Live gate A1 (docker-dev, opc-plc restart / SIGINT / kill): the fast path never fired — a real process stop delivers no session status; the keep-alives report BadSecureChannelClosed (0x80860000) once, then BadConnectionClosed (0x80AE0000) interleaved with BadNoCommunication for the whole outage. Reproduced in-process with TcpStallProxy.HardClose (reset every connection, refuse new ones; server and session alive behind it): the identical sequence, and the SDK 1.5.378 session never opens a new connection on its own (48 s with the proxy accepting again, zero attempts) — a closed channel cannot recover in place. The driver now treats BadSecureChannelClosed/BadConnectionClosed as definitive on the SECOND closed-channel keep-alive failure in one outage (a good keep-alive resets the count), raising ConnectionLost ~1 keep-alive after the drop. BadNoCommunication / BadRequestTimeout / BadNotConnected (stall/pause) stay with the watchdog; the stall test still sees no ConnectionLost. New wire test (hard close + reopen ⇒ raised once, SDK never reconnects, reinit brings the identical value back Good) and unit tests (sustained raises once; a single blip that recovers does not) — all red on the previous code. Docs updated.
345 lines
27 KiB
Markdown
345 lines
27 KiB
Markdown
# OPC UA Client (Gateway) Driver
|
||
|
||
Getting-started guide for the OPC UA Client driver. This is the short path — for
|
||
the full per-field spec read [`docs/v2/driver-specs.md §8`](../v2/driver-specs.md),
|
||
and for the test-harness map read [OpcUaClient-Test-Fixture.md](OpcUaClient-Test-Fixture.md).
|
||
|
||
## What it talks to
|
||
|
||
A **remote OPC UA server**. This driver runs the *opposite* direction from the
|
||
usual "server exposes PLC data" flow: it acts as an OPC UA **client**, opens a
|
||
`Session` against an upstream server, and re-exposes that server's address space
|
||
through the local OtOpcUa server. Browse, read, write, subscribe, alarm, and
|
||
history calls are passed through to the upstream endpoint.
|
||
|
||
It is built on the OPC Foundation UA .NET Standard reference SDK and runs
|
||
in-process in the OtOpcUa server's .NET 10 AnyCPU host — pure managed, no
|
||
out-of-process isolation.
|
||
|
||
> There is **no standalone driver CLI** for the OPC UA Client driver. To exercise
|
||
> a remote OPC UA endpoint by hand, point the general-purpose
|
||
> [Client CLI](../Client.CLI.md) at it directly.
|
||
|
||
## Project split
|
||
|
||
| Project | Target | Role |
|
||
|---------|--------|------|
|
||
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient/` | net10.0 | In-process driver — session lifetime, read / write / subscribe / alarm / history passthrough |
|
||
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Browser/` | net10.0 | `IDriverBrowser` — live address-picker browse used by the AdminUI |
|
||
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Contracts/` | net10.0 | Config records + enums bound from `DriverConfig` JSON |
|
||
|
||
## Minimum deployment
|
||
|
||
```jsonc
|
||
"Drivers": {
|
||
"upstream-1": {
|
||
"Type": "OpcUaClient",
|
||
"Config": {
|
||
"EndpointUrl": "opc.tcp://plc.internal:4840",
|
||
"SecurityPolicy": "None",
|
||
"SecurityMode": "None",
|
||
"AuthType": "Anonymous"
|
||
}
|
||
}
|
||
}
|
||
```
|
||
|
||
`EndpointUrls` (a list) takes precedence over the single-URL `EndpointUrl` and
|
||
provides ordered **failover** — the driver tries each candidate in turn at every
|
||
`InitializeAsync` (including the comms-loss watchdog's re-initialise), and the first to connect wins (e.g. a hot-standby pair on
|
||
4840 / 4841). See
|
||
`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Contracts/OpcUaClientDriverOptions.cs`
|
||
for every field (security policy/mode, auth type, session timeout, keep-alive,
|
||
browse root, node/depth caps). `ReconnectPeriod` was **deleted** (#676 — unused since #670 removed the SDK reconnect
|
||
handler, and the AdminUI no longer shows it); stored configs that still carry `reconnectPeriod` keep parsing in the
|
||
factory, the Test-Connect probe and the browse picker (unknown keys are skipped), and the form drops it on the next save.
|
||
|
||
### Endpoint address: the configured host and port win (#676)
|
||
|
||
GetEndpoints returns each endpoint with the URL the **server** believes it lives at. Behind NAT, a port map, a
|
||
container port publish or a proxy that address is unreachable from the client — or reachable but bypassing the proxy.
