "disable the machines in qa"):

  • instance disable on QA ids 1, 2, 9, 11, 12, 13, 10, 14, 15 (Z28061–Z28069) all returned success; instance list shows state 2 (Disabled) for all nine.
  • The QA site no longer runs them: a debug snapshot of Z28063 returns instanceNotFound.
  • WarmCanary (still enabled) and ZIPSEN (already disabled) were not touched.
  • The last MES call to QA was at 2026-11-19 18:26Z. From now on, MES/Delmia calls to QA for these machines fail until the callers move to PROD.
  • To undo: instance enable + deploy instance for those ids on QA.

Notes from the run:

  • template validate --id 5 reports 3 errors: alarms Left/RightMTALockout and MantleTempHigh reference *ReactorSide.MTA_Lockout/MantleTemp, which it calls "not in the flattened configuration". QA's CvdReactor gives the same 3 errors, yet QA deployed Z28063 successfully on 2026-11-15, after those alarms were created (09-30 and 10-22). So this looks like a false positive in template validate for members of composed, derived templates; it is not a deploy blocker. Watch the first PROD deploy anyway.
  • QA's RightMESReceiver template is missing 14 inherited attribute rows and 2 inherited scripts. PROD's copy (id 9) is complete. This is a QA-side defect only.

1. What QA runs (findings)

1.1 Templates (QA ScadaBridge wonder-app-vq03:8085, site site-a id 2, area Aisle001)

Template Role Members
CvdReactor (id 1) The machine. One instance per reactor 16 attributes (machine UDAs: ChlorineFlow, HydrogenFlow, TrunkPressure, Heartbeat*, LeakTest*, MachineCode/ID/Description, …); 3 computed alarms; 8 scripts; 7 native alarm sources; 5 compositions
↳ LeftMESReceiver / RightMESReceiver Derived from MESReceiver (id 3) 26 attributes each: MoveIn* and MoveOut* handshake tags plus ScanStateCmd. The base carries the MoveIn/MoveOut scripts
↳ LeftReactorSide / RightReactorSide Derived from ReactorSide (id 7, "Galaxy $Reactor_Side") 60 attributes plus composed LeakTest (23 attributes)
↳ DelmiaReceiver Derived from DelmiaReceiver (id 12) 10 attributes: ReadyFlag, RecipeDownloadFlag, RecipeProcessedFlag, RecipeProcessResult[Text], DownloadPath, WorkOrderNumber, PartNumber, JobStepNumber, Username

Not copied, because they are QA test content: IpsenSim + its MESReceiver (instance ZIPSEN), WarmCanary (the OtOpcUa Warm monitor), and the standalone LeakTest base, which comes along anyway as a dependency.

Scripts on CvdReactor. All of them are Call-triggered: there are no timers and no value-change triggers.

  • MesMoveIn, MesMoveOut, MesIsMoveInReady, MesIsMoveOutReady and MesSampleData parse <SAPID>_A|_B[_LT] and pick Children[side+"MESReceiver"].
  • ProcessRecipeDownload uses Children["DelmiaReceiver"].
  • AlarmStatus is a stub that returns an empty list.
  • IpsenMoveIn is legacy.
  • MesMoveOut and MesSampleData also read BTDB on the site (Database.Connection("BTDB"), best-effort cycle data).

The computed alarms (MantleTempHigh, Left/RightMTALockout) only read values. So a deployed instance is passive. It reads tags and evaluates alarms, and writes nothing to the Galaxy until an inbound API call reaches it.

