Plan docs/plans/2026-11-22-prod-cvd-content-copy.md with the QA findings, the hierarchical-name binding remap (QA and PROD reuse Galaxy suffixes for different machines), BT checks, the run status and the QA reactor disable. Generated inputs under docs/deploy/2026-11-22-prod-cvd-content/ (bindings, alarm-source overrides, mapping, QA export, BT preflight SQL, helper scripts; no secrets). PROD plan §0.1a rows for the content run and the mxgw changes. Claude-Session: https://claude.ai/code/session_01GT67AD5mc2BnaaAfY3hqqQ
26 KiB
PROD content: copy the CVD reactor templates and inbound API methods from QA, and configure Z28061–Z28069 (plan, 2026-11-22)
Owner, 2026-11-22: "investigate the templates in use on QA scadabridge. how the tags are mapped, etc. Then generate a plan
on how to copy them to prod, copy the api methods used too, and configure the machine in the attached screenshot. note
the template instances should run on the par server cluster, the api methods can run on the central server."
The screenshot shows Galaxy NAM / NewJersey / CVDAisle_1 / Z28061…Z28069.
This is Phase 7 of 2026-11-19-prod-scadabridge-mxgw-install.md.
Status 2026-11-22 16:50Z: steps 0–9 DONE on PROD (record ScadaBridge docs/deployment/deployment-records/2026-11-22-prod-cvd-reactors-content.md). Step 10 (cutover) is with the owner and the MES/Delmia teams. The keys are MES_Key with QA's grants minus IpsenMESMoveIn (so DelmiaRecipeDownload is included), and delmia-notifier. Delmia sends the plain MachineCode (Z28063).
Before the run, everything was read-only:
- the QA management API (lists,
get,bundle export, audit query); - QA Galaxy
ZBover SQL as NAM\dohertj2; - PROD Galaxy browse through vp03's gateway with the
scadabridge-prodkey (metadata:read); bundle previewon PROD, which does not apply anything.
The generated inputs are in ../deploy/2026-11-22-prod-cvd-content/.
0. Run status (2026-11-22, owner: "start the plan but wait to deploy to the par sites")
Steps 0–6 were done on the PROD central through the management API. Nothing has been deployed to any site:
deploy status shows 0 deployments, and both sites' artifactsDeployedAt are unchanged. Run log:
scratchpad run/run-log.md.
| Step | Result | IDs |
|---|---|---|
| 0 BT re-check | 9 machines + CVD_Reactors exist, no conflicts |
n/a |
| 1 Mapping | Galaxy re-read: 108 objects, identical to mapping.md |
n/a |
| 2 Templates | 11 imported (--on-conflict skip, 0 blockers) |
ids 1–11; CvdReactor = 5 |
3 BTDB db-connection |
created; deploy artifacts held |
id 1 |
| 4 API methods | 7 created; identical to the QA JSON | 1 MesMoveIn, 2 MesMoveOut, 3 DelmiaRecipeDownload, 4 SimpleAlarmStatusRequest, 5 MesSampleData, 6 MesIsMoveInReady, 7 MesIsMoveOutReady |
| 5 Area | CVDAisle_1 on site-par |
area 1 |
| 6 Instances | created with 244 bindings (connection 1) and 7 alarm-source overrides each; Disabled, not deployed | Z28063=1, Z28061=2, Z28062=3, Z28064=4, Z28065=5, Z28066=6, Z28067=7, Z28068=8, Z28069=9 |
Held, waiting on the owner's go:
deploy artifacts --site-id 1;- deploy and enable of the instances (steps 6/7);
- API keys (step 8);
- smoke test (step 9);
- cutover (step 10).
QA reactors disabled 2026-11-22 16:38Z (owner: "disable the machines in qa"):
instance disableon QA ids 1, 2, 9, 11, 12, 13, 10, 14, 15 (Z28061–Z28069) all returned success;instance listshows state 2 (Disabled) for all nine.- The QA site no longer runs them: a
debug snapshotof Z28063 returnsinstanceNotFound. - WarmCanary (still enabled) and ZIPSEN (already disabled) were not touched.
