- Endpoint rewrite: the driver now connects to the configured host AND port (scheme match, advertised path kept) instead of the server-advertised URL — fixes NAT/port-map upstreams and lets an in-test proxy carry the session (SDK SelectEndpoint rule). - TcpStallProxy + OpcUaClientDriverStallWireTests: the in-place blip (#670) is now wire-tested on loopback — one Bad, frozen read stamp, same session, identical value republished Good, a post-recovery change arrives, no source-time regression after the SDK's late backlog flush. - Defect found by that test, fixed: a change published right after a stall rode a Publish response the SDK timed out and never republished, leaving the node Good on the pre-change value indefinitely. New trailing reconcile read (Timeout + KeepAliveInterval after recovery) publishes any Good value newer than the last accepted one, through the replay guard's mark. - IDriverConnectionLossSource (Core.Abstractions): opt-in definitive-loss signal. DriverInstanceActor attaches in PreStart / detaches in PostStop and turns a raise into a disconnect only while Connected. OpcUaClient raises once per session on keep-alive BadSessionIdInvalid/BadSessionClosed/BadSessionNotActivated/ BadServerHalted (measured: the SDK never re-opens a halted channel) or a dropped subscription; ambiguous codes stay with the #527 watchdog. - Replay guard: one Information summary per recovery when the window closes ("dropped N late notifications across M refs"), with a timer so quiet subscriptions log it too. - ReconnectPeriod deleted (options, AdminUI form, docs, tests); stored configs that carry reconnectPeriod still parse in the factory, probe and browser. - Docs: OpcUaClient.md, DriverLifecycle.md, driver-specs.md, CLAUDE.md.
23 KiB
OPC UA Client (Gateway) Driver
Getting-started guide for the OPC UA Client driver. This is the short path — for
the full per-field spec read docs/v2/driver-specs.md §8,
and for the test-harness map read OpcUaClient-Test-Fixture.md.
What it talks to
A remote OPC UA server. This driver runs the opposite direction from the
usual "server exposes PLC data" flow: it acts as an OPC UA client, opens a
Session against an upstream server, and re-exposes that server's address space
through the local OtOpcUa server. Browse, read, write, subscribe, alarm, and
history calls are passed through to the upstream endpoint.
It is built on the OPC Foundation UA .NET Standard reference SDK and runs in-process in the OtOpcUa server's .NET 10 AnyCPU host — pure managed, no out-of-process isolation.
There is no standalone driver CLI for the OPC UA Client driver. To exercise a remote OPC UA endpoint by hand, point the general-purpose Client CLI at it directly.
Project split
| Project | Target | Role |
|---|---|---|
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient/ |
net10.0 | In-process driver — session lifetime, read / write / subscribe / alarm / history passthrough |
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Browser/ |
net10.0 | IDriverBrowser — live address-picker browse used by the AdminUI |
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Contracts/ |
net10.0 | Config records + enums bound from DriverConfig JSON |
Minimum deployment
"Drivers": {
"upstream-1": {
"Type": "OpcUaClient",
"Config": {
"EndpointUrl": "opc.tcp://plc.internal:4840",
"SecurityPolicy": "None",
"SecurityMode": "None",
"AuthType": "Anonymous"
}
}
}
EndpointUrls (a list) takes precedence over the single-URL EndpointUrl and
provides ordered failover — the driver tries each candidate in turn at every
InitializeAsync (including the comms-loss watchdog's re-initialise), and the first to connect wins (e.g. a hot-standby pair on
4840 / 4841). See
src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Contracts/OpcUaClientDriverOptions.cs
for every field (security policy/mode, auth type, session timeout, keep-alive,
browse root, node/depth caps). ReconnectPeriod was deleted (#676 — unused since #670 removed the SDK reconnect
handler, and the AdminUI no longer shows it); stored configs that still carry reconnectPeriod keep parsing in the
factory, the Test-Connect probe and the browse picker (unknown keys are skipped), and the form drops it on the next save.
Endpoint address: the configured host and port win (#676)
GetEndpoints returns each endpoint with the URL the server believes it lives at. Behind NAT, a port map, a
container port publish or a proxy that address is unreachable from the client — or reachable but bypassing the proxy.
The driver therefore rewrites the selected endpoint's host and port to the configured URL's whenever the schemes
match, keeping the advertised path (the SDK's own CoreClientUtils.SelectEndpoint rule, which the driver's
policy-aware endpoint selection used to bypass). A different scheme is left alone; an unparseable advertised URL falls
back to the configured one. OpcUaClientDriver.RewriteEndpointUrl.
