Found by the read-only live gate against the TwinCAT 2.11 Elma cleaners Z33856 / Z33733: - The Beckhoff library reports a TC2 dotted MEMBER symbol's ByteSize as if the PLC's byte count were a bit count (STRING(80) -> 11, INT -> 1, UDINT -> 1) while DataType.ByteSize is right (81/2/4, raw SYM_INFOBYNAMEEX says 81). The previous commit's typeof(byte[]) read sliced by the symbol size, so .OPC_MACHINEDATA.PROCESSSTATUS read "ready for o" at Good; the notification width check would also have refused every numeric member. The shape now takes the resolved type's size, and string reads go by index group/offset (or a fresh handle for 0xF005) at that width. - P_INITINPUT_ACTION.SLOTID is "STRING(20) (VAR_IN_OUT)" - a 4-byte reference - but resolves to a plain STRING(20); a String tag read 21 bytes at the pointer as text at Good. The symbol's own VAR_IN_OUT marker now classifies it NonScalar -> BadTypeMismatch.
300 lines
17 KiB
Markdown
300 lines
17 KiB
Markdown
# Beckhoff TwinCAT (ADS) Driver
|
||
|
||
Getting-started guide for the Beckhoff TwinCAT driver. This is the short path —
|
||
for the full per-field spec read [`docs/v2/driver-specs.md §6`](../v2/driver-specs.md),
|
||
for hands-on CLI testing read [Driver.TwinCAT.Cli.md](../Driver.TwinCAT.Cli.md),
|
||
and for the test-harness map read [TwinCAT-Test-Fixture.md](TwinCAT-Test-Fixture.md).
|
||
|
||
## What it talks to
|
||
|
||
Beckhoff PLC runtimes — **TwinCAT 2 and TwinCAT 3** — over the Beckhoff **ADS**
|
||
protocol carried by **AMS** routing. The driver runs in-process in the OtOpcUa
|
||
server's .NET 10 AnyCPU host. It compiles and runs without a local AMS router,
|
||
but every wire call returns `BadCommunicationError` until a router is reachable
|
||
(the router translates an AMS Net ID to an IP route).
|
||
|
||
Addressing is **symbol-based**: tags are referenced by their TwinCAT symbolic
|
||
name (e.g. `MAIN.bStart`, `GVL.Counter`, `Motor1.Status.Running`) rather than by
|
||
raw memory offset. One driver instance fans out to N targets, each identified by
|
||
an AMS Net ID + port.
|
||
|
||
## Project split
|
||
|
||
| Project | Target | Role |
|
||
|---------|--------|------|
|
||
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT/` | net10.0 | In-process driver — hosts the ADS client, symbol-path parser, and per-device probe loops |
|
||
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT.Contracts/` | net10.0 | Config records + the `TwinCATDataType` enum bound from `DriverConfig` JSON |
|
||
|
||
## Minimum deployment
|
||
|
||
```jsonc
|
||
"Drivers": {
|
||
"twincat-cell-1": {
|
||
"Type": "TwinCAT",
|
||
"Config": {
|
||
"Devices": [ { "HostAddress": "ads://5.23.91.23.1.1:851", "DeviceName": "Cell1" } ],
|
||
"Tags": [
|
||
{ "Name": "Start", "DeviceHostAddress": "ads://5.23.91.23.1.1:851",
|
||
"SymbolPath": "MAIN.bStart", "DataType": "Bool", "Writable": true },
|
||
{ "Name": "Count", "DeviceHostAddress": "ads://5.23.91.23.1.1:851",
|
||
"SymbolPath": "GVL.Counter", "DataType": "Int32", "Writable": false }
|
||
]
|
||
}
|
||
}
|
||
}
|
||
```
|
||
|
||
### AMS address form
|
||
|
||
`HostAddress` is an `ads://{netId}:{port}` URI parsed by
|
||
`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT/TwinCATAmsAddress.cs`. The Net ID
|
||
is six dot-separated octets (NOT an IP — a Beckhoff-specific identifier the
|
||
router maps to a route); the port is the AMS service port (851 = TC3 PLC runtime
|
||
1, 852 = runtime 2, 801 / 811 / 821 = TC2 PLC runtimes). Port defaults to 851
|
||
when omitted (`ads://5.23.91.23.1.1`) — **a TwinCAT 2 target must name `:801`**.
