dabd8eb955
MAJOR-1: the SDK skips TypeInfo.IsInstanceOfDataType on any node with an OnWriteValue handler (every writable equipment node), and the node manager's fail-fast treated numeric<->numeric as compatible, so a UInt32[] to a Galaxy Int32 array matched MxValueEncoder's int[] arm by CLR covariance and was written bit-reinterpreted with a Good result. EvaluateEquipmentWriteStructure now matches an ARRAY write's element type exactly (Byte[]/ByteString the only equivalence; Variant[]/object[] refused) -> BadTypeMismatch, nothing dispatched. MxValueEncoder's int[]/long[] arms are exact-type guarded too, and the Galaxy parity test's false "the SDK refuses" premise is corrected (the UInt32/UInt64 exclusion is now the encoder's own answer). Scalar writes keep numeric widening by decision: consumers write CLR-typed values (Double to a Float node) and every driver's scalar encoder range-checks. MINOR: Modbus row honours maxRegistersPerWrite (smallest of DriverConfig / the tag's DeviceConfig, default 123) and FC15's 1968-coil ceiling, and requires region + numeric address; Modbus/S7/Galaxy require isArray + integer arrayLength >= 1 (Galaxy: an unbounded node would let a short write resize the attribute); an array value to a scalar node is refused inline. Docs: Uns.md array-write rules + upgrade note (ReadWrite array tags become client-writable on first boot), Modbus.md, Galaxy.md. Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe