@@ -793,27 +793,54 @@ in the codebase for the forward-compat shape, but the gateway-side
|
||||
`AcknowledgeAlarmByName` when the public RPC supplies a recognizable
|
||||
`Provider!Group.Tag` reference.
|
||||
|
||||
**Opt-in managed GUID ack.** Setting `MXGATEWAY_USE_MANAGED_ALARM_ACK=1`
|
||||
in the gateway's environment (workers inherit it) routes GUID-keyed acks
|
||||
through `aaAlarmManagedClient.AlarmClient.AlarmAckByGUID` instead of the
|
||||
wnwrap method. That managed method is implemented on this build and
|
||||
carries operator domain and full name natively. The worker reaches it by
|
||||
reflection (`AaManagedAlarmAckConsumer`) because the members are
|
||||
non-public, and runs its own Initialize → Register → Subscribe lifecycle
|
||||
against the alarm subscription expression. The path is deliberately
|
||||
conservative:
|
||||
**Opt-in managed GUID ack — does not work on this rig (live-tested
|
||||
2026-10-18).** Setting `MXGATEWAY_USE_MANAGED_ALARM_ACK=1` in the
|
||||
gateway's environment (workers inherit it) makes the worker build an
|
||||
`AaManagedAlarmAckConsumer`, which drives
|
||||
`aaAlarmManagedClient.AlarmClient` by reflection (its members are
|
||||
non-public) and is meant to take GUID-keyed acks in place of the
|
||||
wnwrap method. The live test shows it cannot do that as built, so leave
|
||||
the flag off.
|
||||
|
||||
- If the DLL cannot load or the lifecycle returns a non-zero status, the
|
||||
worker drops back to the wnwrap ack path; alarm reads never fail
|
||||
because of it.
|
||||
- Subtag-mode acks (forced subtag, or failover currently on the standby)
|
||||
stay on the subtag consumer: their GUIDs are synthetic and only it can
|
||||
resolve them.
|
||||
- By-name acks stay on wnwrap — `AlarmClient` has no by-name ack.
|
||||
The test raised `TestMachine_001.TestAlarm001` with a secured write,
|
||||
read its GUID from the wnwrap XML snapshot (the public API exposes no
|
||||
alarm GUIDs), and acknowledged it through the `AcknowledgeAlarm` RPC
|
||||
with the flag on:
|
||||
|
||||
A zero return still means *accepted*, not *applied*; a secured
|
||||
(`MxSecurityOperate`) alarm needs an authenticated operator. The skip-gated
|
||||
`AlarmManagedGuidAckLiveSmokeTests` asserts the ack actually lands.
|
||||
| Step | Result |
|
||||
|---|---|
|
||||
| RPC ack by GUID, flag off (control) | `NotImplementedException`; `.Acked` stays `False` |
|
||||
| RPC ack by GUID, flag on | Same `NotImplementedException`; `.Acked` `False`, `.AckMsg` empty |
|
||||
| `AlarmClient.RegisterConsumer` in a process with a registered wnwrap consumer | `-65` — and wnwrap gets `-65` if the managed client registered first; a real `hWnd` does not help |
|
||||
| Managed client alone in its own process, records loaded | `AlarmAckByGUID` → `-1`, `SelectByGUID` → `-1` for the wnwrap GUID in both byte orders, `AlarmAckSelected` → `-57` |
|
||||
|
||||
Three separate problems follow:
|
||||
|
||||
1. **The two libraries cannot share a process.** The worker always runs
|
||||
a wnwrap reader, so the managed `RegisterConsumer` fails with `-65`.
|
||||
The dispatcher is built to drop back to the wnwrap ack path on a
|
||||
lifecycle failure (so alarm reads keep working), and it does so
|
||||
silently — which is why the flag-on RPC is indistinguishable from the
|
||||
control.
|
||||
2. **The managed client does not recognise the wnwrap GUID.** `-1` from
|
||||
`SelectByGUID` is "not found", not a security refusal, even with the
|
||||
client holding records. Getting the client's own identifier for the
|
||||
alarm is not reliable either: `GetHighPriAlarm` mostly throws the
|
||||
FILETIME `ArgumentOutOfRangeException` described above. The
|
||||
`MxSecurityOperate` question was therefore never reached.
|
||||
3. **The gateway does not send the identity fields.** Its GUID arm fills
|
||||
`OperatorNode`, `OperatorDomain` and `OperatorFullName` with empty
|
||||
strings, so the domain and full name the managed method carries
|
||||
would not arrive through the public RPC even if 1 and 2 were solved.
|
||||
|
||||
A working managed ack would need the client hosted out of process, a way
|
||||
to resolve the alarm to the identifier the managed client uses, and the
|
||||
identity fields plumbed through the gateway. Routing rules the worker
|
||||
already applies stay correct and would carry over: subtag-mode acks
|
||||
(synthetic GUIDs) stay on the subtag consumer, and by-name acks stay on
|
||||
wnwrap because `AlarmClient` has no by-name ack. The skip-gated
|
||||
`AlarmManagedGuidAckLiveSmokeTests` exercises the in-process
|
||||
arrangement and hits problem 1.
|
||||
|
||||
### 5. STA / threading — resolved
|
||||
|
||||
|
||||
@@ -446,11 +446,12 @@ behavior.
|
||||
The alarm monitor is independent of client sessions: `AcknowledgeAlarm` and
|
||||
`StreamAlarms` are session-less RPCs served by the monitor.
|
||||
|
||||
GUID-keyed acknowledges can opt into AVEVA's managed alarm client by setting
|
||||
the environment variable `MXGATEWAY_USE_MANAGED_ALARM_ACK=1` on the gateway
|
||||
process (workers inherit it; under NSSM, add it to the service environment).
|
||||
It is off by default and has no `MxGateway:*` option because it is still
|
||||
awaiting live confirmation on the rig. See
|
||||
The worker also reads `MXGATEWAY_USE_MANAGED_ALARM_ACK` (inherited from the
|
||||
gateway process). Setting it to `1` is meant to route GUID-keyed acknowledges
|
||||
through AVEVA's managed alarm client, but a live test (2026-10-18) showed the
|
||||
path cannot work as built: the managed client fails to register alongside the
|
||||
worker's wnwrap reader and the worker silently falls back to wnwrap. Leave it
|
||||
unset. It has no `MxGateway:*` option. See
|
||||
[AlarmClientDiscovery](./AlarmClientDiscovery.md) ("Opt-in managed GUID ack").
|
||||
|
||||