# `otopcua-ablegacy-cli` — AB Legacy (PCCC) test client
Ad-hoc probe / read / write / subscribe tool for SLC 500 / MicroLogix 1100 /
MicroLogix 1400 / PLC-5 devices, talking to the **same** `AbLegacyDriver` the
OtOpcUa server uses (libplctag PCCC back-end).
Third of four driver test-client CLIs. Shares `Driver.Cli.Common` with the
others.
## Build + run
```powershell
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Cli -- --help
```
## Common flags
| Flag | Default | Purpose |
|---|---|---|
| `-g` / `--gateway` | **required** | Canonical `ab://host[:port]/cip-path` |
| `-P` / `--plc-type` | `Slc500` | Slc500 / MicroLogix / Plc5 / LogixPccc |
| `--timeout-ms` | `5000` | Per-operation timeout — see precedence note below |
| `--retries` | `0` | Retry count on transient `BadCommunicationError` (PR 9 / #252) |
| `--demote-failure-threshold` | `3` | **PR ablegacy-12 / #255** — consecutive comm failures before the device is auto-demoted |
| `--demote-for-ms` | `30000` | **PR ablegacy-12 / #255** — auto-demote cool-down window in ms |
| `--no-demote` | off | **PR ablegacy-12 / #255** — disable auto-demote entirely (counters still tick) |
| `--verbose` | off | Serilog debug output |
Family ↔ CIP-path cheat sheet:
- **SLC 5/05 / PLC-5** — `1,0`
- **MicroLogix 1100 / 1400** — empty path (`ab://host/`) — they use direct EIP
with no backplane
- **LogixPccc** — `1,0` (Logix controller accessed via the PCCC compatibility
layer; rare)
- **PLC-5 via 1756-DHRIO bridge** — `1,<slot>,2,<station-octal>` (PLC-5 only).
See [drivers/AbLegacy-DH-Bridging.md](drivers/AbLegacy-DH-Bridging.md) for
the full DH+ syntax, octal-station reference (00..77 = 0..63), and manual
hardware smoke procedure.
#### DHRIO worked example (PR ablegacy-13 / #256)
PLC-5 on DH+ node 7 (octal 07), DHRIO module in chassis slot 3,
EtherNet/IP gateway 192.168.1.10:
```powershell
otopcua-ablegacy-cli read `
-g ab://192.168.1.10/1,3,2,07 `
-P Plc5 -a N7:10 -t Int
```
The parser validates `1,<slot>,2,<station>`: port-1 must be the backplane,
slot must be 0..16, port-3 must be `2` (DH+), station must be octal 0..77 (so
`80`, `90`, etc. are rejected). Combining a DH+ bridge path with a non-PLC-5
family at startup throws `InvalidOperationException("DHRIO bridging is
PLC-5-only")`.
### Per-device timeout / retry tuning (#252, PR 9)
The CLI's `--timeout-ms` is the **driver-wide default** when launched as a
one-shot test client. In production (server-side, multi-device deployment)
each `AbLegacyDeviceOptions` row carries its own optional `Timeout` /
`Retries` that override the driver-wide value.
Precedence (highest → lowest): per-device override → driver-wide default →
hard-coded fallback (2000 ms / 0 retries).
Tuning cheat sheet — start here, measure, then trim:
| Family | Recommended `Timeout` | Notes |
|---|---|---|
| SLC 5/01 (RS-232 / DH+ bridge) | **5000 ms** | Slowest of the bunch; serial round-trip plus DH+ hop |
| SLC 5/02 / 5/03 (DH+) | 3000 ms | Bridged Ethernet → DH+ adds ~1 s |
| **SLC 5/04 / 5/05** (Ethernet) | **2000 ms** | Fastest of the SLC family — direct EIP/PCCC |
| MicroLogix 1100 / 1400 | **3000 ms** | Single-CPU, slow scan; no backplane |
| PLC-5 (Ethernet I/F) | 2500 ms | Comparable to SLC 5/05 over EIP |
| LogixPccc compat layer | 2000 ms | Logix CPU is fast; PCCC layer is the floor |
A small `--retries 1` (or `2` for slow chassis) is generally safe — the retry
loop only fires on transient `BadCommunicationError`; terminal errors
(`BadNodeIdUnknown`, `BadTypeMismatch`, …) surface on the first attempt.