|
||
The driver therefore rewrites the selected endpoint's **host and port** to the configured URL's whenever the schemes
|
||
match, keeping the advertised path (the SDK's own `CoreClientUtils.SelectEndpoint` rule, which the driver's
|
||
policy-aware endpoint selection used to bypass). A configured URL with **no port** keeps the advertised port (copying
|
||
the port-less `-1` would have sent the session to 4840). A different scheme is left alone; an unparseable advertised
|
||
URL falls back to the configured one. `OpcUaClientDriver.RewriteEndpointUrl`.
|
||
|
||
### Session lifetime
|
||
|
||
A single `Session` per driver instance; subscriptions multiplex onto it. Stored NodeIds embed the server-stable namespace **URI** (not the
|
||
session-relative `ns=N` index) so a remote namespace-table reorder across a
|
||
restart doesn't silently re-point references at the wrong namespace.
|
||
|
||
### Upstream outage and recovery (Gitea #670)
|
||
|
||
The session keep-alive (`KeepAliveInterval`, default 5 s) is the liveness signal:
|
||
|
||
- **Good keep-alive / any data or event notification** advances `DriverHealth.LastSuccessfulRead` — a
|
||
subscription-only driver never calls `ReadAsync`, so without this its read stamp froze at connect time.
|
||
- **Bad keep-alive** ⇒ health `Degraded` (`LastError = "keep-alive: <status>"`, read stamp preserved), host status
|
||
`Stopped`, and — **once per outage**, not per keep-alive — every subscribed ref is published `BadNoCommunication`
|
||
with its last value retained and **source + server timestamp = the detection time** (live-gate F1: stamped with the
|
||
last Good's source time it collided with that row's `(TagId, SourceTimeUtc)` history key and was never stored), plus a quality-only `BadNoCommunication` annotation (#626 pattern, no alarm-state
|
||
change, no `/alerts` row) on every subscribed alarm condition.
|
||
- **The session survives** (a network blip; the keep-alive turns Good again) ⇒ recovered in place: health `Healthy`,
|
||
the refs still Bad are re-read once and published Good (a server whose subscription survived does not resend an
|
||
unchanged value, and a `(value, status)` dedup downstream lets the identical value through), alarm quality goes
|
||
back Good and a `ConditionRefresh` re-reports anything missed. A notification that lands first wins over the read.
|
||
For a bounded **replay window** after such a recovery — max(30 s, 2 x the longest subscription keep-alive window) —
|
||
each ref is guarded by a high-water mark — its last Good upstream source time, raised by the recovery read and
|
||
advanced by every notification accepted in the window — and a notification whose source time is at or BELOW it
|
||
(equal included: OPC UA moves the source timestamp on every value or status change, so an equal one is a replay)
|
||
is dropped: the SDK was seen delivering a missed one 4–6 s late, which regressed the node (live-gate F2). The
|
||
guard holds for the WHOLE window — fresh notifications arrive ~1 s after recovery, before the late replay, so a
|
||
ref is never disarmed early (the F2 re-gate failed on exactly that). A notification with no source time passes
|
||
without moving the mark. Outside that window every notification is
|
||
accepted whatever its timestamp, so an upstream clock that steps backwards (NTP, a PLC clock reset) never
|
||
freezes a node. The outage Bad never moves the comparison; a re-initialise resets it.
|
||
⚠️ **By design, inside the window a notification whose source time EQUALS the last accepted one is dropped** — so a
|
||
status-only change that keeps the old source timestamp (not what OPC UA servers are supposed to do) is lost during
|
||
the window only (the trailing re-read below repairs it). When the window closes — or a second recovery re-arms it —
|
||
the driver logs ONE line, `post-recovery replay window closed — dropped N late notifications across M refs after
|
||
recovery`, at **Information when N > 0** and Debug otherwise, because the per-drop line is Debug and the
|
||
`stale_notification_dropped` counter is OTel-only, which made the guard unobservable on the docker-dev rig (#676).
|
||
A re-arm starts the count afresh.
|
||
- **Trailing re-read after an in-place recovery (#676).** Found by the TCP-stall wire test: a change the server
|
||
published just after the stall ended rode a Publish response that had been in flight across the stall; the SDK
|
||
timed that request out (`BadTimeout`), discarded the response and never republished the message (the following
|
||
keep-alives moved the sequence number past it), so the node stayed **Good on the pre-change value indefinitely**.
