Joseph Doherty 8be82e02c2 Path-based NodeIds — decouple client contract from driver address
The pre-refactor design minted OPC UA NodeIds directly from the driver's
FullReference (the native-address string). That had three long-term
problems:

1. OPC UA Part 3 §5.2.2 requires NodeIds to be immutable across a node's
   lifetime. A rename of the underlying device address — Galaxy attribute,
   S7 tag, Modbus register alias — changed the NodeId and broke every
   client that had pinned the previous identifier.
2. Two drivers with coincidentally-matching native addresses (e.g. `temp`
   in Modbus and `temp` in S7 under different Equipment rows) collided on
   the NodeId identifier.
3. TagConfig was being placed verbatim on the wire; for drivers whose
   TagConfig is JSON (every driver shipped today, per the
   CK_Tag_TagConfig_IsJson check constraint), clients saw the raw JSON
   blob as the NodeId string.

Refactor:

* DriverNodeManager.Variable now mints a stable path-based NodeId
  `{driverId}/{folder-path}/{browseName}` and records the driver-side
  FullReference in a new _fullRefByNodeId map. OnReadValue / OnWriteValue
  / ResolveFullRef look the FullReference up via that map instead of
  casting NodeId.Identifier. The old cast path is preserved as a
  fallback so any test fixture that still registers variables with
  FullRef-shaped NodeIds keeps working.

* EquipmentNodeWalker.AddTagVariable now extracts the cross-driver
  `FullName` field from Tag.TagConfig before handing the address to
  DriverAttributeInfo. Every shipped driver stores the wire reference in
  TagConfig[FullName]; falling back to the raw string covers any future
  driver that wants an opaque non-JSON address. ExtractFullName is
  exposed internal for unit coverage.

* scripts/e2e/test-galaxy.ps1 defaults updated to the new path-based
  NodeIds. Verified live against p7-smoke-galaxy on the dev box:
  `ns=2;s=p7-smoke-galaxy/lab-floor/galaxy-line/reactor-1/Source` reads
  return Status=0x00000000 with a real Galaxy byte-array value.

Test suite: 195/195 Core.Tests + 283/283 Server.Tests green. Five new
ExtractFullName / FullName-passthrough tests added.

Task #112 GA-3 — golden-path read verified end-to-end; remaining E2E
script stages still blocked on pre-existing issues (ScriptedAlarm
predicate NRE on empty upstream cache, PowerShell $changeLines.Count
guard), tracked separately.
Task #134 — complete.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>