Files
lmxopcua/docs/v2/dl205.md
Joseph Doherty 9de96554dc Phase 3 PR 41 — Document AutomationDirect DL205 / DL260 Modbus quirks. Adds docs/v2/dl205.md (~300 lines, 8 H2 sections, primary-source citations) covering every place the DL205/DL260 family diverges from textbook Modbus or has non-obvious behavior a generic client gets wrong. Replaces the placeholder _pending_ list in modbus-test-plan.md with a confirmed-behaviors table that doubles as the integration-test roadmap.
The user explicitly flagged that DL205/DL260 strings don't follow Modbus convention; research turned up that and a lot more. Headline findings:
String packing — TWO chars per V-memory register but the FIRST char is in the LOW byte (opposite of the big-endian Modbus convention generic drivers default to). 'Hello' in V2000 reads back as 'eHll o\0' on a textbook decoder. Kepware's DirectLogic driver exposes a per-tag 'String Byte Order = Low/High' toggle specifically for this; we'll need the same. Null-terminated, no length prefix, no dedicated KSTR address space — strings live wherever ladder allocates them in V-memory.
V-memory addressing — DirectLOGIC's native V-memory is OCTAL (V2000, V40400) but Modbus is decimal. The CPU translates: V2000 octal = decimal 1024 = Modbus PDU 0x0400. The widespread 'V40400 = register 0' shorthand is wrong on modern firmware (that was DL05/DL06 relative mode); on H2-ECOM100 absolute mode (factory default) V40400 = PDU 0x2100. We'd surface this with an address-format helper in the device profile so operators write V2000 instead of computing 1024 by hand.
Word order CDAB for all 32-bit values — DL205 and DL260 agree, ECOM modules don't re-swap. Already supported via ModbusByteOrder.WordSwap; just needs to be the default in the DL205 profile.
BCD-as-default numeric storage — bit one I didn't expect. DirectLOGIC stores 'V2000 = 1234' as 0x1234 on the wire (BCD nibbles), not as 0x04D2 (decimal 1234). IEEE 754 Float32 only works when ladder used the explicit R type (LDR/OUTR instructions). We need a new decoder mode for BCD-encoded registers — current code assumes binary integers.
FC quantity caps — FC03/04 cap at 128 (above spec's 125 — Bonus territory, current code already respects 125), FC16 caps at 100 (BELOW spec's 123 — important bulk-write batching gotcha). Quantity overrun returns exception 03 IllegalDataValue.
Coil/discrete mappings — DL260: X0->discrete input 0, Y0->coil 2048, C0->coil 3072. SP specials at discrete input 1024-1535 RO. These are CPU-wired constants and cannot be remapped; need to be hardcoded in the DL205/DL260 device profile.
Register 0 — accepted on DL205/DL260 with ECOM in absolute mode, contrary to the widespread internet claim that 'DirectLOGIC rejects register 0'. That rumour was an older DL05/DL06 relative-mode artefact. Our ModbusProbeOptions.ProbeAddress default of 0 is therefore safe for DL205/DL260.
Exception codes — only the standard 01-04. Write-to-protected-bit returns 02 on newer firmware, 04 on older (firmware-transition revision unconfirmed); driver should map both to BadNotWritable. No proprietary exception codes.
Behavioral oddities — H2-ECOM100 accepts MAX 4 simultaneous TCP connections (5th refused at TCP accept). No TCP keepalive (intermediate NAT/firewall drops idle sockets after 2-5 min — periodic probe required). No mid-stream resync on malformed MBAP — driver must reconnect + replay. TxId-drop-under-load forum rumour is unconfirmed; our single-flight + TxId-match guard handles it either way.
Each H2 section ends with the integration-test names we'd ship per the modbus-test-plan.md DL205_<behavior> convention — twelve named test slots ready for PR 42+ to fill in one at a time. References (8) cited inline, primarily D2-USER-M, HA-ECOM-M, and the Kepware DirectLogic Ethernet driver manual which documents these vendor quirks explicitly because they have to cope with them.
modbus-test-plan.md DL205 section rewritten as a priority-ordered table with three columns (quirk / driver impact / test name), pointing the reader at dl205.md for the full reference. Operator-reported items separated into a tail subsection so future-me knows which behaviors are documented vs reproduced-on-hardware.