- The last MES call to QA was at 2026-11-19 18:26Z. From now on, MES/Delmia calls to QA for these machines fail until the callers move to PROD.
- To undo:
instance enable+deploy instancefor those ids on QA.
Notes from the run:
template validate --id 5reports 3 errors: alarmsLeft/RightMTALockoutandMantleTempHighreference*ReactorSide.MTA_Lockout/MantleTemp, which it calls "not in the flattened configuration". QA's CvdReactor gives the same 3 errors, yet QA deployed Z28063 successfully on 2026-11-15, after those alarms were created (09-30 and 10-22). So this looks like a false positive intemplate validatefor members of composed, derived templates; it is not a deploy blocker. Watch the first PROD deploy anyway.- QA's
RightMESReceivertemplate is missing 14 inherited attribute rows and 2 inherited scripts. PROD's copy (id 9) is complete. This is a QA-side defect only.
1. What QA runs (findings)
1.1 Templates (QA ScadaBridge wonder-app-vq03:8085, site site-a id 2, area Aisle001)
| Template | Role | Members |
|---|---|---|
CvdReactor (id 1) |
The machine. One instance per reactor | 16 attributes (machine UDAs: ChlorineFlow, HydrogenFlow, TrunkPressure, Heartbeat*, LeakTest*, MachineCode/ID/Description, …); 3 computed alarms; 8 scripts; 7 native alarm sources; 5 compositions |
↳ LeftMESReceiver / RightMESReceiver |
Derived from MESReceiver (id 3) |
26 attributes each: MoveIn* and MoveOut* handshake tags plus ScanStateCmd. The base carries the MoveIn/MoveOut scripts |
↳ LeftReactorSide / RightReactorSide |
Derived from ReactorSide (id 7, "Galaxy $Reactor_Side") |
60 attributes plus composed LeakTest (23 attributes) |
↳ DelmiaReceiver |
Derived from DelmiaReceiver (id 12) |
10 attributes: ReadyFlag, RecipeDownloadFlag, RecipeProcessedFlag, RecipeProcessResult[Text], DownloadPath, WorkOrderNumber, PartNumber, JobStepNumber, Username |
Not copied, because they are QA test content: IpsenSim + its MESReceiver (instance ZIPSEN), WarmCanary (the OtOpcUa
Warm monitor), and the standalone LeakTest base, which comes along anyway as a dependency.
Scripts on CvdReactor. All of them are Call-triggered: there are no timers and no value-change triggers.
MesMoveIn,MesMoveOut,MesIsMoveInReady,MesIsMoveOutReadyandMesSampleDataparse<SAPID>_A|_B[_LT]and pickChildren[side+"MESReceiver"].ProcessRecipeDownloadusesChildren["DelmiaReceiver"].AlarmStatusis a stub that returns an empty list.IpsenMoveInis legacy.MesMoveOutandMesSampleDataalso read BTDB on the site (Database.Connection("BTDB"), best-effort cycle data).
The computed alarms (MantleTempHigh, Left/RightMTALockout) only read values. So a deployed instance is passive.
It reads tags and evaluates alarms, and writes nothing to the Galaxy until an inbound API call reaches it.
1.2 Tag mapping
Every template attribute's data-source reference is just its own name (e.g. ChlorineFlow). Every Galaxy address
comes from a per-instance connection binding (dataSourceReferenceOverride) on data connection 1 MxGateway. The
Galaxy shape is the same in both galaxies:
Z2806x ($CVDReactor) → instance root attributes Z2806x.<attr>
├─ DelmiaReceiver (DelmiaReceiver_0NN) → DelmiaReceiver.<attr> DelmiaReceiver_0NN.<attr>
├─ Left ($Reactor_Side, Left_0NN) → LeftReactorSide.<attr> Left_0NN.<attr>
│ ├─ LeakTest (LeakTest_0NN) → LeftReactorSide.LeakTest.<attr> Left_0NN.LeakTest.<attr>
│ ├─ MESReceiver (MESReceiver_0NN) → LeftMESReceiver.<attr> MESReceiver_0NN.<attr>
│ ├─ Setpoints, TableAlarms → (not bound; TableAlarms feeds a native alarm source)
└─ Right (same as Left)
There are 244 bindings per machine: 16 root, 2×26 MES, 2×83 side (including LeakTest), and 10 Delmia.