Session lifetime
A single Session per driver instance; subscriptions multiplex onto it. Stored NodeIds embed the server-stable namespace URI (not the
session-relative ns=N index) so a remote namespace-table reorder across a
restart doesn't silently re-point references at the wrong namespace.
Upstream outage and recovery (Gitea #670)
The session keep-alive (KeepAliveInterval, default 5 s) is the liveness signal:
- Good keep-alive / any data or event notification advances
DriverHealth.LastSuccessfulRead— a subscription-only driver never callsReadAsync, so without this its read stamp froze at connect time. - Bad keep-alive ⇒ health
Degraded(LastError = "keep-alive: <status>", read stamp preserved), host statusStopped, and — once per outage, not per keep-alive — every subscribed ref is publishedBadNoCommunicationwith its last value retained and source + server timestamp = the detection time (live-gate F1: stamped with the last Good's source time it collided with that row's(TagId, SourceTimeUtc)history key and was never stored), plus a quality-onlyBadNoCommunicationannotation (#626 pattern, no alarm-state change, no/alertsrow) on every subscribed alarm condition. - The session survives (a network blip; the keep-alive turns Good again) ⇒ recovered in place: health
Healthy, the refs still Bad are re-read once and published Good (a server whose subscription survived does not resend an unchanged value, and a(value, status)dedup downstream lets the identical value through), alarm quality goes back Good and aConditionRefreshre-reports anything missed. A notification that lands first wins over the read. For a bounded replay window after such a recovery — max(30 s, 2 x the longest subscription keep-alive window) — each ref is guarded by a high-water mark — its last Good upstream source time, raised by the recovery read and advanced by every notification accepted in the window — and a notification whose source time is at or BELOW it (equal included: OPC UA moves the source timestamp on every value or status change, so an equal one is a replay) is dropped: the SDK was seen delivering a missed one 4–6 s late, which regressed the node (live-gate F2). The guard holds for the WHOLE window — fresh notifications arrive ~1 s after recovery, before the late replay, so a ref is never disarmed early (the F2 re-gate failed on exactly that). A notification with no source time passes without moving the mark. Outside that window every notification is accepted whatever its timestamp, so an upstream clock that steps backwards (NTP, a PLC clock reset) never freezes a node. The outage Bad never moves the comparison; a re-initialise resets it. ⚠️ By design, inside the window a notification whose source time EQUALS the last accepted one is dropped — so a status-only change that keeps the old source timestamp (not what OPC UA servers are supposed to do) is lost during the window only. When the window closes the driver logs ONE Information line —post-recovery replay window closed — dropped N late notifications across M refs after recovery— because the per-drop line is Debug and thestale_notification_droppedcounter is OTel-only, which made the guard unobservable on the docker-dev rig (#676). - Trailing re-read after an in-place recovery (#676). Found by the TCP-stall wire test: a change the server
published just after the stall ended rode a Publish response that had been in flight across the stall; the SDK
timed that request out (
BadTimeout), discarded the response and never republished the message (the following keep-alives moved the sequence number past it), so the node stayed Good on the pre-change value indefinitely.Timeout + KeepAliveIntervalafter the recovery — when every request in flight across the stall has completed or timed out — every subscribed ref is read once more, and any Good value newer than the last one accepted for that ref is published (through the replay guard's mark while the window is open, so it can never regress a node). An Information line names how many refs it had to repair. - The session does not come back (an upstream restart: the server forgot the session) ⇒ the driver stays
Degradedwith its read stamp frozen, which is the #527 comms-loss watchdog's trip condition;DriverInstanceActorrunsShutdownAsync+InitializeAsync(retried every 10 s while the server is down) and re-subscribes data + alarms; the new subscription's initial values come back Good. Alarm last-told state survives the re-initialise (#619), so the post-subscribeConditionRefreshraises no un-ack flicker; the host's reconnect annotation restores condition quality. - Fast recovery for a DEFINITIVELY lost session (#676). The driver implements