## PCCC address primer
File letters imply data type; type flag still required so the CLI knows how to
parse your `--value`.
| File | Type | CLI `--type` |
|---|---|---|
| `N` | signed int16 | `Int` |
| `F` | float32 | `Float` |
| `B` | bit-packed (`B3:0/3` addresses bit 3 of word 0) | `Bit` |
| `L` | long int32 (SLC 5/05+ only) | `Long` |
| `A` | analog int (semantically like N) | `AnalogInt` |
| `ST` | ASCII string (82-byte + length header) | `String` |
| `T` | timer sub-element (`T4:0.ACC` / `.PRE` / `.EN` / `.DN`) | `TimerElement` |
| `C` | counter sub-element (`C5:0.ACC` / `.PRE` / `.CU` / `.CD` / `.DN`) | `CounterElement` |
| `R` | control sub-element (`R6:0.LEN` / `.POS` / `.EN` / `.DN` / `.ER`) | `ControlElement` |
## Commands
### `probe`
```powershell
# SLC 5/05 — default probe address N7:0
otopcua-ablegacy-cli probe -g ab://192.168.1.20/1,0
# MicroLogix 1100 — status file first word
otopcua-ablegacy-cli probe -g ab://192.168.1.30/ -P MicroLogix -a S:0
```
`probe` output (PR ablegacy-12 / #255) reports both `Health` (driver health
state) and `Host state`. The latter is sourced from `IHostConnectivityProbe`
and surfaces `Demoted` when the auto-demote threshold has tripped — a fast
visual signal that the CLI is short-circuiting future reads against this
device until the cool-down expires:
```text
Gateway: ab://192.168.1.20/1,0
PLC type: Slc500
Health: Degraded
Host state: Demoted
Last error: libplctag status -33 reading N7:0
```
### Auto-demote knobs
```powershell
# Trip after just one comm failure, hold for 60s.
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a N7:0 -t Int `
--demote-failure-threshold 1 --demote-for-ms 60000
# Opt out of auto-demote — stresses the link without short-circuiting.
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a N7:0 -t Int --no-demote
```
The CLI is a one-shot test client — auto-demote primarily matters in the
server-side multi-device deployment, where a single demoted PLC can no
longer block reads against its healthy peers. Use the CLI flags to
reproduce a flapping-link scenario locally before tuning the server-side
`appsettings.json` `Demote` block.
### `read`
```powershell
# Integer
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a N7:10 -t Int
# Float
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a F8:0 -t Float
# Bit-within-word
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a B3:0/3 -t Bit
# Long (SLC 5/05+)
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a L19:0 -t Long
# Timer ACC
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a T4:0.ACC -t TimerElement
# Diagnostic counter (PR ablegacy-10 / #253). The seven _Diagnostics/<name>
# addresses live alongside user tags — short-circuit serves them straight from
# the in-process counter store, so no PCCC frame is sent to the PLC.
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 --address _Diagnostics/RequestCount
```
The diagnostic surface auto-emits per device — no config required. See
`docs/drivers/AbLegacy-Diagnostics.md` for the full counter table + reset
semantics + collision-rejection rules.
### `write`
```powershell
otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a N7:10 -t Int -v 42
otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a F8:0 -t Float -v 3.14
otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a B3:0/3 -t Bit -v on
```
Writes to timer / counter / control sub-elements land at the wire level but
the PLC's runtime semantics (EN/DN edge-triggering, preset reload) are
PLC-managed — use with caution.
### `subscribe`
```powershell
otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a N7:10 -t Int -i 500
```
#### Deadband
PR 8 — per-tag absolute / percent change filter on top of the polled subscription. The driver
caches the last *published* value per tag and suppresses `OnDataChange` notifications until the
new sample crosses the configured threshold.
| Flag | Effect |
|---|---|
| `--deadband-absolute <value>` | Suppress until `|new - prev| >= value`. |
| `--deadband-percent <value>` | Suppress until `|new - prev| >= |prev * value / 100|`. `prev == 0` always publishes (avoids div-by-zero). |
Booleans bypass the filter entirely (every transition publishes); strings + status changes
always publish; first-seen always publishes; both flags set → either passing triggers a
publish (Kepware-style logical OR).