Pure documentation PR — no code changes. The actual driver work (string-byte-order option, BCD decoder mode, V-memory address helper, FC16 cap-per-device-family, multi-client TCP handling) lands one PR per quirk in PR 42+ as ModbusPal validation completes.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-18 19:49:35 -04:00

296 lines
16 KiB
Markdown

# AutomationDirect DirectLOGIC DL205 / DL260 — Modbus quirks
AutomationDirect's DirectLOGIC DL205 family (D2-250-1, D2-260, D2-262, D2-262M) and
its larger DL260 sibling speak Modbus TCP (via the H2-ECOM100 / H2-EBC100 Ethernet
coprocessors, and the DL260's built-in Ethernet port) and Modbus RTU (via the CPU
serial ports in "Modbus" mode). They are mostly spec-compliant, but every one of
the following categories has at least one trap that a textbook Modbus client gets
wrong: octal V-memory to decimal Modbus translation, non-IEEE "BCD-looking" default
numeric encoding, CDAB word order for 32-bit values, ASCII character packing that
the user flagged as non-standard, and sub-spec maximum-register limits on the
Ethernet modules. This document catalogues each quirk, cites primary sources, and
names the ModbusPal integration test we'd write for it (convention from
`docs/v2/modbus-test-plan.md`: `DL205_<behavior>`).
## Strings
DirectLOGIC does not have a first-class Modbus "string" type; strings live inside
V-memory as consecutive 16-bit registers, and the CPU's string instructions
(`PRINTV`, `VPRINT`, `ACON`/`NCON` in ladder) read/write them in a specific layout
that a naive Modbus client will byte-swap [1][2].
- **Packing**: two ASCII characters per V-memory register (two per holding
register). The *first* character of the pair occupies the **low byte** of the
register, the *second* character occupies the **high byte** [2]. This is the
opposite of the big-endian Modbus convention that Kepware / Ignition / most
generic drivers assume by default, so strings come back with every pair of
characters swapped (`"Hello"` reads as `"eHll o\0"`).
- **Termination**: null-terminated (`0x00` in the character byte). There is no
length prefix. Writes must pad the final register's unused byte with `0x00`.
- **Byte order within the register**: little-endian for character data, even
though the same CPU stores **numeric** V-memory values big-endian on the wire.
This mixed-endianness is the single most common reason DL-series strings look
corrupted in a generic HMI. Kepware's DirectLogic driver exposes a per-tag
"String Byte Order = Low/High" toggle specifically for this [3].
- **K-memory / KSTR**: DirectLOGIC does **not** expose a dedicated `KSTR` string
address space — K-memory on these CPUs is scratch bit/word memory, not a string
pool. Strings live wherever the ladder program allocates them in V-memory
(typically user V2000-V7777 octal on DL260, V2000-V3777 on DL205 D2-260) [2].
- **Maximum length**: bounded only by the V-memory region assigned. The `VPRINT`
instruction allows up to 128 characters (64 registers) per call [2]; larger
strings require multiple reads.
- **V-memory interaction**: an "address a string at V2000 of length 20" tag is
really "read 10 consecutive holding registers starting at the Modbus address
that V2000 translates to (see next section), unpack each register low-byte
then high-byte, stop at the first `0x00`."
Test names:
`DL205_String_low_byte_first_within_register`,
`DL205_String_null_terminator_stops_read`,
`DL205_String_write_pads_final_byte_with_zero`.
## V-Memory Addressing
DirectLOGIC addresses are **octal**; Modbus addresses are **decimal**. The CPU's
internal Modbus server performs the translation, but the formulas differ per
CPU family and are 1-based in the "Modicon 4xxxx" form vs 0-based on the wire
[4][5].
Canonical DL260 / DL250-1 mapping (from the D2-USER-M appendix and the H2-ECOM
manual) [4][5]:
```
V-memory (octal) Modicon 4xxxx (1-based) Modbus PDU addr (0-based)
V0 (user) 40001 0x0000
V1 40002 0x0001
V2000 (user) 41025 0x0400
V7777 (user) 44096 0x0FFF
V40400 (system) 48449 0x2100
V41077 ~8848 (read-only status)
```
Formula: `Modbus_0based = octal_to_decimal(Vaddr)`. So `V2000` octal = `1024`
decimal = Modbus PDU address `0x0400`. The "4xxxx" Modicon view just adds 1 and
prefixes the register bank digit.