|
||
`Timeout + KeepAliveInterval` after the recovery — when every request in flight across the stall has completed or
|
||
timed out — every subscribed ref is read once more and published when its **(value, status) differs** from the last
|
||
value delivered for that ref **and is not older** than it. Any status counts: a Good→Bad/Uncertain change lost in the
|
||
pipeline is as stale as a lost value. "Older" compares source timestamps only when both carry one; a read with no
|
||
source timestamp (a server that does not send them) is the server's current state and counts as newer. An **equal**
|
||
source timestamp with different content IS published — it is the server's current state, not a replay, and it repairs
|
||
the equal-timestamp status-only change the replay guard drops by design. An identical (value, status) is never
|
||
republished. A ref that received ANY delivery while the read was in flight is skipped (a per-ref delivery counter is
|
||
captured before the read is issued): without source timestamps the read's sample cannot be ordered against that
|
||
notification, and publishing it would regress the node. An Information line names how many refs it had to repair. The trailing read and the replay-guard disarm
|
||
timer run on the driver clock and are cancelled when the session is released (re-initialise / shutdown / dispose).
|
||
- **No older value is ever delivered after a newer one.** The paths that publish upstream data — live notifications,
|
||
the recovery read, the trailing read and the comms-loss Bad fan — make their "may I publish this?" decision and the
|
||
publish inside one driver-wide critical section. A single lock rather than one per ref: it also serialises delivery
|
||
across subscriptions (the SDK dispatches each subscription's messages on its own worker), which is cheap because each
|
||
section is a dictionary update plus a subscriber `Tell` and nothing awaits under it. Subscribers run inside it — the
|
||
host's handler only `Tell`s an actor — so a subscriber must never block on, or call back into, the driver.
|
||
- **The session does not come back** (an upstream restart: the server forgot the session) ⇒ the driver stays
|
||
`Degraded` with its read stamp frozen, which is the #527 comms-loss watchdog's trip condition; `DriverInstanceActor`
|
||
runs `ShutdownAsync` + `InitializeAsync` (retried every 10 s while the server is down) and re-subscribes data +
|
||
alarms; the new subscription's initial values come back Good. Alarm last-told state survives the re-initialise
|
||
(#619), so the post-subscribe `ConditionRefresh` raises no un-ack flicker; the host's reconnect annotation restores
|
||
condition quality.
|
||
- **Fast recovery for a DEFINITIVELY lost session (#676).** The driver implements `IDriverConnectionLossSource` and
|
||
raises `ConnectionLost` — **once per session**, re-armed by a re-initialise — when the loss is certain, so the host
|
||
re-initialises at once instead of after the watchdog's 90 s. Definitive means: a keep-alive status of
|
||
`BadSessionIdInvalid` / `BadSessionClosed` / `BadSessionNotActivated` (the server forgot, closed or never activated
|
||
the session) or `BadServerHalted`, or a subscription the **server** reported gone (below). `BadServerHalted` is on the list
|
||
because it was **measured**: on the restart wire test a gracefully stopped server reports `BadServerHalted` (and the
|
||
keep-alives alternate it with `BadNoCommunication`), and the SDK never re-opens a channel the server halted — 15 s
|
||
after the server was back, the same session still failed every request with `BadServerHalted`; `BadSessionIdInvalid`
|
||
never arrived.
|
||
**A CLOSED connection is definitive too, once sustained (live gate A1).** Against a real opc-plc on docker-dev, none of
|
||
`docker restart`, a graceful SIGINT stop (opc-plc itself logged `BadServerHalted`) or `docker kill` delivered a
|
||
session status to the client: the keep-alives reported `BadSecureChannelClosed` (0x80860000) once, then
|
||
`BadConnectionClosed` (0x80AE0000) interleaved with `BadNoCommunication` for the whole outage, so the first cut of the
|
||
fast path never fired and recovery took 91–127 s. Reproduced in-process with `TcpStallProxy.HardClose` (every
|
||
connection reset, new ones refused, the server AND its session still alive behind it): the same sequence, and the SDK
|
||
1.5.378 session **never opens a new connection by itself** — 48 s after the proxy accepted connections again, not one
|
||
attempt. So a closed channel can never recover in place; on the **second** closed-channel keep-alive failure in one
|
||
outage (`IsClosedChannel`; a good keep-alive resets the count, so a single transient does not count) the driver raises
|
||
`ConnectionLost` — about one keep-alive interval after the connection dropped. Everything else —
|
||
`BadNoCommunication`, `BadNotConnected`, `BadRequestTimeout`/`BadTimeout` (what a stalled or paused link produces) —
|
||
is **ambiguous** (the link may resume and keep its session, see the stall test) and stays with the watchdog.