Native alarm sources mirror Galaxy alarms by object prefix:
ReactorAlarms=Z2806x.;Left/RightSideAlarms=Left_0NN.;Left/RightLeakTestAlarms=LeakTest_0NN.;Left/RightTableAlarms=TableAlarms_0NN..
1.3 ⚠ PROD reuses the same tag names for different machines
QA's and PROD's Galaxies number their contained objects differently, and the numbers collide. For example:
- QA
Left_001is Z28061's left side; PRODLeft_001is Z28065's; - QA
MESReceiver_023is Z28061-Left; on PROD it is Z28061-Left by coincidence, butMESReceiver_025is Z28062-Left on QA and Z28069-Left on PROD.
If QA's bindings were copied unchanged, every PROD instance would read and write another reactor's tags, with Good quality and no error. For that reason no instance or binding is carried over from QA. The PROD bindings were generated by hierarchical name instead:
- resolve QA
tag→ QAZ2806x.Left.LeakTest; - look up the PROD object with the same hierarchical name;
- keep QA's reference style (
Left_0NN.LeakTest.<attr>).
Every one of the 9×244 attributes was checked against the PROD object's attribute list; all of them exist. PROD objects (read 2026-11-22 from the vp03 gateway):
| Instance | Left | Right | Left LeakTest | Right LeakTest | Left MESReceiver | Right MESReceiver | DelmiaReceiver | Left TableAlarms | Right TableAlarms |
|---|---|---|---|---|---|---|---|---|---|
| Z28061 | Left_005 | Right_005 | LeakTest_009 | LeakTest_010 | MESReceiver_023 | MESReceiver_024 | DelmiaReceiver_043 | TableAlarms_009 | TableAlarms_010 |
| Z28062 | Left_004 | Right_004 | LeakTest_007 | LeakTest_008 | MESReceiver_021 | MESReceiver_022 | DelmiaReceiver_042 | TableAlarms_007 | TableAlarms_008 |
| Z28063 | Left_003 | Right_003 | LeakTest_005 | LeakTest_006 | MESReceiver_019 | MESReceiver_020 | DelmiaReceiver_041 | TableAlarms_005 | TableAlarms_006 |
| Z28064 | Left_002 | Right_002 | LeakTest_003 | LeakTest_004 | MESReceiver_017 | MESReceiver_018 | DelmiaReceiver_040 | TableAlarms_003 | TableAlarms_004 |
| Z28065 | Left_001 | Right_001 | LeakTest_001 | LeakTest_002 | MESReceiver_015 | MESReceiver_016 | DelmiaReceiver_039 | TableAlarms_001 | TableAlarms_002 |
| Z28066 | Left_009 | Right_009 | LeakTest_017 | LeakTest_018 | MESReceiver_031 | MESReceiver_032 | DelmiaReceiver_047 | TableAlarms_017 | TableAlarms_018 |
| Z28067 | Left_008 | Right_008 | LeakTest_015 | LeakTest_016 | MESReceiver_029 | MESReceiver_030 | DelmiaReceiver_046 | TableAlarms_015 | TableAlarms_016 |
| Z28068 | Left_007 | Right_007 | LeakTest_013 | LeakTest_014 | MESReceiver_027 | MESReceiver_028 | DelmiaReceiver_045 | TableAlarms_013 | TableAlarms_014 |
| Z28069 | Left_006 | Right_006 | LeakTest_011 | LeakTest_012 | MESReceiver_025 | MESReceiver_026 | DelmiaReceiver_044 | TableAlarms_011 | TableAlarms_012 |
Re-run the generator before applying if the PROD Galaxy is redeployed in the meantime. Contained objects get renumbered when they are recreated.
