Historian — server-side OPC UA HistoryRead (Phase C)

Phase C wires server-side OPC UA HistoryRead for authored equipment tags flagged historized. The feature is driver-agnostic: any equipment tag (Galaxy, Modbus, OpcUaClient, or any other driver) can be marked historized; the server dispatches all history reads to the registered IHistorianDataSource — today, the Wonderware sidecar client (WonderwareHistorianClient). No EF migration is required; the historian flag rides in the existing schemaless TagConfig JSON blob alongside the Phase B alarm object.

Design reference: docs/plans/2026-06-14-galaxy-phase-c-historian-design.md.


Historized TagConfig schema

A tag is historized by adding fields to its TagConfig blob on the /uns equipment page Tags tab (raw-JSON textarea). No separate UI control exists — Galaxy (the primary use case) already uses the raw-JSON editor.

Fields

Field Type Required Description
isHistorized bool yes Marks the tag historized. Materialises the OPC UA node with Historizing=true and the HistoryRead AccessLevel bit.
historianTagname string no Explicit historian tagname to query. When absent or empty, defaults to the tag's driver FullName (the TagConfig.FullName).

Examples

Default historian tagname (uses FullName = TestMachine_002.TestFloat):

{"FullName":"TestMachine_002.TestFloat","isHistorized":true}

Explicit historian tagname override:

{"FullName":"TestMachine_002.TestFloat","isHistorized":true,"historianTagname":"Plant.Line1.Flow"}

A tag that is both historized and a native alarm:

{"FullName":"TestMachine_002.HiAlarm","isHistorized":true,"alarm":{"alarmType":"OffNormalAlarm","severity":700}}

ServerHistorian configuration

The ServerHistorian section in appsettings.json controls the historian read path. Enabled defaults to false; when disabled, the server registers NullHistorianDataSource and all HistoryRead calls on historized nodes return GoodNoData (empty, not an error).

{
  "ServerHistorian": {
    "Enabled": false,
    "Host": "localhost",
    "Port": 32569,
    "UseTls": false,
    "ServerCertThumbprint": "",
    "SharedSecret": ""
  }
}
Key Type Default Description
Enabled bool false Enable the live WonderwareHistorianClient. falseNullHistorianDataSource (empty reads).
Host string localhost DNS name or IP of the machine running the historian sidecar.
Port int 32569 TCP port the sidecar listens on (OTOPCUA_HISTORIAN_TCP_PORT).
UseTls bool false Wrap the TCP connection in TLS.
ServerCertThumbprint string Optional SHA-1 thumbprint to pin the sidecar's TLS certificate. Leave empty for CA-chain validation.
SharedSecret string Shared secret token the sidecar expects on every connection. Required when Enabled.

Do not commit SharedSecret to appsettings.json. Set it via an environment variable, a secrets store, or a deployment-time overlay. The checked-in default is always empty.

The ServerHistorian section is independent of the AlarmHistorian section (the alarm write path). They share the same Wonderware sidecar process but hold separate client instances and separate SharedSecret values.


HistoryRead behavior

Read variants

The server supports all four OPC UA HistoryRead variants:

Variant Node type CLI --aggregate
Raw Historized variable (omit --aggregate)
Processed Historized variable Average, Minimum, Maximum, Total, Count
AtTime Historized variable n/a (client supplies exact timestamps)
Events Equipment folder (event notifier) n/a

Variable nodes (historized tags) serve Raw, Processed, and AtTime history. Historizing=true and AccessLevels.HistoryRead are set at materialization so any compliant OPC UA client can discover historized capability from the node's attributes.

Equipment-folder event-notifier nodes serve Event history. Every equipment folder that owns at least one alarm condition is already an event notifier; the server registers a sourceName (the equipment id) for each such folder and maps event history reads to the Wonderware historian using that source. Event-field projection supports the standard BaseEventType select clauses — EventId, SourceName, Time, ReceiveTime, Message, and Severity; an unsupported select operand returns a null field (spec-conformant).