1.2 Tag mapping

Every template attribute's data-source reference is just its own name (e.g. ChlorineFlow). Every Galaxy address comes from a per-instance connection binding (dataSourceReferenceOverride) on data connection 1 MxGateway. The Galaxy shape is the same in both galaxies:

Z2806x ($CVDReactor)                       → instance root attributes        Z2806x.<attr>
├─ DelmiaReceiver  (DelmiaReceiver_0NN)     → DelmiaReceiver.<attr>           DelmiaReceiver_0NN.<attr>
├─ Left  ($Reactor_Side, Left_0NN)          → LeftReactorSide.<attr>          Left_0NN.<attr>
│   ├─ LeakTest    (LeakTest_0NN)           → LeftReactorSide.LeakTest.<attr> Left_0NN.LeakTest.<attr>
│   ├─ MESReceiver (MESReceiver_0NN)        → LeftMESReceiver.<attr>          MESReceiver_0NN.<attr>
│   ├─ Setpoints, TableAlarms               → (not bound; TableAlarms feeds a native alarm source)
└─ Right  (same as Left)

There are 244 bindings per machine: 16 root, 2×26 MES, 2×83 side (including LeakTest), and 10 Delmia.

Native alarm sources mirror Galaxy alarms by object prefix:

  • ReactorAlarms = Z2806x.;
  • Left/RightSideAlarms = Left_0NN.;
  • Left/RightLeakTestAlarms = LeakTest_0NN.;
  • Left/RightTableAlarms = TableAlarms_0NN..

1.3 ⚠ PROD reuses the same tag names for different machines

QA's and PROD's Galaxies number their contained objects differently, and the numbers collide. For example:

  • QA Left_001 is Z28061's left side; PROD Left_001 is Z28065's;
  • QA MESReceiver_023 is Z28061-Left; on PROD it is Z28061-Left by coincidence, but MESReceiver_025 is Z28062-Left on QA and Z28069-Left on PROD.

If QA's bindings were copied unchanged, every PROD instance would read and write another reactor's tags, with Good quality and no error. For that reason no instance or binding is carried over from QA. The PROD bindings were generated by hierarchical name instead:

  1. resolve QA tag → QA Z2806x.Left.LeakTest;
  2. look up the PROD object with the same hierarchical name;
  3. keep QA's reference style (Left_0NN.LeakTest.<attr>).

Every one of the 9×244 attributes was checked against the PROD object's attribute list; all of them exist. PROD objects (read 2026-11-22 from the vp03 gateway):

Instance Left Right Left LeakTest Right LeakTest Left MESReceiver Right MESReceiver DelmiaReceiver Left TableAlarms Right TableAlarms
Z28061 Left_005 Right_005 LeakTest_009 LeakTest_010 MESReceiver_023 MESReceiver_024 DelmiaReceiver_043 TableAlarms_009 TableAlarms_010
Z28062 Left_004 Right_004 LeakTest_007 LeakTest_008 MESReceiver_021 MESReceiver_022 DelmiaReceiver_042 TableAlarms_007 TableAlarms_008
Z28063 Left_003 Right_003 LeakTest_005 LeakTest_006 MESReceiver_019 MESReceiver_020 DelmiaReceiver_041 TableAlarms_005 TableAlarms_006
Z28064 Left_002 Right_002 LeakTest_003 LeakTest_004 MESReceiver_017 MESReceiver_018 DelmiaReceiver_040 TableAlarms_003 TableAlarms_004
Z28065 Left_001 Right_001 LeakTest_001 LeakTest_002 MESReceiver_015 MESReceiver_016 DelmiaReceiver_039 TableAlarms_001 TableAlarms_002
Z28066 Left_009 Right_009 LeakTest_017 LeakTest_018 MESReceiver_031 MESReceiver_032 DelmiaReceiver_047 TableAlarms_017 TableAlarms_018
Z28067 Left_008 Right_008 LeakTest_015 LeakTest_016 MESReceiver_029 MESReceiver_030 DelmiaReceiver_046 TableAlarms_015 TableAlarms_016
Z28068 Left_007 Right_007 LeakTest_013 LeakTest_014 MESReceiver_027 MESReceiver_028 DelmiaReceiver_045 TableAlarms_013 TableAlarms_014
Z28069 Left_006 Right_006 LeakTest_011 LeakTest_012 MESReceiver_025 MESReceiver_026 DelmiaReceiver_044 TableAlarms_011 TableAlarms_012

Re-run the generator before applying if the PROD Galaxy is redeployed in the meantime. Contained objects get renumbered when they are recreated.