|
||
Consequence: a restarted, stopped or killed upstream is re-initialised within roughly one keep-alive plus one
|
||
reconnect interval instead of ~100 s; a pause (`docker pause`, a congested link) still recovers in place. ⚠️ **Known gap:** the host acts on the signal only while the driver is
|
||
`Connected`, and the driver raises it once per session — so a definitive loss raised while the host is not
|
||
Connected (e.g. `BadServerHalted` on the fresh session before the host has processed the successful initialise) is
|
||
swallowed and that session falls back to the watchdog. Re-raising on later keep-alives would close it but was left out
|
||
to keep the once-per-session contract simple; the cost is the pre-#676 recovery time, in a narrow window.
|
||
- **The subscription dies but the session lives** (an outage longer than the subscription lifetime —
|
||
`LifetimeCount` x publishing interval, often well under the session timeout — or a server that drops it) ⇒ keep-alives
|
||
stay Good, so they cannot be the signal. A `PublishError` of `BadNoSubscription` (while subscriptions are tracked) or
|
||
`BadSubscriptionIdInvalid` naming a tracked subscription, or a tracked subscription whose SDK `PublishingStopped`
|
||
persists for one more subscription keep-alive window + 5 s across good keep-alives, declares it lost: `Degraded`
|
||
(`"subscription lost: …"`), the outage published once, and — sticky until the session is released — **nothing**
|
||
advances `LastSuccessfulRead` any more (not good keep-alives, not a sibling subscription's notifications), so the
|
||
watchdog's re-initialise recreates it. Both detectors are wire-tested independently. A subscription the **server**
|
||
reported gone (`BadNoSubscription` / `BadSubscriptionIdInvalid`) never comes back on its session, so that also raises
|
||
`ConnectionLost` (#676) and the re-initialise happens at once; the `PublishingStopped` **heuristic** is an inference
|
||
from silence and keeps going through the watchdog.
|
||
- An in-place recovery is bound to the session whose keep-alive recovered: one overtaken by a re-initialise neither
|
||
publishes, nor degrades, nor re-arms the outage latch of the new session.
|
||
|
||
There is **no in-driver reconnect** any more. The SDK's `SessionReconnectHandler` (removed) retried forever in SDK
|
||
1.5.378 (its "exhausted" path was unreachable), recreated sessions by cloning subscriptions the driver never
|
||
re-tracked, and kept health `Healthy` throughout — so on docker-dev a stopped opc-plc left nodes Good on their last
|
||
value indefinitely and they never recovered. A teardown against a lost session skips the wire deletes and `CloseSession`
|
||
(bounded to 5 s otherwise). SDK warnings (keep-alive / publish / channel errors) now reach the driver's own logger,
|
||
rate-limited to 20 per minute with a suppressed-count note; the per-driver SDK logger factory is disposed with the
|
||
driver.
|
||
|
||
### Namespace assignment (retired, Gitea #648)
|
||
|
||
Earlier versions required a per-instance `TargetNamespaceKind` (`Equipment` +
|
||
a mandatory `UnsMappingTable`, or `SystemPlatform` + an empty table). Both
|
||
options are **removed**: nothing ever read the mapping table beyond the startup
|
||
check, and in v3 the raw-to-UNS projection is explicit (`UnsTagReference`), so
|
||
the choice carried no behaviour — it only made a config without the key fail
|
||
`Initialize`. Remote nodes are authored as `/raw` tags bound by their upstream
|
||
`nodeId`; there is no namespace field on the driver, the AdminUI form or the
|
||
seed.
|
||
|
||
Stored `DriverConfig` JSON that still carries `targetNamespaceKind` or
|
||
`unsMappingTable` keeps working: the keys are unknown and ignored on parse and
|
||
initialise (the AdminUI form drops them on the next save). Pinned by
|
||
`OpcUaClientReinitConfigAdoptionTests.Legacy_namespace_keys_are_ignored_by_parse_and_initialise`.
|
||
|
||
## Capability surface
|
||
|
||
`OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWritable, ISubscribable, IHostConnectivityProbe, IAlarmSource, IDriverConnectionLossSource`
|
||
(`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient/OpcUaClientDriver.cs:31`).