IDriverConnectionLossSourceand raisesConnectionLost— once per session, re-armed by a re-initialise — when the loss is certain, so the host re-initialises at once instead of after the watchdog's 90 s. Definitive means: a keep-alive status ofBadSessionIdInvalid/BadSessionClosed/BadSessionNotActivated(the server forgot, closed or never activated the session) orBadServerHalted, or a tracked subscription declared lost (below).BadServerHaltedis on the list because it was measured: on the restart wire test a gracefully stopped server reportsBadServerHalted(and the keep-alives alternate it withBadNoCommunication), and the SDK never re-opens a channel the server halted — 15 s after the server was back, the same session still failed every request withBadServerHalted;BadSessionIdInvalidnever arrived. Everything else —BadNoCommunication,BadConnectionClosed,BadNotConnected,BadRequestTimeout/BadTimeout(what a stalled link produces) — is ambiguous (the link may resume and keep its session, see the stall test) and stays with the watchdog. Consequence: a gracefully restarted upstream recovers in roughly one reconnect interval (≈10 s) instead of ~100 s; an upstream that vanishes without a halt (killed, cable pulled) still waits for the watchdog. - The subscription dies but the session lives (an outage longer than the subscription lifetime —
LifetimeCountx publishing interval, often well under the session timeout — or a server that drops it) ⇒ keep-alives stay Good, so they cannot be the signal. APublishErrorofBadNoSubscription(while subscriptions are tracked) orBadSubscriptionIdInvalidnaming a tracked subscription, or a tracked subscription whose SDKPublishingStoppedpersists for one more subscription keep-alive window + 5 s across good keep-alives, declares it lost:Degraded("subscription lost: …"), the outage published once, and — sticky until the session is released — nothing advancesLastSuccessfulReadany more (not good keep-alives, not a sibling subscription's notifications), so the watchdog's re-initialise recreates it. Both detectors are wire-tested independently. A dead subscription never comes back on its session, so this also raisesConnectionLost(#676) and the re-initialise happens at once. - An in-place recovery is bound to the session whose keep-alive recovered: one overtaken by a re-initialise neither publishes, nor degrades, nor re-arms the outage latch of the new session.
There is no in-driver reconnect any more. The SDK's SessionReconnectHandler (removed) retried forever in SDK
1.5.378 (its "exhausted" path was unreachable), recreated sessions by cloning subscriptions the driver never
re-tracked, and kept health Healthy throughout — so on docker-dev a stopped opc-plc left nodes Good on their last
value indefinitely and they never recovered. A teardown against a lost session skips the wire deletes and CloseSession
(bounded to 5 s otherwise). SDK warnings (keep-alive / publish / channel errors) now reach the driver's own logger,
rate-limited to 20 per minute with a suppressed-count note; the per-driver SDK logger factory is disposed with the
driver.
Namespace assignment (retired, Gitea #648)
Earlier versions required a per-instance TargetNamespaceKind (Equipment +
a mandatory UnsMappingTable, or SystemPlatform + an empty table). Both
options are removed: nothing ever read the mapping table beyond the startup
check, and in v3 the raw-to-UNS projection is explicit (UnsTagReference), so
the choice carried no behaviour — it only made a config without the key fail
Initialize. Remote nodes are authored as /raw tags bound by their upstream
nodeId; there is no namespace field on the driver, the AdminUI form or the
seed.
Stored DriverConfig JSON that still carries targetNamespaceKind or
unsMappingTable keeps working: the keys are unknown and ignored on parse and
initialise (the AdminUI form drops them on the next save). Pinned by
OpcUaClientReinitConfigAdoptionTests.Legacy_namespace_keys_are_ignored_by_parse_and_initialise.
Capability surface
OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWritable, ISubscribable, IHostConnectivityProbe, IAlarmSource, IDriverConnectionLossSource
(src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient/OpcUaClientDriver.cs:31).