1.4 QA defects found; not copied, reported only

  • Z28061 and Z28062 carry 38 stale bindings each, from DEV-era module names (DelmiaRecv, Left/RightDelmiaReceiver, *.DelmiaJobStep, *.PID_AlarmString, *.LeakTest.MESMoveIn/Out). They point at another machine's objects (Z28061 → Z28062's sides; Z28062 → Z28069's) and at attributes that don't exist in either Galaxy. They are harmless, but they are noise.
  • The template's native alarm sources are hard-coded to Z28061-era QA objects: Z28061., Left_001., and LeakTest_002. for both LeakTest sources. Z28063–Z28069 have no overrides, so on QA they mirror Z28061's alarms. Z28062's overrides are also off by one (LeakTest_005/006, TableAlarms_005/006; its real objects are LeakTest_004/003 and TableAlarms_004/003).
  • MantleTempHigh watches only RightReactorSide.MantleTemp and fires on equality with "600", not on ≥ 600. It is copied as is; the owner should decide whether that is intended.

1.5 Inbound API methods (central)

Inbound methods always run on the central. Each one looks up SELECT TOP 1 Code FROM dbo.Machine WHERE SAPID=@s on db-connection BTDB, then Route.To(<Code>) to the instance on whichever site hosts it, here site-par.

QA inbound traffic in the last 30 days (audit query --channel ApiInbound):

Method Calls (last) Copy?
MesMoveIn 103 by MES_Key (11-19) yes
MesMoveOut 96 by MES_Key (11-19) yes
SimpleAlarmStatusRequest 202 by MES_Key (11-19) yes (returns an empty list today; AlarmStatus is a stub)
MesIsMoveInReady / MesIsMoveOutReady test key only yes: read-only, and used as the PROD smoke test
DelmiaRecipeDownload none yes: the Delmia path. PROD Delmia caller is dnc-app-vp01
MesSampleData none yes (owner may drop it)
IpsenMESMoveIn none no (recommended): legacy, superseded by MesMoveIn, routes to the legacy IpsenMoveIn script

1.6 BTDB records (QA BT wondersqlqa = WONDER-SQL-VQ03, DB BT, read 2026-11-22)

MesMoveIn and the other methods resolve SAPID → dbo.Machine.Code, and Code must equal the ScadaBridge instance name. The reactors' own Galaxy scripts also open batches in BT by machine code (StartMachineBatch and the rest). So PROD BT needs the same records before any machine is used.

QA has one group and nine machines, and no MachineAlarm rows for them:

MachineGroup Name Description Parent Members
CVD_Reactors CVD Reactors CVD Reactors in Parsippany, NJ none Z28061–Z28069
Code Name ZTag SAPID Description
Z28061 T5 Z28061 103559 Z28061 Table 5
Z28062 T4 Z28062 103563 CVD Reactors in Parsippany, NJ
Z28063 T3 Z28063 103564 〃
Z28064 T2 Z28064 103565 〃
Z28065 T1 Z28065 103566 〃
Z28066 T9 Z28066 103567 〃
Z28067 T8 Z28067 103568 〃
Z28068 T7 Z28068 103569 〃
Z28069 T6 Z28069 103570 Z28069 Table 6

Common to all nine: TimeZone Eastern Standard Time, MultipleBatch/MultipleCycle 0, Active 1, OtherData {}.

Name is the table number. The two descriptions that differ (Z28061, Z28069) are copied as they are.

MES sends <SAPID>_A|_B[_LT], e.g. 103564_A. The inbound method uses the leading digits for the lookup, and the machine script uses the suffix to pick the side.

PROD BT already has these records (checked 2026-11-22).

  • Database: PROD BT is wondersqlpd = WONDER-SQL-VP03, DB BT. The SQL login wonderapp (from ~/.zshenv, HISTORIAN_SQL_USER/_PASSWORD) works there with db_datareader + db_datawriter, INSERT on Machine/MachineGroup/MachineGroupMembership, and SELECT on Runtime.dbo.Timezone. NAM\dohertj2 and NAM\adm_dohertj2 cannot log in.
  • Who created them: marting4, on 2026-11-21 at 04:03Z: group CVD_Reactors (id 20) with all nine machines (MachineID 119–127) as members.
  • Match with QA: every field is identical to QA (Code, Name, ZTag, SAPID, Description, TimeZone, flags, Active, OtherData, group membership, and no MachineAlarm rows). There are no batches yet.
  • Schema difference: PROD BT's MachineGroup predates the DARS sprint-1 schema and has no ParentMachineGroupID column. The script was corrected so it doesn't name that column.