1.4 QA defects found; not copied, reported only
- Z28061 and Z28062 carry 38 stale bindings each, from DEV-era module names (
DelmiaRecv,Left/RightDelmiaReceiver,*.DelmiaJobStep,*.PID_AlarmString,*.LeakTest.MESMoveIn/Out). They point at another machine's objects (Z28061 → Z28062's sides; Z28062 → Z28069's) and at attributes that don't exist in either Galaxy. They are harmless, but they are noise. - The template's native alarm sources are hard-coded to Z28061-era QA objects:
Z28061.,Left_001., andLeakTest_002.for both LeakTest sources. Z28063–Z28069 have no overrides, so on QA they mirror Z28061's alarms. Z28062's overrides are also off by one (LeakTest_005/006,TableAlarms_005/006; its real objects areLeakTest_004/003andTableAlarms_004/003). MantleTempHighwatches onlyRightReactorSide.MantleTempand fires on equality with"600", not on ≥ 600. It is copied as is; the owner should decide whether that is intended.
1.5 Inbound API methods (central)
Inbound methods always run on the central. Each one looks up SELECT TOP 1 Code FROM dbo.Machine WHERE SAPID=@s on
db-connection BTDB, then Route.To(<Code>) to the instance on whichever site hosts it, here site-par.
QA inbound traffic in the last 30 days (audit query --channel ApiInbound):
| Method | Calls (last) | Copy? |
|---|---|---|
MesMoveIn |
103 by MES_Key (11-19) |
yes |
MesMoveOut |
96 by MES_Key (11-19) |
yes |
SimpleAlarmStatusRequest |
202 by MES_Key (11-19) |
yes (returns an empty list today; AlarmStatus is a stub) |
MesIsMoveInReady / MesIsMoveOutReady |
test key only | yes: read-only, and used as the PROD smoke test |
DelmiaRecipeDownload |
none | yes: the Delmia path. PROD Delmia caller is dnc-app-vp01 |
MesSampleData |
none | yes (owner may drop it) |
IpsenMESMoveIn |
none | no (recommended): legacy, superseded by MesMoveIn, routes to the legacy IpsenMoveIn script |
1.6 BTDB records (QA BT wondersqlqa = WONDER-SQL-VQ03, DB BT, read 2026-11-22)
MesMoveIn and the other methods resolve SAPID → dbo.Machine.Code, and Code must equal the ScadaBridge instance
name. The reactors' own Galaxy scripts also open batches in BT by machine code (StartMachineBatch and the rest).
So PROD BT needs the same records before any machine is used.
QA has one group and nine machines, and no MachineAlarm rows for them:
| MachineGroup | Name | Description | Parent | Members |
|---|---|---|---|---|
CVD_Reactors |
CVD Reactors | CVD Reactors in Parsippany, NJ | none | Z28061–Z28069 |
| Code | Name | ZTag | SAPID | Description |
|---|---|---|---|---|
| Z28061 | T5 | Z28061 | 103559 | Z28061 Table 5 |
| Z28062 | T4 | Z28062 | 103563 | CVD Reactors in Parsippany, NJ |
| Z28063 | T3 | Z28063 | 103564 | 〃 |
| Z28064 | T2 | Z28064 | 103565 | 〃 |
| Z28065 | T1 | Z28065 | 103566 | 〃 |
| Z28066 | T9 | Z28066 | 103567 | 〃 |
| Z28067 | T8 | Z28067 | 103568 | 〃 |
| Z28068 | T7 | Z28068 | 103569 | 〃 |
| Z28069 | T6 | Z28069 | 103570 | Z28069 Table 6 |
Common to all nine: TimeZone Eastern Standard Time, MultipleBatch/MultipleCycle 0, Active 1, OtherData {}.
Name is the table number. The two descriptions that differ (Z28061, Z28069) are copied as they are.
MES sends <SAPID>_A|_B[_LT], e.g. 103564_A. The inbound method uses the leading digits for the lookup, and the
machine script uses the suffix to pick the side.
PROD BT already has these records (checked 2026-11-22).