|
||
|
||
The driver never registers a route on the PLC: it sends no UDP `AddRoute` and
|
||
writes nothing to the PLC's route table. The route from the PLC back to this
|
||
host's AMS Net ID (and the AMS router's route to the PLC) is provisioned
|
||
out-of-band — the same posture as the ignitionoee driver's
|
||
`Register Route on Connect = off` (TwinCAT-009).
|
||
|
||
### Symbol path form
|
||
|
||
Symbol paths are parsed by
|
||
`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT/TwinCATSymbolPath.cs`, which
|
||
mirrors IEC 61131-3 structured-text identifiers: global-variable-list
|
||
(`GVL.Counter`), program variable (`MAIN.bStart`), struct member access
|
||
(`Motor1.Status.Running`), array subscripts (`Data[5]`, `Matrix[1,2]`), and
|
||
bit-access (`Flags.0`).
|
||
|
||
**TwinCAT 2 globals keep their leading dot.** A TC2 global is named with ONE
|
||
leading dot (`.OPC_HEARTBEAT`, `.OPC_MACHINEDATA.PROCESSSTATUS`,
|
||
`.ARRCARRIERDATA_V[1].SWORKORDER`) and the PLC requires it — without it
|
||
`SYM_HNDBYNAME` answers 0x710 (symbol not found), observed live on a TC 2.11 CX.
|
||
The parser keeps the dot on the root segment, so bit access on a TC2 global
|
||
(`.OPC_STATUS.WORD.3`) still reads the parent word `.OPC_STATUS.WORD`. Exactly one
|
||
dot: `..x`, `.` and `.[1]` are rejected. (Before this, the dot made the parser
|
||
give up and the raw string went to ADS verbatim, losing bit-index handling.)
|
||
|
||
**BOOL-within-word writes** — writing a bit-access path (e.g. `MAIN.Flags.3`)
|
||
is a driver-level parent-word read-modify-write: the driver reads the parent
|
||
word as `UDInt`, flips the target bit, and writes the word back, under a
|
||
per-parent lock. The lock serialises the driver's own concurrent bit-writers
|
||
against the same word, but cannot guard against the PLC program writing that
|
||
word between the driver's read and write — this is an inherent limitation of
|
||
any software-level RMW.
|
||
|
||
## Tag discovery
|
||
|
||
`DiscoverAsync` always emits the pre-declared `Tags` as the authoritative config
|
||
path, under `TwinCAT/{device}/`. When `EnableControllerBrowse` is set, the
|
||
driver also walks each device's symbol table and surfaces controller-resident
|
||
globals / program locals under a `Discovered/` sub-folder; any symbol-loader
|
||
error falls back to pre-declared-only so a flaky symbol download never blocks
|
||
discovery.
|
||
|
||
Discovered variables are named by their full instance path (flat, no dot
|
||
splitting), so a TC2 global appears as `.OPC_HEARTBEAT` — with its dot, never
|
||
as an empty-named folder. TwinCAT 2 reports many top-level integers by their
|
||
ADS base-type name (`INT16`, `UINT16` — 354 symbols on a real TC 2.11 Elma
|
||
cleaner) and pads some member type names (`"REAL "`); both map like their IEC
|
||
twins, so those symbols are no longer silently dropped. The CLI `browse
|
||
--prefix` filter is a case-sensitive `StartsWith` on that name, so filter TC2
|
||
globals with the dot (`--prefix .OPC_`; `OPC_` matches nothing).
|
||
|
||
## Strings and declared-type checking
|
||
|
||
Ported from the ignitionoee TwinCAT driver (0.19.2–0.19.4), where each was
|
||
found against a real TwinCAT 2 PLC:
|
||
|
||
- **A `String` / `WString` tag matches a PLC `STRING(n)` / `WSTRING(n)` of any
|
||
`n`** and is read at the PLC's own width — `STRING(n)` is n+1 bytes,
|
||
`WSTRING(n)` 2(n+1). This also applies to native notifications, which
|
||
previously could not register a string at all (the Beckhoff marshaller needs
|
||
an explicit length and threw), taking the rest of that subscribe call down
|
||
with it.
|
||
- **A string ends at its first NUL** (`0x00` for STRING, an aligned `U+0000`
|
||
for WSTRING). Bytes after it are stale content from a longer earlier value
|
||
(live: work order `67504440` read back with a stale `"\0" + "1"` tail).