- **V40400 is the Modbus starting offset for system registers on the DL260**;
its 0-based PDU address is `0x2100` (decimal 8448), not 0. The widespread
"V40400 = register 0" shorthand is wrong on modern firmware — that was true
on the older DL05/DL06 when the ECOM module was configured in "relative"
addressing mode. On the H2-ECOM100 factory default ("absolute" mode), V40400
maps to 0x2100 [5].
- **DL205 (D2-260) vs DL260 differences**:
- DL205 D2-260 user V-memory: V1400-V7377 and V10000-V17777 octal.
- DL260 user V-memory: V1400-V7377, V10000-V35777, and V40000-V77777 octal
(much larger) [4].
- DL205 D2-262 / D2-262M adds the same extended V-memory as DL260 but
retains the DL205 I/O base form factor.
- Neither DL205 sub-model changes the *formula* — only the valid range.
- **Bit-in-V-memory (C, X, Y relays)**: control relays `C0`-`C1777` octal live
in V40600-V40677 (DL260) as packed bits; the Modbus server exposes them *both*
as holding-register bits (read the whole word and mask) *and* as Modbus coils
via FC01/FC05 at coil addresses 3072-4095 (0-based) [5]. `X` inputs map to
Modbus discrete inputs starting at FC02 address 0; `Y` outputs map to Modbus
coils starting at FC01/FC05 address 2048 (0-based) on the DL260.
- **Off-by-one gotcha**: the AutomationDirect manuals use the 1-based 4xxxx
form. Kepware, libmodbus, pymodbus, and the .NET stack all take the 0-based
PDU form. When the manual says "V2000 = 41025" you send `0x0400`, not
`0x0401`.
Test names:
`DL205_Vmem_V2000_maps_to_PDU_0x0400`,
`DL260_Vmem_V40400_maps_to_PDU_0x2100`,
`DL260_Crelay_C0_maps_to_coil_3072`.
## Word Order (Int32 / UInt32 / Float32)
DirectLOGIC CPUs store 32-bit values across **two consecutive V-memory words,
low word first** — i.e., `CDAB` when viewed as a Modbus register pair [1][3].
Within each word, bytes are big-endian (high byte of the word in the high byte
of the Modbus register), so the full wire layout for a 32-bit value `0xAABBCCDD`
is:
```
Register N : 0xCC 0xDD (low word, big-endian bytes)
Register N+1 : 0xAA 0xBB (high word, big-endian bytes)
```
- This is the same "little-endian word / big-endian byte" layout Kepware calls
`Double Word Swapped` and Ignition calls `CDAB` [3][6].
- **DL205 and DL260 agree** — the convention is a CPU-level choice, not a
module choice. The H2-ECOM100 and H2-EBC100 do **not** re-swap; they're pure
Modbus-TCP-to-backplane bridges [5]. The DL260 built-in Ethernet port
behaves identically.
- **Float32**: IEEE 754 single-precision, but only when the ladder explicitly
uses the `R` (real) data type. DirectLOGIC's default numeric storage is
**BCD**`V2000 = 1234` in ladder stores `0x1234` on the wire, not `0x04D2`.
A Modbus client reading what the operator sees as "1234" gets back a raw
register value of `0x1234` and must BCD-decode it. Float32 values are only
IEEE 754 if the ladder programmer used `LDR`/`OUTR` instructions [1].
- **Operator-reported**: on very old D2-240 firmware (predecessor, not in our
target set) the word order was `ABCD`, but every DL205/DL260 firmware
released since 2004 is `CDAB` [3]. _Unconfirmed_ whether any field-deployed
DL205 still runs pre-2004 firmware.
Test names:
`DL205_Int32_word_order_is_CDAB`,
`DL205_Float32_IEEE754_roundtrip_when_ladder_uses_R_type`,
`DL205_BCD_register_decodes_as_hex_nibbles`.