|
||
|
||
| Capability | Path | Notes |
|
||
|------------|------|-------|
|
||
| `ITagDiscovery` | `DiscoverAsync` (recursive browse) | Mirrors the upstream tree from `BrowseRoot` (default `ObjectsFolder` i=85), bounded by `MaxDiscoveredNodes` / `MaxBrowseDepth` |
|
||
| `IReadable` | `ReadAsync` → `Session.ReadAsync` | Upstream `StatusCode`s pass through verbatim (cascading-quality rule) |
|
||
| `IWritable` | `WriteAsync` → `Session.WriteAsync` | Passthrough write |
|
||
| `ISubscribable` | native OPC UA subscriptions / monitored items | The remote server pushes data changes |
|
||
| `IHostConnectivityProbe` | session keep-alive | Host key is the endpoint URL actually connected to after the failover sweep |
|
||
| `IAlarmSource` | `SubscribeAlarmsAsync` (EventFilter) + `AcknowledgeAsync` | Subscribes to upstream alarm/condition events and forwards acks |
|
||
|
||
> **Native alarms (#619).** An alarm raw tag is `TagConfig` `{ "nodeId": "<upstream SourceNode>", "alarm": {...} }`.
|
||
> The host subscribes with RawPaths and routes on (driver, RawPath), so the driver matches each
|
||
> event's `ConditionId` (then its `SourceNode`) against the tag's authored `nodeId` and reports the **RawPath** as
|
||
> `ConditionId`. Author `nodeId` as the upstream **condition** node for a 1:1 mapping (required when one source carries
|
||
> several conditions, e.g. Hi + HiHi); authoring the **source** node folds every condition of that source into one
|
||
> tag. `Acknowledge` is called on the condition node of the last event seen for the RawPath **with that event's
|
||
> EventId** (Part 9 §5.7.3). The event's `ActiveState/Id` + `AckedState/Id` are selected and turned into the
|
||
> `Raise`/`Acknowledge`/`Clear`/`Retrigger` kinds the host projector consumes (without a kind no upstream alarm could ever
|
||
> show active); the kinds are emitted from the state **last told to the host** per RawPath, so an identical re-delivery
|
||
> emits nothing (no re-raise, which would un-ack). An inactive → active+acked move is ONE `ActiveAcknowledged` (#656; it
|
||
> used to be `Raise` + `Acknowledge`, a client-visible unacked intermediate); a move into inactive+unacked is ONE
|
||
> `InactiveUnacknowledged` (#657; it used to be `Raise`/`Retrigger` + `Clear`, an Active flicker). The first event per
|
||
> condition after a start or deploy respawn is flagged `IsRestatement` and states the upstream condition so it lands
|
||
> from whatever the host retained: an inactive+acked one goes out as `Clear` + `Acknowledge` (#657; it used to be an
|
||
> `Unspecified` the host wrote as "Activated", and a retained-Active host condition stayed Active). So the host writes no
|
||
> duplicate row when its condition already shows that state (see `docs/AlarmTracking.md`). Condition **branch** events (non-null `BranchId`) are ignored.
|
||
> **`ConditionRefresh`** is called after the event item is created, after a keep-alive outage the session survived, and on a
|
||
> `RefreshRequired` event, so a condition already active upstream is reported at subscribe; `RefreshStart`/`RefreshEnd`
|
||
> markers are dropped. A server without it (`BadNotSupported`/`BadMethodInvalid`/…) is logged once and tolerated.
|
||
> Last-told state survives a re-initialise (the host re-subscribes the same set over nodes it did not rebuild) and is
|
||
> forgotten when the subscribed set changes (the host rebuilt, recreating the nodes inactive). Index keys are server-stable (`nsu=`), so a namespace reorder across a re-initialise keeps
|
||
> matching. docker-dev seeds an opc-plc driver (`MAIN-opcua`); the alarm tag is
|
||
> created only when `@OpcPlcAlarmSourceNodeId` is set in `docker-dev/seed/seed-clusters.sql`.
|
||
|
||
> This driver does **not** implement `IRediscoverable` — there is no
|
||
> push-driven rediscovery signal from a remote OPC UA server in this driver.
|
||
|
||
### History: not supported (Gitea #655)
|
||
|
||
This driver does **not** proxy the upstream server's HistoryRead. The server serves
|
||
HistoryRead only through the server-wide `IHistorianDataSource` (see `docs/Historian.md`);
|
||
drivers carry no history capability, and the former `IHistoryProvider` passthrough
|
||
(Raw / Processed / AtTime / Events) was never dispatched to and has been deleted.
