# Pending: Worker time-conversion fixes #226 + #228 (DEV first, then QA)
**Status: NOT deployed.** This is the deploy note for the next gateway deploy. Ship both fixes in one
deploy: they are both in the x86 Worker, both change timestamps consumers see, and both are on `main`.
| Fix | Commit | Behaviour change on the box |
|---|---|---|
| #226 wnwrap alarm DATE+TIME are already UTC; stop adding GMTOFFSET-DSTADJUST | `892bdc1a` | Every wnwrap alarm time (`QueryActiveAlarms`, alarm events) moves **4-5 h earlier**, to correct UTC. OtOpcUa/ScadaBridge dedup keyed on raise time sees each existing alarm once with the new time. |
| #228 `Write2`/`WriteSecured2` (+ bulk) time argument sent as box-local time | `9ef6fc84` | The stored source timestamp of a timestamped write equals the instant sent, instead of being shifted by the box's UTC offset (+5 h on a UTC-5 box in winter, +4 h in summer). No consumer calls `Write2` today (ScadaBridge and OtOpcUa have no call site). |
Build **Server and Worker together from one `main` SHA at or after `9ef6fc84`** (the upgrade script refuses
staged builds from different SHAs; they share `WorkerProtocolVersion`). Procedure, traps and rollback:
`docs/runbooks/DeployUpgradeNssmService.md` and `scripts/deploy/Upgrade-MxGatewayService.ps1`.
## What else rides along
- **DEV vd03** runs `2b13564e`. `2b13564e..9ef6fc84` adds only #226, #227 (opt-in `emit_stream_attached`,
additive proto, Contracts/Client 0.4.0) and #228, plus docs/tests. Nothing else changes for current
consumers.
- **QA vq03/vq04** run `4f931e4`. A `main` build also carries the 2026-10-21 review remediation and the
operator-authenticated alarm ack (`488649c`). The QA deploy is therefore gated by **#170**: every QA
OtOpcUa node with a Galaxy driver must first run lmxopcua `dc0a24f2`+ and have an `AlarmAck` fallback
account (or per-key ack identities) configured, or every Galaxy ack is refused. Close that gate first or
in the same window.
## DEV (wonder-app-vd03) first
1. Build on windev in a scratch folder from the chosen SHA: Worker
`dotnet build src\ZB.MOM.WW.MxGateway.Worker\ZB.MOM.WW.MxGateway.Worker.csproj -c Release -p:Platform=x86`
and run `Worker.Tests` x86 (expect 0 failures; 783 passed / 12 skipped at `9ef6fc84`); publish the Server
self-contained as in runbook section 4. Do not touch windev's own `MxAccessGw` service.
2. Stage both to vd03 over SMB, run the upgrade script on the box (deploy activity, WinRM in scope):
`Upgrade-MxGatewayService.ps1 -ServerSource <stage>\Server -WorkerSource <stage>\Worker -ExpectedSha <sha> -Label issue226-228`.
Single box: stop, swap, start once (trap 1, `OrphanWorkerTerminator`).
3. Runbook section 7 checks (health 200, pre-upgrade `mxgw_` key authenticates, wrong key rejected, Worker
path proven by a read).
4. **#228 check, from the Mac, no remote exec:** with a scoped key for `MESReceiver_025.*` (Z28062, never
Z28061), run
`MXGATEWAY_LIVE_GATEWAY_ASSERT_WRITE2_TIMESTAMP=1 dotnet test clients/dotnet/ZB.MOM.WW.MxGateway.Client.Tests --filter FullyQualifiedName~LiveGatewayWrite2Tests`
with `MXGATEWAY_LIVE_GATEWAY_ENDPOINT`, `MXGATEWAY_LIVE_GATEWAY_API_KEY_FILE` and
`MXGATEWAY_LIVE_GATEWAY_WRITE_ITEM=MESReceiver_025.MoveInBatchID` (`docs/GatewayTesting.md`, "Live gateway
write"). Both tests must pass: `Write2_SupervisoryAdvise_KeepsSentTimestamp` failed on `2b13564e` with
sent `01:36:51Z` / stored `06:36:51Z`. Revoke and delete the key afterwards.
5. **#226 check:** `QueryActiveAlarms` for `Galaxy!CVDAisle_1.TableAlarms_008.RuntimeAlert` reads
`2026-07-28T20:02:46.830Z` (was `01:02:46.830Z` on 07-29), and a fresh alarm's time equals
`Runtime.dbo.Events.EventTimeUtc` on wonder-sql-vd03 (read over SQL, not WinRM).
6. Write the deploy record in `docs/deploy/` and update the scadaproj index row.
## QA (wonder-app-vq03 / vq04) after DEV passes
1. Confirm the #170 prerequisites above on both QA OtOpcUa nodes.
2. Same SHA and staged builds as DEV. The gateways are singletons per box: deploy vq03, run the section 7
checks, then vq04 (rolling). The vq04 gateway depends on vq03 for Galaxy SQL and alarms.
3. #228 check as DEV step 4 against each QA gateway, with a Z28062 test attribute that exists on QA (pick
and record it; `MESReceiver_025.MoveInBatchID` is the DEV item). #226 check as DEV step 5 against the
QA Historian.
4. Deploy record, index row.
## Rollback
Runbook section 8: stop, confirm no Server/Worker process, rename the `Server.bak-*`/`Worker.bak-*` pair back,
start once. Both fixes are Worker-only behaviour; no store or schema changes, so rollback restores the old
(wrong) times and nothing else.
## Evidence the fix works (windev, 2026-11-12, Eastern Standard Time, UTC-5)
The live smoke `WorkerLiveMxAccessSmokeTests.GatewaySession_WithLiveWorker_Write2ValueWithTimestampToAdvisedItem`
(in-process gateway, its own worker; the `MxAccessGw` service was untouched) on `TestChildObject.TestInt`:
| Worker | Sent | Stored | Result |
|---|---|---|---|
| `9ef6fc84` (fix) | `2026-11-13T01:46:31Z` | `2026-11-13T01:46:31Z` | Passed |
| `9ef6fc84` with the conversion removed (negative control) | `2026-11-13T01:47:32Z` | `2026-11-13T06:47:32Z` | Failed by exactly +5 h |
Both runs got `OnWriteComplete` `Ok` and restored the original value.