|
||
- **A STRING decodes as Windows-1252** (umlauts, `°` in alarm texts), or UTF-8
|
||
when the target reports UTF-8 string data (TwinCAT 3.1 4026+ "UTF8 Encoding
|
||
for STRING"). It no longer depends on the server's culture — the Beckhoff
|
||
marshaller falls back to the host's ANSI code page, which is 1250 on a Polish
|
||
host. Writes still go through the Beckhoff marshaller.
|
||
- **String-ness is a kind.** A numeric tag over a PLC string, a string tag over
|
||
a numeric, `String` over a `WSTRING` (or vice versa), and a string over a
|
||
struct/array are refused with `BadTypeMismatch` and a WARN, instead of
|
||
publishing the PLC's bytes as the wrong type at Good.
|
||
- **Native notifications are additionally width- and float-checked.** A
|
||
notification delivers raw bytes decoded as the *declared* type, so `DInt`
|
||
over a PLC `REAL` (same width, bit pattern reinterpreted) or `DInt` over
|
||
`LINT` (truncated) is refused too. A same-width, same-kind divergence (`DInt`
|
||
vs `UDINT`, `Time` vs a 4-byte integer) is tolerated. A refused tag is
|
||
isolated: it publishes `BadTypeMismatch`, the rest of the subscription
|
||
registers, and the probe-tick retry re-checks it after a PLC program change.
|
||
Reads go through the Beckhoff symbol cache, which converts numeric values by
|
||
the PLC's own type, so only the string-kind rule applies there.
|
||
- **Sizes come from the resolved data type, not the symbol.** On a TwinCAT 2
|
||
target the Beckhoff library reports a dotted *member* symbol's `ByteSize` as if
|
||
the PLC's byte count were a bit count (`.OPC_MACHINEDATA.PROCESSSTATUS`
|
||
`STRING(80)` → 11 B, an `INT` member → 1, a `UDINT` → 1) while its resolved
|
||
`DataType.ByteSize` is correct (81 / 2 / 4, matching raw `SYM_INFOBYNAMEEX`).
|
||
String reads therefore address the symbol's index group/offset explicitly at
|
||
the type's width — sizing them by the symbol truncated `"ready for operation"`
|
||
to `"ready for o"` at Good.
|
||
- **A `VAR_IN_OUT` member is a reference, not a value.** TC2 names it
|
||
`STRING(20) (VAR_IN_OUT)` (4 bytes) but the library resolves its type to the
|
||
plain `STRING(20)`; the symbol's own name wins and such a tag is refused
|
||
(`BadTypeMismatch`) instead of publishing the memory at the pointer as text.
|
||
|
||
### Live validation (2026-10-07, TwinCAT 2.11 Elma cleaners)
|
||
|
||
Read-only, against Z33856 (`10.201.45.236.1.1:801`) and Z33733
|
||
(`5.25.53.46.1.1:801`) over the VPN, through an in-process
|
||
`Beckhoff.TwinCAT.Ads.TcpRouter` in a scratch harness: ReadState RUN; browse
|
||
discovered 45,083 / 42,666 variables incl. the `INT16`/`UINT16` globals
|
||
(`.ACTUALOPERATIONMODE`, `.ADSSTATE_RUN`) and 3,663 / 3,564 leading-dot names, no
|
||
empty names; `.ADSSTATE_RUN` = 5 with bits `.0`/`.1`/`.2` = true/false/true;
|
||
work-order and part-number strings whose PLC buffers carry a stale tail after
|
||
the NUL (`68261005\0` + `01`) read as `68261005` through both poll and native
|
||
notifications; `DInt` over a `STRING(80)` → `BadTypeMismatch` in both paths with
|
||
the rest of the subscription Good. No PLC value held a genuine non-ASCII string
|
||
to exercise Windows-1252 live — that rule is unit-tested only.
|
||
|
||
## Capability surface
|
||
|
||
`TwinCATDriver : IDriver, IReadable, IWritable, ITagDiscovery, ISubscribable, IHostConnectivityProbe, IPerCallHostResolver, IRediscoverable`
|
||
(`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT/TwinCATDriver.cs`).