../deploy/2026-11-22-prod-cvd-content/btdb/prod-bt-cvd-machines.sql is kept as a re-check:

  • Section 1 is a read-only preflight. It lists the server and database, rows that already exist, and conflicts: a Code with a different SAPID or ZTag, a SAPID or ZTag used by another machine, or a time zone missing from Runtime.dbo.Timezone.
  • Section 2 sits behind a RETURN guard. It inserts only what is missing, in one transaction, never updates or deletes, and THROWs on any conflict.
  • Result on 2026-11-22: section 1 was run as wonderapp against PROD BT and QA BT, and the transaction was rolled back. Both show only "exists" rows (9 machines + the group) and no conflicts.
  • No insert is needed. The BTDB Manager's config import was not usable anyway: it writes only into the BT database it is connected to, which is DEV.

1.7 What PROD has today

PROD (wonder-app-vp03:8085) holds no templates, instances, API methods, db-connections, API keys or areas.

Sites:

  • site-par id 1 on par-vp03/04; data connection id 1 MxGateway → par-vp03:5120 / par-vp04:5120, Connected;
  • site-app id 2 on the app boxes, connection id 2. Not used here.

1.8 The BTDB db-connection on QA, and what PROD gets

QA ScadaBridge has one db-connection, BTDB (id 1). Its connection string is encrypted at rest. It was decrypted on the Mac on 2026-11-22 from the QA config DB (the key ring is stored unencrypted there) and read with the password redacted:

QA:   Server=wondersqlqa.zmr.zimmer.com;Database=BT;User Id=wonderapp;Password=***;TrustServerCertificate=True;MultiSubnetFailover=True
PROD: Server=wondersqlpd.zmr.zimmer.com;Database=BT;User Id=wonderapp;Password=***;TrustServerCertificate=True;MultiSubnetFailover=True
  • Login: wonderapp on PROD BT is proven (§1.6).
  • Encryption: no Encrypt keyword is given. Microsoft.Data.SqlClient then defaults to encrypting, and TrustServerCertificate=True skips the CA check, exactly as on QA.
  • Failover: MultiSubnetFailover=True is required because wondersqlpd is an AG listener.
  • Name: the connection must be named BTDB. Every inbound method and both site scripts address it by that name (Database.QuerySingleAsync("BTDB", …) and Database.Connection("BTDB")).
  • Helper: apply-btdb-connection.sh builds the string in a 0600 temp file and passes it with --connection-string-file, so the password never appears on argv or in the repo.

2. Import path, tested with bundle preview on PROD

  • Templates: bundle export --templates CvdReactor --include-dependencies on QA gives 11 templates. Previewed on PROD: 11 adds, 0 blockers, no site or connection mappings, no QA hostnames. The bundle is stored at ../deploy/2026-11-22-prod-cvd-content/qa-export/cvdreactor-templates.scadabundle (sha256 6dcdc453…235e3). The connection name MxGateway in the native alarm sources matches PROD.
  • API methods: the bundle is blocked. Every method gets a blocker on System (from System.Func<…>), and SimpleAlarmStatusRequest also gets one on Array (Array.Empty). The import reference scanner reads those as missing SharedScripts or ExternalSystems. This is a false positive in ScadaBridge (issue to be filed). The workaround is to create the methods with api-method create, using the definitions exported to qa-export/api-methods.json. Those definitions hold scripts and schemas only; there are no keys in them.
  • Instances, bindings, API keys and the db-connection are created on PROD directly. They are never imported from QA.