- Database: PROD BT is
wondersqlpd= WONDER-SQL-VP03, DBBT. The SQL loginwonderapp(from~/.zshenv,HISTORIAN_SQL_USER/_PASSWORD) works there withdb_datareader+db_datawriter, INSERT onMachine/MachineGroup/MachineGroupMembership, and SELECT onRuntime.dbo.Timezone. NAM\dohertj2 and NAM\adm_dohertj2 cannot log in. - Who created them: marting4, on 2026-11-21 at 04:03Z: group
CVD_Reactors(id 20) with all nine machines (MachineID 119–127) as members. - Match with QA: every field is identical to QA (Code, Name, ZTag, SAPID, Description, TimeZone, flags, Active,
OtherData, group membership, and no
MachineAlarmrows). There are no batches yet. - Schema difference: PROD BT's
MachineGrouppredates the DARS sprint-1 schema and has noParentMachineGroupIDcolumn. The script was corrected so it doesn't name that column.
../deploy/2026-11-22-prod-cvd-content/btdb/prod-bt-cvd-machines.sql
is kept as a re-check:
- Section 1 is a read-only preflight. It lists the server and database, rows that already exist, and conflicts:
a Code with a different SAPID or ZTag, a SAPID or ZTag used by another machine, or a time zone missing from
Runtime.dbo.Timezone. - Section 2 sits behind a
RETURNguard. It inserts only what is missing, in one transaction, never updates or deletes, andTHROWs on any conflict. - Result on 2026-11-22: section 1 was run as
wonderappagainst PROD BT and QA BT, and the transaction was rolled back. Both show only "exists" rows (9 machines + the group) and no conflicts. - No insert is needed. The BTDB Manager's config import was not usable anyway: it writes only into the BT database it is connected to, which is DEV.
1.7 What PROD has today
PROD (wonder-app-vp03:8085) holds no templates, instances, API methods, db-connections, API keys or areas.
Sites:
site-parid 1 on par-vp03/04; data connection id 1MxGateway→ par-vp03:5120 / par-vp04:5120, Connected;site-appid 2 on the app boxes, connection id 2. Not used here.
1.8 The BTDB db-connection on QA, and what PROD gets
QA ScadaBridge has one db-connection, BTDB (id 1). Its connection string is encrypted at rest. It was decrypted
on the Mac on 2026-11-22 from the QA config DB (the key ring is stored unencrypted there) and read with the password
redacted:
QA: Server=wondersqlqa.zmr.zimmer.com;Database=BT;User Id=wonderapp;Password=***;TrustServerCertificate=True;MultiSubnetFailover=True
PROD: Server=wondersqlpd.zmr.zimmer.com;Database=BT;User Id=wonderapp;Password=***;TrustServerCertificate=True;MultiSubnetFailover=True
- Login:
wonderappon PROD BT is proven (§1.6). - Encryption: no
Encryptkeyword is given. Microsoft.Data.SqlClient then defaults to encrypting, andTrustServerCertificate=Trueskips the CA check, exactly as on QA. - Failover:
MultiSubnetFailover=Trueis required becausewondersqlpdis an AG listener. - Name: the connection must be named
BTDB. Every inbound method and both site scripts address it by that name (Database.QuerySingleAsync("BTDB", …)andDatabase.Connection("BTDB")). - Helper:
apply-btdb-connection.shbuilds the string in a 0600 temp file and passes it with--connection-string-file, so the password never appears on argv or in the repo.
2. Import path, tested with bundle preview on PROD
- Templates:
bundle export --templates CvdReactor --include-dependencieson QA gives 11 templates. Previewed on PROD: 11 adds, 0 blockers, no site or connection mappings, no QA hostnames. The bundle is stored at../deploy/2026-11-22-prod-cvd-content/qa-export/cvdreactor-templates.scadabundle(sha2566dcdc453…235e3). The connection nameMxGatewayin the native alarm sources matches PROD. - API methods: the bundle is blocked. Every method gets a blocker on
System(fromSystem.Func<…>), andSimpleAlarmStatusRequestalso gets one onArray(Array.Empty). The import reference scanner reads those as missing SharedScripts or ExternalSystems. This is a false positive in ScadaBridge (issue to be filed). The workaround is to create the methods withapi-method create, using the definitions exported toqa-export/api-methods.json. Those definitions hold scripts and schemas only; there are no keys in them. - Instances, bindings, API keys and the db-connection are created on PROD directly. They are never imported from QA.