|
||
|
||
| Capability | Path | Notes |
|
||
|------------|------|-------|
|
||
| `IReadable` | `ReadAsync` → ADS `ReadValueAsync` | Per-device client, lazily connected and serialized per device |
|
||
| `IWritable` | `WriteAsync` → ADS `WriteValueAsync` | BOOL-within-word writes (e.g. `MAIN.Flags.3`) use a driver-level parent-word read-modify-write (read as UDInt, flip bit, write back) under a per-parent lock. Read-only tags return `BadNotWritable`. |
|
||
| `ITagDiscovery` | `DiscoverAsync` | Pre-declared tags + opt-in controller symbol browse |
|
||
| `ISubscribable` | native ADS notifications (default), poll fallback | `UseNativeNotifications=true` registers device notifications so the PLC pushes changes; `false` uses the shared `PollGroupEngine` |
|
||
| `IHostConnectivityProbe` | per-device probe loop | One `HostConnectivityStatus` per configured device; `Running`/`Stopped` transitions raise `OnHostStatusChanged` |
|
||
| `IPerCallHostResolver` | `ResolveHost` lookup in the tag map | Routes each call to the device of the referenced tag; returns an empty-string sentinel when unresolved |
|
||
| `IRediscoverable` | symbol-version-changed callback | A PLC re-download fires `OnRediscoveryNeeded`. ⚠️ **No consumer wires it today** ([#518](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/518), [#507](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/507)) — the address space does **not** rebuild; a config redeploy is required. Driver-side behaviour is log-observable only |
|
||
|
||
### Rediscovery on PLC re-download
|
||
|
||
`IRediscoverable` is the distinguishing capability. When the ADS client detects
|
||
`DeviceSymbolVersionInvalid` (1809 / 0x0711) — the documented TwinCAT
|
||
symbol-version-changed signal, raised when a PLC program is re-downloaded —
|
||
every symbol and notification handle is invalidated. The driver raises
|
||
`OnRediscoveryNeeded` with a `TwinCAT` scope hint, so that the signal is treated
|
||
as an address-space change rather than a transient connection error.
|
||
|
||
⚠️ **That is the intended design, not present behaviour.** No consumer subscribes
|
||
to `OnRediscoveryNeeded` anywhere in `src/`, and the scope hint is read by nothing
|
||
([#518](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/518),
|
||
[#507](https://gitea.dohertylan.com/dohertj2/lmxopcua/issues/507)). Today the
|
||
signal is observable only in the driver log; after a PLC re-download the served
|
||
address space changes only on a config redeploy.
|
||
|
||
### Native notifications
|
||
|
||
By default the driver registers native ADS device notifications: the PLC pushes
|
||
value changes on its own cycle, which is strictly better for latency and CPU
|
||
than polling. `NotificationMaxDelayMs` lets TwinCAT coalesce notifications up to
|
||
a batching delay for high-churn signals. Set `UseNativeNotifications=false` for
|
||
deployments where the AMS router has notification limits you can't raise — then
|
||
the driver falls through to the shared poll engine.
|
||
|
||
## Single-connection-per-device
|
||
|
||
Each device's ADS client is lazily connected and serialized by a per-device
|
||
connect gate, so a concurrent read / write / probe can't race a client
|
||
create-or-dispose. Probe-initiated connects use the probe timeout; reads and
|
||
writes use the driver-wide `Timeout`.
|
||
|
||
## Testing
|
||
|
||
- **Unit tests** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT.Tests/` cover
|
||
the AMS / symbol-path parsers, the status mapper, and the driver lifecycle via
|
||
a fake ADS client factory.
|
||
- **Integration fixture** — see
|
||
[TwinCAT-Test-Fixture.md](TwinCAT-Test-Fixture.md) for the harness map.
|
||
- **CLI** — [Driver.TwinCAT.Cli.md](../Driver.TwinCAT.Cli.md) documents the
|
||
standalone read/write/browse/probe CLI for manual checks.
|
||
|
||
## 1-D array support
|
||
|
||
A TwinCAT tag becomes a **1-D OPC UA array node** when its `TagConfig` JSON carries
|
||
`"isArray": true` and `"arrayLength": N` (N ≥ 1). The canonical rule:
|
||
`isArray: true` + `arrayLength >= 1` → array; `isArray: false` (any length) → scalar.
|
||
|
||
**Read mechanism** — the driver performs an **ADS native array symbol read** against the
|
||
declared `SymbolPath`. ADS returns the full array value buffer for a symbol that maps to a
|
||
TwinCAT array type (e.g. `ARRAY [0..9] OF REAL`); the driver reads `N` elements from the
|
||
response.