3. Decisions and inputs needed before running

# Item Recommendation Blocks
C1 ScadaBridge BTDB db-connection on PROD (§1.8): mirror QA's, with only the server changed. It is used by the central (the SAPID lookup in every inbound method) and by site-par (MesMoveOut/MesSampleData cycle data). Still unverified: the path from par-vp03/04 → wondersqlpd:1433. The centrals already reach wondersqlpd for the ScadaBridge config DB. Use the same login as QA (wonderapp, password from ~/.zshenv). Ask the DBA for a read-only BT login later, since the scripts only SELECT. Prove the PAR path with the first MesMoveOut/MesSampleData call after cutover; a failure there is best-effort and does not fail the move-out Steps 3 and 6
C2 PROD BT records: ✅ already present and identical to QA (§1.6; created by marting4 2026-11-21) Nothing to do. Step 0 only re-checks none
C3 Area on site-par CVDAisle_1, matching the Galaxy. QA's name is Aisle001 Step 5
C4 mxgw alarm area (open since 11-20). Native alarm mirroring returns nothing while gateway alarms are off; computed alarms still work. NAM, which covers CVDAisle_1. It is set on all four gateways, which needs a gateway restart and is its own deploy step Native alarms only
C5 Cutover (Q9). QA's Galaxy has its own copy of these nine reactors, on OI_WAR_PAR_MBTCP, and MES MES_Key drives them through QA ScadaBridge today. Deploy on PROD whenever convenient (the instances are passive). Cut over by switching the MES and Delmia callers to PROD, one stack per machine. After that, disable the QA instances, or leave them if MES no longer calls QA Step 9
C6 Which URL MES and Delmia call. There is no VIP in front of vp03/vp04:8085. Owner/IT: a DNS alias or LB for the active central, or the callers fail over between both Step 9
C7 API key names MES_Key (all copied methods except Delmia) and delmia-notifier (DelmiaRecipeDownload). Hand both over out of band; never put them in chat or a repo Step 8

Not needed: #60. The mxgw galaxy-sql 503 only affects Galaxy browse; MXAccess reads and writes work, and site-par is Connected.

4. Steps (management API through the CLI, from the Mac; no WinRM; each step gets an owner go)

Use sbp=(… --url http://wonder-app-vp03.zmr.zimmer.com:8085 --username dohertj2 --password-file <0600>). Pass secrets only through --*-file.

  1. BTDB records (C2): re-check only. The records already exist on PROD BT.
    • Run section 1 of btdb/prod-bt-cvd-machines.sql as wonderapp on wondersqlpd/BT. Expect 9 machines and the group as "exists", and no CONFLICT rows.
    • Only if a row has gone missing: remove the RETURN guard and run the whole script. It inserts only the missing rows.
  2. Re-validate the mapping. Re-run the Galaxy read and generator. Stop if any PROD tag name changed since 2026-11-22.
  3. Templates.
    • bundle preview --input cvdreactor-templates.scadabundle must still show 11 adds and 0 blockers.
    • Then bundle import, with conflict policy fail/skip (nothing exists).
    • Verify: template list shows the 11, and template validate --id <CvdReactor> passes.
  4. BTDB db-connection (C1, §1.8).
    • Run apply-btdb-connection.sh <sbp wrapper>.
    • db-connection list must show BTDB.
    • Then run deploy artifacts --site-id 1, which ships the db-connection to site-par for the two site scripts that read BT.
    • The central uses it directly for the inbound methods, so they need no deploy.
    • There is no built-in test-connection. The first proof is step 9: a ready-check call does the SAPID lookup through BTDB.
  5. Inbound API methods (central, §1.5).
    • First run apply-api-methods.sh <sbp wrapper> --dry, then the same without --dry.

    • It creates these from qa-export/api-methods.json, with the same script, parameter and return schemas, timeout and trace flag as QA:

      Method Timeout Required parameters Used on QA by
      MesMoveIn 46 s SAPID, JobSequenceNumber, WorkOrders, OperatorName MES (MES_Key)
      MesMoveOut 45 s SAPID, WorkOrders, OperatorName MES (MES_Key)
      SimpleAlarmStatusRequest 30 s (SAPID) MES (MES_Key)
      MesIsMoveInReady 30 s SAPID test key; read-only
      MesIsMoveOutReady 30 s SAPID test key; read-only
      MesSampleData 30 s ContainerNumber none
      DelmiaRecipeDownload 45 s (MachineCode, …) none; the Delmia path
    • --include-legacy also creates IpsenMESMoveIn. Leave it out unless MES confirms it still calls that method.