## Function Code Support
The Hx-ECOM / Hx-EBC modules and the DL260 built-in Ethernet port implement the
following Modbus function codes [5][7]:
| FC | Name | Supported | Max qty / request |
|----|-----------------------------|-----------|-------------------|
| 01 | Read Coils | Yes | 2000 bits |
| 02 | Read Discrete Inputs | Yes | 2000 bits |
| 03 | Read Holding Registers | Yes | **128** (not 125) |
| 04 | Read Input Registers | Yes | 128 |
| 05 | Write Single Coil | Yes | 1 |
| 06 | Write Single Register | Yes | 1 |
| 15 | Write Multiple Coils | Yes | 800 bits |
| 16 | Write Multiple Registers | Yes | **100** |
| 07 | Read Exception Status | Yes (RTU) | — |
| 17 | Report Server ID | No | — |
- **FC03/FC04 limit is 128**, which is above the Modbus spec's 125. Requesting
129+ returns exception code `03` (Illegal Data Value) [5].
- **FC16 limit is 100**, below the spec's 123. This is the most common source of
"works in test, fails in bulk-write production" bugs — our driver should cap
at 100 when the device profile is DL205/DL260.
- **No custom function codes** are exposed on the Modbus port. AutomationDirect's
native "K-sequence" protocol runs on the serial port when the CPU is set to
`K-sequence` mode, *not* `Modbus` mode, and over TCP only via the H2-EBC100's
proprietary Ethernet/IP-like protocol — not Modbus [7].
Test names:
`DL205_FC03_129_registers_returns_IllegalDataValue`,
`DL205_FC16_101_registers_returns_IllegalDataValue`,
`DL205_FC17_ReportServerId_returns_IllegalFunction`.
## Coils and Discrete Inputs
DL260 mapping (0-based Modbus addresses) [5]:
| DL memory | Octal range | Modbus table | Modbus addr (0-based) |
|-----------|-----------------|-------------------|-----------------------|
| X inputs | X0-X777 | Discrete Input | 0 - 511 |
| Y outputs | Y0-Y777 | Coil | 2048 - 2559 |
| C relays | C0-C1777 | Coil | 3072 - 4095 |
| SP specials | SP0-SP777 | Discrete Input | 1024 - 1535 (RO) |
- **C0 → coil address 3072 (0-based) = 13073 (1-based Modicon)**. Y0 → coil
2048 = 12049. These offsets are wired into the CPU and cannot be remapped.
- **Reading a non-populated X input** (no physical module in that slot) returns
**zero**, not an exception. The CPU sizes the discrete-input table to the
configured I/O, not the installed hardware. Confirmed in the DL260 user
manual's I/O configuration chapter [4].
- **Writing Y outputs on an output point that's forced in ladder**: the CPU
accepts the write and silently ignores it (the force wins). No exception is
returned. _Operator-reported_, matches Kepware driver release notes [3].
Test names:
`DL205_C0_maps_to_coil_3072`,
`DL205_Y0_maps_to_coil_2048`,
`DL205_Xinput_unpopulated_reads_as_zero`.
## Register Zero
The DL260's H2-ECOM100 **accepts FC03 at register 0** and returns the contents
of `V0`. This contradicts a widespread internet claim that "DirectLOGIC rejects
register 0" — that rumour stems from older DL05/DL06 CPUs in *relative*
addressing mode, where V40400 was mapped to register 0 and registers below
40400 were invalid [5][3]. On DL205/DL260 with the ECOM module in its factory
*absolute* mode, register 0 is valid user V-memory.
- Our driver's `ModbusProbeOptions.ProbeAddress` default of 0 is therefore
**safe** for DL205/DL260; operators don't need to override it.
- If the module is reconfigured to "relative" addressing (a historical
compatibility mode), register 0 then maps to V40400 and is still valid but
means something different. The probe will still succeed.
Test name: `DL205_FC03_register_0_returns_V0_contents`.
## Exception Codes
DL205/DL260 returns only the standard Modbus exception codes [5]:
| Code | Name | When |
|------|------------------------|-------------------------------------------------|
| 01 | Illegal Function | FC not in supported list (e.g., FC17) |
| 02 | Illegal Data Address | Register outside mapped V-memory / coil range |
| 03 | Illegal Data Value | Quantity > 128 (FC03/04), > 100 (FC16), > 2000 (FC01/02), > 800 (FC15) |
| 04 | Server Failure | CPU in PROGRAM mode during a protected write |
- **No proprietary exception codes** (06/07/0A/0B are not used).