3. Decisions and inputs needed before running
| # | Item | Recommendation | Blocks |
|---|---|---|---|
| C1 | ScadaBridge BTDB db-connection on PROD (§1.8): mirror QA's, with only the server changed. It is used by the central (the SAPID lookup in every inbound method) and by site-par (MesMoveOut/MesSampleData cycle data). Still unverified: the path from par-vp03/04 → wondersqlpd:1433. The centrals already reach wondersqlpd for the ScadaBridge config DB. |
Use the same login as QA (wonderapp, password from ~/.zshenv). Ask the DBA for a read-only BT login later, since the scripts only SELECT. Prove the PAR path with the first MesMoveOut/MesSampleData call after cutover; a failure there is best-effort and does not fail the move-out |
Steps 3 and 6 |
| C2 | PROD BT records: ✅ already present and identical to QA (§1.6; created by marting4 2026-11-21) | Nothing to do. Step 0 only re-checks | none |
| C3 | Area on site-par | CVDAisle_1, matching the Galaxy. QA's name is Aisle001 |
Step 5 |
| C4 | mxgw alarm area (open since 11-20). Native alarm mirroring returns nothing while gateway alarms are off; computed alarms still work. | NAM, which covers CVDAisle_1. It is set on all four gateways, which needs a gateway restart and is its own deploy step |
Native alarms only |
| C5 | Cutover (Q9). QA's Galaxy has its own copy of these nine reactors, on OI_WAR_PAR_MBTCP, and MES MES_Key drives them through QA ScadaBridge today. |
Deploy on PROD whenever convenient (the instances are passive). Cut over by switching the MES and Delmia callers to PROD, one stack per machine. After that, disable the QA instances, or leave them if MES no longer calls QA | Step 9 |
| C6 | Which URL MES and Delmia call. There is no VIP in front of vp03/vp04:8085. | Owner/IT: a DNS alias or LB for the active central, or the callers fail over between both | Step 9 |
| C7 | API key names | MES_Key (all copied methods except Delmia) and delmia-notifier (DelmiaRecipeDownload). Hand both over out of band; never put them in chat or a repo |
Step 8 |
Not needed: #60. The mxgw galaxy-sql 503 only affects Galaxy browse; MXAccess reads and writes work, and site-par is
Connected.
4. Steps (management API through the CLI, from the Mac; no WinRM; each step gets an owner go)
Use sbp=(… --url http://wonder-app-vp03.zmr.zimmer.com:8085 --username dohertj2 --password-file <0600>). Pass
secrets only through --*-file.
- BTDB records (C2): re-check only. The records already exist on PROD BT.
- Run section 1 of
btdb/prod-bt-cvd-machines.sqlaswonderapponwondersqlpd/BT. Expect 9 machines and the group as "exists", and noCONFLICTrows. - Only if a row has gone missing: remove the
RETURNguard and run the whole script. It inserts only the missing rows.
- Run section 1 of
- Re-validate the mapping. Re-run the Galaxy read and generator. Stop if any PROD tag name changed since 2026-11-22.
- Templates.
bundle preview --input cvdreactor-templates.scadabundlemust still show 11 adds and 0 blockers.- Then
bundle import, with conflict policyfail/skip(nothing exists). - Verify:
template listshows the 11, andtemplate validate --id <CvdReactor>passes.
- BTDB db-connection (C1, §1.8).
- Run
apply-btdb-connection.sh <sbp wrapper>. db-connection listmust showBTDB.- Then run
deploy artifacts --site-id 1, which ships the db-connection to site-par for the two site scripts that read BT. - The central uses it directly for the inbound methods, so they need no deploy.
- There is no built-in test-connection. The first proof is step 9: a ready-check call does the SAPID lookup
through
BTDB.
- Run
- Inbound API methods (central, §1.5).