Graceful degradation

Situation HistoryRead status
Historized node, historian configured and reachable, results found Good
Historized node, historian configured, time range empty GoodNoData
Historized node, historian NOT configured (Enabled=false / Null source) GoodNoData (empty)
Non-historized node BadHistoryOperationUnsupported
Backend timeout or exception BadHistoryOperationUnsupported per node; other nodes in the same batch are unaffected

A historized node with no historian configured never returns an error status — it returns empty. This means a deployment can author and publish historized tags before the historian sidecar is provisioned, without producing error spikes in connected clients.

Known limitations

  • No server-managed continuation points. Each HistoryRead call is single-shot. The server honors the client's NumValuesPerNode limit but does not issue continuation points for large result sets. Paging across multiple calls is a documented follow-up.
  • No modified-value history (HistoryReadModified). Requests for modified values return BadHistoryOperationUnsupported. This is a follow-up.

Redundancy and authorization

History reads are served from any node — there is no Primary gate. Authorization is the standard OPC UA HistoryRead permission enforced by the SDK through the AccessLevels.HistoryRead bit set at materialization. A session without sufficient permissions receives BadUserAccessDenied from the SDK before the dispatch reaches the historian.


Authoring workflow

  1. Open the equipment's Tags tab on /uns/equipment/{id}.
  2. Create or edit the tag. Because Galaxy uses the raw-JSON editor, add "isHistorized":true (and optionally "historianTagname":"...") directly in the TagConfig textarea.
  3. Save and publish. The server rebuilds its address space; the node materialises with Historizing=true and the HistoryRead AccessLevel bit.
  4. Confirm with Client.CLI read that the node's Status is Good and that the value is updating. Then issue a historyread to verify the historian connection returns data.

Client.CLI historyread examples

The historyread command reads historical data from any node. Supply start and end times in ISO 8601 UTC form. See docs/Client.CLI.md for the full flag reference.

# Raw history for a historized Galaxy tag (last 24 hours by default)
otopcua-cli historyread \
  -u opc.tcp://localhost:4840/OtOpcUa \
  -n "ns=2;s=EQ-55297329838d/GalaxyTestTag" \
  --start "2026-06-13T00:00:00Z" --end "2026-06-14T00:00:00Z"

# Limit to 100 values
otopcua-cli historyread \
  -u opc.tcp://localhost:4840/OtOpcUa \
  -n "ns=2;s=EQ-55297329838d/GalaxyTestTag" \
  --start "2026-06-13T00:00:00Z" --end "2026-06-14T00:00:00Z" \
  --max 100

# 1-hour average aggregate
otopcua-cli historyread \
  -u opc.tcp://localhost:4840/OtOpcUa \
  -n "ns=2;s=EQ-55297329838d/GalaxyTestTag" \
  --start "2026-06-13T00:00:00Z" --end "2026-06-14T00:00:00Z" \
  --aggregate Average --interval 3600000

# Authenticated read (ReadOnly role or higher required)
otopcua-cli historyread \
  -u opc.tcp://localhost:4840/OtOpcUa \
  -n "ns=2;s=EQ-55297329838d/GalaxyTestTag" \
  --start "2026-06-13T00:00:00Z" --end "2026-06-14T00:00:00Z" \
  -U reader -P password

Supported --aggregate values: Average, Minimum, Maximum, Count, Start, End, StandardDeviation (aliases: avg, min, max, stddev/stdev, first, last). --interval is the processing interval in milliseconds (default 3600000 = 1 hour).


Live /run gate

The live read gate requires the Wonderware historian sidecar running on the WW Historian VM (10.100.0.48) and AVEVA Historian healthy. Set ServerHistorian:Enabled=true with the correct Host, Port, and SharedSecret in appsettings.json (or via environment variables), then deploy and publish at least one historized Galaxy tag. The gate is operator-driven — it is not part of the local docker-dev rig.

See AlarmHistorian.md for the historian sidecar setup and ServiceHosting.md for the sidecar service configuration.