|
||
|
||
⚠️ **Native notifications do not carry arrays.** The notification path registers the
|
||
declared *scalar* type, so before the declared-type check an array tag subscribed natively
|
||
published only its first element at Good. It is now refused with `BadTypeMismatch` (the PLC
|
||
symbol is an array, not a scalar). Subscribe array tags with `UseNativeNotifications=false`
|
||
(the poll engine uses the array read above) until native array notifications are added.
|
||
|
||
**Unit test coverage** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT.Tests/` covers
|
||
the array symbol read path via the fake ADS client factory. The TwinCAT integration
|
||
fixture is down during normal dev.
|
||
|
||
**Live-verify** — integration-fixture-gated (requires the TwinCAT Docker fixture / AMS router).
|
||
|
||
**Deferrals** — array *writes* (`ADS WriteValueAsync` for an array), multi-dimensional
|
||
arrays, per-element historization. `IRediscoverable` fires and now surfaces a `/hosts` re-browse prompt, but still does not rebuild the address space (#518)
|
||
on PLC re-download (unchanged semantics from scalar nodes).
|
||
|
||
See [Uns.md §Array tags](../Uns.md#array-tags-1-d) for the cross-driver coverage matrix
|
||
and the UI authoring flow.
|
||
|
||
## Controller-discovered struct/UDT/FB member variables
|
||
|
||
When `EnableControllerBrowse` is set, `BrowseSymbolsAsync` walks the device's symbol tree
|
||
recursively and expands **Struct / UDT / Function-Block typed symbols** into their **atomic
|
||
member leaves** as individually addressable OPC UA Variables, surfaced under the `Discovered/`
|
||
sub-folder.
|
||
|
||
### What is discovered
|
||
|
||
- Each symbol of a struct, UDT, or FB type is recursively expanded. The walk follows the ADS
|
||
symbol tree's `SubSymbols` collection.
|
||
- **Full instance paths** are preserved for every leaf (e.g. `MAIN.Motor.Speed`,
|
||
`GVL.Drive1.Status.Running`).
|
||
- The recursion is **depth-capped at 8 levels** to guard against pathological or circular-like
|
||
layouts.
|
||
- **Unsupported leaves** (types the driver cannot map to an OPC UA data type) are silently
|
||
dropped rather than surfaced as error nodes.
|
||
|
||
### Pre-declared Structure-typed tags
|
||
|
||
Pre-declared `Tags` with a `DataType` of `Structure` are **still rejected** — the driver cannot
|
||
read an opaque struct blob without knowing its member layout. For structs that must be
|
||
individually addressed, use `EnableControllerBrowse` to let the driver discover the member
|
||
layout from the controller's symbol table, rather than pre-declaring the container tag.
|
||
|
||
### Member writes
|
||
|
||
Discovered struct/UDT/FB member **writes** are **deferred** in this release. Scalar atomic
|
||
members can be written when pre-declared with `Writable: true`; the controller-browse expansion
|
||
path does not yet wire the write channel.
|
||
|
||
### Live caveat — Flat-mode vs VirtualTree-mode browse
|
||
|
||
The ADS client's `BrowseSymbolsAsync` may return symbols in **Flat mode** (a flat list of all
|
||
instance paths, with no `SubSymbols` populated) on some TC3 runtime configurations, in which
|
||
case the recursive struct expansion produces no sub-symbols and the walk yields only top-level
|
||
symbols. If a live TC3 browse does not populate `SubSymbols` on struct-typed symbols, the
|
||
alternative is **VirtualTree mode** (which returns a hierarchical symbol tree with `SubSymbols`
|
||
populated). VirtualTree-mode browse is an unverified follow-up; if Flat-mode struct expansion
|
||
produces empty `Discovered/` sub-folders for struct symbols, switch to VirtualTree mode via the
|
||
driver configuration.
|
||
|
||
## Further reading
|
||
|
||
- [`docs/v2/driver-specs.md §6`](../v2/driver-specs.md) — full per-field spec and
|
||
DriverConfig JSON shape
|
||
- [Driver.TwinCAT.Cli.md](../Driver.TwinCAT.Cli.md) — standalone TwinCAT driver CLI
|
||
- [TwinCAT-Test-Fixture.md](TwinCAT-Test-Fixture.md) — test-harness map
|