-
First run
apply-api-methods.sh <sbp wrapper> --dry, then the same without--dry. -
It creates these from
qa-export/api-methods.json, with the same script, parameter and return schemas, timeout and trace flag as QA:Method Timeout Required parameters Used on QA by MesMoveIn46 s SAPID, JobSequenceNumber, WorkOrders, OperatorName MES ( MES_Key)MesMoveOut45 s SAPID, WorkOrders, OperatorName MES ( MES_Key)SimpleAlarmStatusRequest30 s (SAPID) MES ( MES_Key)MesIsMoveInReady30 s SAPID test key; read-only MesIsMoveOutReady30 s SAPID test key; read-only MesSampleData30 s ContainerNumber none DelmiaRecipeDownload45 s (MachineCode, …) none; the Delmia path -
--include-legacyalso createsIpsenMESMoveIn. Leave it out unless MES confirms it still calls that method. -
Verify:
api-method listshows all 7, andapi-method getfor each matches the QA JSON. -
All 7 route with
Route.To(<Machine.Code>)to the instances on site-par, so they work only after step 6/7.
-
- Area.
site area create --site-id 1 --name CVDAisle_1(C3). - Instances, one machine first. Pick an idle one, e.g. Z28063.
instance create --name Z28063 --template-id <CvdReactor id> --site-id 1 --area-id <id>.instance set-bindings --id <n> --bindings "$(cat bindings/Z28063.json)". That is 244 entries, connection 1. It upserts, and the instance is new.instance native-alarm-source import --instance-id <n> --file alarm-sources/Z28063.csv. That is all 7 sources, so the QA-era template defaults are never used.instance diffshows 244 bindings and 7 overrides.deploy instance --id <n>.- Gate:
debug snapshot --id <n>: attributes Good at the same rate as the Galaxy shows. An idle side shows some source-Bad, so compare with the gateway read, not with 100 %.- Spot-check 3 values against the Galaxy: a root UDA, a side attribute and a
LeakTest.*attribute. - site-par active node logs clean.
- QA unaffected.
- Remaining eight. Same as step 6, in two batches. Then
deploy artifacts --site-id 1is no longer needed after restarts: the instances now reference connection 1, so it is rebuilt on boot. - API keys.
security api-key create --name MES_Key --methods MesMoveIn,MesMoveOut,SimpleAlarmStatusRequest,MesIsMoveInReady,MesIsMoveOutReady,MesSampleDataand--name delmia-notifier --methods DelmiaRecipeDownload. Save each token straight to the Keychain (zb-prod/sb-inbound-<name>); it is shown only once. - Smoke test. This step is read-only on the machines.
POST /api/MesIsMoveInReadywith{}→ 400VALIDATION_FAILED, which proves the key and the route.- Then a real SAPID for each machine,
<SAPID>_Aand_B(e.g.103564_Afor Z28063 Left; SAPIDs in §1.6) → 200 withIsMoveInReadytrue or false, matching the GalaxyMoveInReadyFlag. That proves BTDB lookup →Route.To→ site-par → correct side, with no write. SimpleAlarmStatusRequest→ 200 with an empty list.
- Cutover (C5/C6), owner and MES/Delmia teams.
- Point the MES and Delmia callers at PROD with the new keys.
- Watch the first real
MesMoveIn/MesMoveOutper machine inaudit query --channel ApiInbound, and in the Flow Debugger. - Then disable the QA instances, or keep QA for testing against its own Galaxy.
- This is the point of no return for consumers. Before it, rollback means deleting the PROD content.
- Records.
- A deploy record in
ScadaBridge/docs/deployment/deployment-records/. - Update the PROD plan §0.1a.
- Memory note.
- A deploy record in
5. Rollback
- Before step 10, on PROD:
instance delete×9, thenapi-method delete,template delete(derived templates before bases),db-connection delete,security api-key delete,deploy artifacts --site-id 1. Nothing outside ScadaBridge's config DB changes, and QA keeps serving MES throughout. - After step 10: point the callers back at QA.
- BT records: none to roll back. They existed before this plan (marting4, 2026-11-21) and are owned outside it.
6. Follow-ups to file
- ScadaBridge: the bundle import reference scanner flags
System.*andArray.*in API method scripts as missing SharedScripts/ExternalSystems. That blocks every inbound method from bundles. - ScadaBridge QA config (§1.4): stale bindings on Z28061/Z28062; native alarm sources on Z28062–Z28069; check
MantleTempHigh. - The open mxgw alarm-area decision (C4) now has a consumer.