```powershell
# Float — drop sub-0.5 jitter from the noisy load-cell address.
otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a F8:0 -t Float -i 500 `
--deadband-absolute 0.5
# Integer — only fire on >= 5% deviation from the last reported value.
otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a N7:10 -t Int -i 500 `
--deadband-percent 5
```
## Array reads
PR 7 — one PCCC frame can carry up to ~120 words. Address an array tag with either the
Rockwell-native `,N` suffix or the libplctag-native `[N]` suffix on the word number; both
forms canonicalise to `[N]` when the driver hands the tag to libplctag, and the parser
caps `N` at 120.
```powershell
# Rockwell `,N` form — "10 consecutive words starting at N7:0"
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0,10" -t Int
# libplctag `[N]` form — same wire result
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0[10]" -t Int
# Float / Long arrays — same suffix syntax, narrower frame ceiling on Float (~60 elements)
# and Long (~60 elements) because each element is 4 bytes vs Int's 2.
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "F8:0,4" -t Float
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "L19:0,4" -t Long
# --array-length override — pin the element count from config rather than the address
# suffix. Wins over the parsed `,N` / `[N]` value when both are set; useful for keeping the
# address string compact while bumping the element count from a tags config file.
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0" --array-length 10 -t Int
```
Array tags reject sub-element references (`T4:0,5.ACC`) and bit suffixes (`N7:0,10/3`) at
parse time — both combinations are semantically meaningless against a contiguous block.
For `B`-files the Rockwell convention is "one BOOL per word, not per bit": `B3:0,10`
returns `bool[10]` (one per word's non-zero state), not `bool[160]`.
### `import-rslogix`
ablegacy-11 / [#254](https://github.com/dohertj2/lmxopcua/issues/254) — bulk-import RSLogix
500 / 5 CSV symbol exports into an `appsettings.json` tag fragment. Avoids hand-typing every
`N7:0` / `F8:12` / `B3:0/5` row of a several-hundred-tag PLC. Binary `.RSS` / `.RSP` project
files are out of scope; export to CSV first.
```powershell
# Default: emit JSON fragment to stdout
otopcua-ablegacy-cli import-rslogix `
--file C:\plc\plc-export.csv `
--device ab://192.168.1.20/1,0
# Write the fragment to a file + print a summary line to stdout
otopcua-ablegacy-cli import-rslogix `
--file C:\plc\plc-export.csv `
--device ab://192.168.1.20/1,0 `
--output tags.json
# Filter by Scope column — only import Local:1 program-scoped tags
otopcua-ablegacy-cli import-rslogix `
--file C:\plc\plc-export.csv `
--device ab://192.168.1.20/1,0 `
--scope Local:1
# Summary mode — one-line counter for CI / health checks
otopcua-ablegacy-cli import-rslogix `
--file C:\plc\plc-export.csv `
--device ab://192.168.1.20/1,0 `
--emit summary
```
| Flag | Default | Purpose |
|---|---|---|
| `-f` / `--file` | **required** | RSLogix CSV path |
| `-d` / `--device` | **required** | `ab://host[:port]/cip-path` every imported tag binds to |
| `--emit` | `appsettings-fragment` | `appsettings-fragment` (JSON) or `summary` (one-line counter) |
| `-o` / `--output` | stdout | Optional output file path |
| `--scope` | none | Scope filter — `Global` / `Local:N` (case-insensitive); empty Scope counts as Global |
| `--max-rows` | unlimited | Defensive cap on rows imported |
| `--strict` | off | Fail-fast on first malformed row (default permissive: skip + log) |
See [drivers/AbLegacy-RSLogix-Import.md](drivers/AbLegacy-RSLogix-Import.md) for the full
column reference, file-letter → `AbLegacyDataType` mapping, and the API surface
(`IRsLogixImporter`, `AbLegacyDriverOptions.AddRsLogixImport`).
## Known caveat — ab_server upstream gap
The integration-fixture `ab_server` Docker container accepts TCP but its PCCC
dispatcher doesn't actually respond — see
[`tests/...AbLegacy.IntegrationTests/Docker/README.md`](../tests/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.IntegrationTests/Docker/README.md).
Point `--gateway` at real hardware or an RSEmulate 500 box for end-to-end
wire-level validation. The CLI itself is correct regardless of which endpoint
you target.