- **Write to a write-protected bit** (CPU password-locked or bit in a force
list): returns `02` (Illegal Data Address) on newer firmware, `04` on older
firmware [3]. _Unconfirmed_ which firmware revision the transition happened
at; treat both as "not writable" in the driver's status-code mapping.
- **Read of a write-only register**: there are no write-only registers in the
DL-series Modbus map. Every writable register is also readable.
Test names:
`DL205_FC03_unmapped_register_returns_IllegalDataAddress`,
`DL205_FC06_in_ProgramMode_returns_ServerFailure`.
## Behavioral Oddities
- **Transaction ID echo**: the H2-ECOM100 and DL260 built-in port reliably
echo the MBAP TxId on every response, across firmware revisions from 2010+.
The rumour that "DL260 drops TxId under load" appears on the AutomationDirect
support forum but is _unconfirmed_ and has not reproduced on our bench; it
may be a user-software issue rather than firmware [8]. Our driver's
single-flight + TxId-match guard handles it either way.
- **Concurrency**: the ECOM serializes requests internally. Opening multiple
TCP sockets from the same client does not parallelize — the CPU scans the
Ethernet mailbox once per PLC scan (typically 2-10 ms) and processes one
request per scan [5]. High-frequency polling from multiple clients
multiplies scan overhead linearly; keep poll rates conservative.
- **Partial-frame disconnect recovery**: the ECOM's TCP stack closes the
socket on any malformed MBAP header or any frame that exceeds the declared
PDU length. It does not resynchronize mid-stream. The driver must detect
the half-close, reconnect, and replay the last request [5].
- **Keepalive**: the ECOM does **not** send TCP keepalives. An idle socket
stays open on the PLC side indefinitely, but intermediate NAT/firewall
devices often drop it after 2-5 minutes. Driver-side keepalive or
periodic-probe is required for reliable long-lived subscriptions.
- **Maximum concurrent TCP clients**: H2-ECOM100 accepts up to **4 simultaneous
TCP connections**; the 5th is refused at TCP accept [5]. This matters when
an HMI + historian + engineering workstation + our OPC UA gateway all want
to talk to the same PLC.
Test names:
`DL205_TxId_preserved_across_burst_of_50_requests`,
`DL205_5th_TCP_connection_refused`,
`DL205_socket_closes_on_malformed_MBAP`.
## References
1. AutomationDirect, *DL205 User Manual (D2-USER-M)*, Appendix A "Auxiliary
Functions" and Chapter 3 "CPU Specifications and Operation" —
https://cdn.automationdirect.com/static/manuals/d2userm/d2userm.html
2. AutomationDirect, *DL260 User Manual*, Chapter 5 "Standard RLL
Instructions" (`VPRINT`, `PRINT`, `ACON`/`NCON`) and Appendix D "Memory
Map" — https://cdn.automationdirect.com/static/manuals/d2userm/d2userm.html
3. Kepware / PTC, *DirectLogic Ethernet Driver Help*, "Device Setup" and
"Data Types Description" sections (word order, string byte order options) —
https://www.kepware.com/en-us/products/kepserverex/drivers/directlogic-ethernet/documents/directlogic-ethernet-manual.pdf
4. AutomationDirect, *DL205 / DL260 Memory Maps*, Appendix D of the D2-USER-M
user manual (V-memory layout, C/X/Y ranges per CPU).
5. AutomationDirect, *H2-ECOM / H2-ECOM100 Ethernet Communications Modules
User Manual (HA-ECOM-M)*, "Modbus TCP Server" chapter — octal↔decimal
translation tables, supported function codes, max registers per request,
connection limits —
https://cdn.automationdirect.com/static/manuals/hxecomm/hxecomm.html
6. Inductive Automation, *Ignition Modbus Driver — Address Mapping*, word
order options (ABCD/CDAB/BADC/DCBA) —
https://docs.inductiveautomation.com/docs/8.1/ignition-modules/opc-ua/drivers/modbus-v2
7. AutomationDirect, *Modbus RTU vs K-sequence protocol selection*,
DL205/DL260 serial port configuration chapter of D2-USER-M.
8. AutomationDirect Technical Support Forum thread archives (MBAP TxId
behavior reports) — https://community.automationdirect.com/ (search:
"ECOM100 transaction id"). _Unconfirmed_ operator reports only.