| Capability | Path | Notes |
|---|---|---|
ITagDiscovery |
DiscoverAsync (recursive browse) |
Mirrors the upstream tree from BrowseRoot (default ObjectsFolder i=85), bounded by MaxDiscoveredNodes / MaxBrowseDepth |
IReadable |
ReadAsync → Session.ReadAsync |
Upstream StatusCodes pass through verbatim (cascading-quality rule) |
IWritable |
WriteAsync → Session.WriteAsync |
Passthrough write |
ISubscribable |
native OPC UA subscriptions / monitored items | The remote server pushes data changes |
IHostConnectivityProbe |
session keep-alive | Host key is the endpoint URL actually connected to after the failover sweep |
IAlarmSource |
SubscribeAlarmsAsync (EventFilter) + AcknowledgeAsync |
Subscribes to upstream alarm/condition events and forwards acks |
Native alarms (#619). An alarm raw tag is
TagConfig{ "nodeId": "<upstream SourceNode>", "alarm": {...} }. The host subscribes with RawPaths and routes on (driver, RawPath), so the driver matches each event'sConditionId(then itsSourceNode) against the tag's authorednodeIdand reports the RawPath asConditionId. AuthornodeIdas the upstream condition node for a 1:1 mapping (required when one source carries several conditions, e.g. Hi + HiHi); authoring the source node folds every condition of that source into one tag.Acknowledgeis called on the condition node of the last event seen for the RawPath with that event's EventId (Part 9 §5.7.3). The event'sActiveState/Id+AckedState/Idare selected and turned into theRaise/Acknowledge/Clear/Retriggerkinds the host projector consumes (without a kind no upstream alarm could ever show active); the kinds are emitted from the state last told to the host per RawPath, so an identical re-delivery emits nothing (no re-raise, which would un-ack). An inactive → active+acked move is ONEActiveAcknowledged(#656; it used to beRaise+Acknowledge, a client-visible unacked intermediate); a move into inactive+unacked is ONEInactiveUnacknowledged(#657; it used to beRaise/Retrigger+Clear, an Active flicker). The first event per condition after a start or deploy respawn is flaggedIsRestatementand states the upstream condition so it lands from whatever the host retained: an inactive+acked one goes out asClear+Acknowledge(#657; it used to be anUnspecifiedthe host wrote as "Activated", and a retained-Active host condition stayed Active). So the host writes no duplicate row when its condition already shows that state (seedocs/AlarmTracking.md). Condition branch events (non-nullBranchId) are ignored.ConditionRefreshis called after the event item is created, after a keep-alive outage the session survived, and on aRefreshRequiredevent, so a condition already active upstream is reported at subscribe;RefreshStart/RefreshEndmarkers are dropped. A server without it (BadNotSupported/BadMethodInvalid/…) is logged once and tolerated. Last-told state survives a re-initialise (the host re-subscribes the same set over nodes it did not rebuild) and is forgotten when the subscribed set changes (the host rebuilt, recreating the nodes inactive). Index keys are server-stable (nsu=), so a namespace reorder across a re-initialise keeps matching. docker-dev seeds an opc-plc driver (MAIN-opcua); the alarm tag is created only when@OpcPlcAlarmSourceNodeIdis set indocker-dev/seed/seed-clusters.sql.
This driver does not implement
IRediscoverable— there is no push-driven rediscovery signal from a remote OPC UA server in this driver.
History: not supported (Gitea #655)
This driver does not proxy the upstream server's HistoryRead. The server serves
HistoryRead only through the server-wide IHistorianDataSource (see docs/Historian.md);
drivers carry no history capability, and the former IHistoryProvider passthrough
(Raw / Processed / AtTime / Events) was never dispatched to and has been deleted.
isHistorized on an OpcUaClient tag means OtOpcUa records the value into the historian
from now on (numeric only), not that upstream history is forwarded. A tag without
isHistorized has no HistoryRead access bit and answers BadHistoryOperationUnsupported.
If upstream-history proxying is wanted later, it needs a new intent key, a dispatch path
through DriverHostActor, and a continuation-point rework — see #655.
Certificate trust
AutoAcceptCertificates accepts any self-signed / untrusted server certificate.
It is dev-only — leave it false in production so a MITM against the
opc.tcp channel fails closed. The SDK rejects a revoked certificate
(BadCertificateRevoked / BadCertificateIssuerRevoked) before the auto-accept handler runs, and the handler
also refuses them explicitly — defence in depth (#277), not a behaviour change.
CertificateValidation (defaults change nothing):
| Key | Default | Meaning |
|---|---|---|
rejectUnknownRevocationStatus |
false |
Reject a server certificate whose revocation status cannot be determined (no CRL for its issuer, or a stale one). Leave false for brownfield sites without CRL infrastructure. Only effective with autoAcceptCertificates off — the auto-accept handler accepts every suppressible error, including revocation-unknown. |
issuerStorePath |
null (= %LocalAppData%/OtOpcUa/pki/issuers) |
Directory used as the trusted-issuer store. The SDK reads issuer CRLs (*.crl) from its crl/ sub-folder, so this is how an operator points the driver at a managed CRL set. |
Subscription tuning (#273)
The per-subscription parameters that used to be hardcoded are driver options; the defaults are the old values.