    • Verify: api-method list shows all 7, and api-method get for each matches the QA JSON.

    • All 7 route with Route.To(<Machine.Code>) to the instances on site-par, so they work only after step 6/7.

  6. Area. site area create --site-id 1 --name CVDAisle_1 (C3).
  7. Instances, one machine first. Pick an idle one, e.g. Z28063.
    • instance create --name Z28063 --template-id <CvdReactor id> --site-id 1 --area-id <id>.
    • instance set-bindings --id <n> --bindings "$(cat bindings/Z28063.json)". That is 244 entries, connection 1. It upserts, and the instance is new.
    • instance native-alarm-source import --instance-id <n> --file alarm-sources/Z28063.csv. That is all 7 sources, so the QA-era template defaults are never used.
    • instance diff shows 244 bindings and 7 overrides.
    • deploy instance --id <n>.
    • Gate:
      • debug snapshot --id <n>: attributes Good at the same rate as the Galaxy shows. An idle side shows some source-Bad, so compare with the gateway read, not with 100 %.
      • Spot-check 3 values against the Galaxy: a root UDA, a side attribute and a LeakTest.* attribute.
      • site-par active node logs clean.
      • QA unaffected.
  8. Remaining eight. Same as step 6, in two batches. Then deploy artifacts --site-id 1 is no longer needed after restarts: the instances now reference connection 1, so it is rebuilt on boot.
  9. API keys. security api-key create --name MES_Key --methods MesMoveIn,MesMoveOut,SimpleAlarmStatusRequest,MesIsMoveInReady,MesIsMoveOutReady,MesSampleData and --name delmia-notifier --methods DelmiaRecipeDownload. Save each token straight to the Keychain (zb-prod/sb-inbound-<name>); it is shown only once.
  10. Smoke test. This step is read-only on the machines.
    • POST /api/MesIsMoveInReady with {} → 400 VALIDATION_FAILED, which proves the key and the route.
    • Then a real SAPID for each machine, <SAPID>_A and _B (e.g. 103564_A for Z28063 Left; SAPIDs in §1.6) → 200 with IsMoveInReady true or false, matching the Galaxy MoveInReadyFlag. That proves BTDB lookup → Route.To → site-par → correct side, with no write.
    • SimpleAlarmStatusRequest → 200 with an empty list.
  11. Cutover (C5/C6), owner and MES/Delmia teams.
    • Point the MES and Delmia callers at PROD with the new keys.
    • Watch the first real MesMoveIn/MesMoveOut per machine in audit query --channel ApiInbound, and in the Flow Debugger.
    • Then disable the QA instances, or keep QA for testing against its own Galaxy.
    • This is the point of no return for consumers. Before it, rollback means deleting the PROD content.
  12. Records.
    • A deploy record in ScadaBridge/docs/deployment/deployment-records/.
    • Update the PROD plan §0.1a.
    • Memory note.

5. Rollback

  • Before step 10, on PROD: instance delete ×9, then api-method delete, template delete (derived templates before bases), db-connection delete, security api-key delete, deploy artifacts --site-id 1. Nothing outside ScadaBridge's config DB changes, and QA keeps serving MES throughout.
  • After step 10: point the callers back at QA.
  • BT records: none to roll back. They existed before this plan (marting4, 2026-11-21) and are owned outside it.

6. Follow-ups to file

  • ScadaBridge: the bundle import reference scanner flags System.* and Array.* in API method scripts as missing SharedScripts/ExternalSystems. That blocks every inbound method from bundles.
  • ScadaBridge QA config (§1.4): stale bindings on Z28061/Z28062; native alarm sources on Z28062–Z28069; check MantleTempHigh.
  • The open mxgw alarm-area decision (C4) now has a consumer.