fix(archreview): gateway core P0 remediation (GWC-01/02/03, TST-02, TST-12)

Interlocking changes across the gateway server (shared GatewaySession.cs /
SessionManager.cs), committed together:

- GWC-01 (Critical): alarm monitor now attaches as an internal
  (non-counted) distributor subscriber instead of a second raw drain of the
  single worker event channel; WorkerClient._events -> SingleReader with a
  claimed-once guard so a future dual-consumer regression throws loudly.
- GWC-02 (High): faulted sessions are swept in CloseExpiredLeasesAsync
  (IsFaultedReapable + FaultedReason); new FaultedGraceSeconds (default 0).
- GWC-03 (High): configurable MaxSparseArrayLength (default 1_000_000)
  enforced before allocation.
- TST-02 (High, security): StreamEvents attach now enforces the opening key
  id -> PermissionDenied on owner mismatch.
- TST-12 (Medium): CLAUDE.md retention-defaults sentence corrected.

Verified: NonWindows build clean; targeted tests 135/135 on macOS, plus
WorkerClientTests 18/18 on the Windows host.
This commit is contained in:
Joseph Doherty
2026-07-09 05:51:57 -04:00
parent 31eec41456
commit 20392cf246
30 changed files with 632 additions and 48 deletions
@@ -470,6 +470,20 @@ public sealed class AlarmFailoverEndToEndTests
}
}
/// <inheritdoc />
public async IAsyncEnumerable<MxEvent> ReadAlarmEventsAsync(
string sessionId,
[EnumeratorCancellation] CancellationToken cancellationToken)
{
await foreach (WorkerEvent workerEvent in _events.Reader.ReadAllAsync(cancellationToken))
{
if (workerEvent.Event is not null)
{
yield return workerEvent.Event;
}
}
}
/// <inheritdoc />
public bool TryGetSession(string sessionId, [MaybeNullWhen(false)] out GatewaySession session)
{