| Key | Default | Notes |
|---|---|---|
subscriptionPublishingInterval |
null |
A .NET TimeSpan string ("00:00:02"), not a number. null = the interval the runtime requests per subscribe (floored at 50 ms). When set it overrides that value (floor still applies); monitored-item sampling follows it. |
subscriptionKeepAliveCount |
10 |
>= 1. |
subscriptionLifetimeCount |
1000 |
Must be >= 3 x keep-alive count (Part 4 §5.13.2). |
subscriptionMaxNotificationsPerPublish |
0 |
0 = server decides. |
subscriptionPriority |
0 |
0-255. |
Out-of-range values (and a non-absolute discoveryUrl) are rejected when the options are loaded — driver creation / InitializeAsync fails once with a clear message rather than the driver faulting and retrying forever. The alarm subscription uses the same counts.
Per-tag tuning (deadband / sampling interval / queue size, #274) is not implemented — it needs an
ISubscribable signature change on Core.
Server OperationLimits (#275)
Nothing driver-side: the SDK session already honours the remote server's
ServerCapabilities/OperationLimits. Opc.Ua.Client.Session derives from Opc.Ua.SessionClientBatched,
fetches the limits on open (FetchOperationLimitsAsync) and splits Read / Write / CreateMonitoredItems / Browse /
HistoryRead requests that exceed them (a limit of 0 = unlimited). The driver issues one logical call per
operation and a unit test pins the Session : SessionClientBatched relationship so an SDK change that dropped
it is caught. (A driver-side splitter was tried and removed: it duplicated the SDK and, on a stalled link, held
the driver gate for chunks x timeout.)
Discovery URL (#278)
discoveryUrl (default null, e.g. opc.tcp://lds:4840): at InitializeAsync the driver runs FindServers on it
and GetEndpoints on every returned server, keeping the endpoints matching securityPolicy + securityMode.
Discovered URLs are tried after endpointUrls/endpointUrl (case-insensitive de-dup) — discovery can add
fallbacks but never outranks or replaces the configured server. Because an LDS commonly registers several servers
(identical line PLCs, a gateway plus a historian) and the first to accept a connection would be bound silently:
discoveryServerUriset: only endpoints of the server with that ApplicationUri are used.- unset and exactly one distinct server discovered: that server is used.
- unset and more than one: the connect attempt fails with an error naming the discovered ApplicationUris and
telling the operator to set
discoveryServerUri.
A discovery network failure (LDS down) is logged and non-fatal — the static list is used (note it is retried on
every InitializeAsync, including comms-loss reconnects). The discovery channel itself is always unsecured (spec).
Diagnostics counters (#276)
Session/publish events are published on the shared OTel meter as the counter
otopcua.driver.opcuaclient.events, tagged driver_instance (the driver instance id) and event =
publish_response, notification (items), data_change, bad_status_value, publish_error,
keepalive_miss, keepalive_recovered (a bad keep-alive followed by a good one on the same session),
stale_notification_dropped (a late replay dropped inside the post-recovery window, see above). A climbing
keepalive_miss / keepalive_recovered rate is the signature of a flapping upstream (reconnect_* were removed with
the reconnect handler, #670). They are not part of DriverHealth or the
/hosts panel.
Testing
- Unit tests —
tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Tests/cover the session lifecycle, namespace remapping, alarm/history passthrough, and config binding against a faked SDK session. - Integration fixture — exercises the driver against a reference OPC UA server (opc-plc) on the shared docker host; see OpcUaClient-Test-Fixture.md for the coverage map.
- Wire tests against the in-process server —
tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests/OpcUaClientDriver*WireTests(no Docker).OpcUaClientDriverStallWireTests(#676) covers the in-place blip that used to be live-gate-only: the driver connects throughTcpStallProxy, an in-test TCP forwarder whose pause holds every byte without closing anything (which only works because of the endpoint rewrite above); it asserts one Bad, a frozen read stamp, recovery on the SAME session, the identical value republished Good, a change published right after recovery still arriving, and no source-time regression once the SDK's late backlog flush has arrived.OpcUaClientDriverReconnectWireTestscovers the server restart (incl. theBadServerHalted→ConnectionLostsignal) and the subscription-lost case.
Further reading
docs/v2/driver-specs.md §8— full per-field spec, namespace-assignment rules, and cascading-quality detail- OpcUaClient-Test-Fixture.md — test-harness map
- Client.CLI.md — general-purpose OPC UA client CLI for ad-hoc browsing of any endpoint