|
||
`isHistorized` on an OpcUaClient tag means OtOpcUa records the value into the historian
|
||
from now on (numeric only), not that upstream history is forwarded. A tag without
|
||
`isHistorized` has no HistoryRead access bit and answers `BadHistoryOperationUnsupported`.
|
||
If upstream-history proxying is wanted later, it needs a new intent key, a dispatch path
|
||
through `DriverHostActor`, and a continuation-point rework — see #655.
|
||
|
||
### Certificate trust
|
||
|
||
`AutoAcceptCertificates` accepts any self-signed / untrusted server certificate.
|
||
It is **dev-only** — leave it `false` in production so a MITM against the
|
||
opc.tcp channel fails closed. The SDK rejects a **revoked** certificate
|
||
(`BadCertificateRevoked` / `BadCertificateIssuerRevoked`) before the auto-accept handler runs, and the handler
|
||
also refuses them explicitly — defence in depth (#277), not a behaviour change.
|
||
|
||
`CertificateValidation` (defaults change nothing):
|
||
|
||
| Key | Default | Meaning |
|
||
|---|---|---|
|
||
| `rejectUnknownRevocationStatus` | `false` | Reject a server certificate whose revocation status cannot be determined (no CRL for its issuer, or a stale one). Leave `false` for brownfield sites without CRL infrastructure. **Only effective with `autoAcceptCertificates` off** — the auto-accept handler accepts every suppressible error, including revocation-unknown. |
|
||
| `issuerStorePath` | `null` (= `%LocalAppData%/OtOpcUa/pki/issuers`) | Directory used as the trusted-issuer store. The SDK reads issuer CRLs (`*.crl`) from its `crl/` sub-folder, so this is how an operator points the driver at a managed CRL set. |
|
||
|
||
### Subscription tuning (#273)
|
||
|
||
The per-subscription parameters that used to be hardcoded are driver options; the defaults are the old values.
|
||
|
||
| Key | Default | Notes |
|
||
|---|---|---|
|
||
| `subscriptionPublishingInterval` | `null` | A .NET `TimeSpan` string (`"00:00:02"`), not a number. `null` = the interval the runtime requests per subscribe (floored at 50 ms). When set it overrides that value (floor still applies); monitored-item sampling follows it. |
|
||
| `subscriptionKeepAliveCount` | `10` | `>= 1`. |
|
||
| `subscriptionLifetimeCount` | `1000` | Must be `>= 3 x` keep-alive count (Part 4 §5.13.2). |
|
||
| `subscriptionMaxNotificationsPerPublish` | `0` | `0` = server decides. |
|
||
| `subscriptionPriority` | `0` | `0`-`255`. |
|
||
|
||
Out-of-range values (and a non-absolute `discoveryUrl`) are rejected when the options are loaded — driver creation / `InitializeAsync` fails once with a clear message rather than the driver faulting and retrying forever. The alarm subscription uses the same counts.
|
||
*Per-tag* tuning (deadband / sampling interval / queue size, #274) is not implemented — it needs an
|
||
`ISubscribable` signature change on Core.
|
||
|
||
### Server OperationLimits (#275)
|
||
|
||
Nothing driver-side: the SDK session already honours the remote server's
|
||
`ServerCapabilities/OperationLimits`. `Opc.Ua.Client.Session` derives from `Opc.Ua.SessionClientBatched`,
|
||
fetches the limits on open (`FetchOperationLimitsAsync`) and splits Read / Write / CreateMonitoredItems / Browse /
|
||
HistoryRead requests that exceed them (a limit of `0` = unlimited). The driver issues one logical call per
|
||
operation and a unit test pins the `Session : SessionClientBatched` relationship so an SDK change that dropped
|
||
it is caught. (A driver-side splitter was tried and removed: it duplicated the SDK and, on a stalled link, held
|
||
the driver gate for chunks x timeout.)
|
||
|
||
### Discovery URL (#278)
|
||
|
||
`discoveryUrl` (default `null`, e.g. `opc.tcp://lds:4840`): at `InitializeAsync` the driver runs `FindServers` on it
|
||
and `GetEndpoints` on every returned server, keeping the endpoints matching `securityPolicy` + `securityMode`.
|
||
Discovered URLs are tried **after** `endpointUrls`/`endpointUrl` (case-insensitive de-dup) — discovery can add
|
||
fallbacks but never outranks or replaces the configured server. Because an LDS commonly registers several servers
|
||
(identical line PLCs, a gateway plus a historian) and the first to accept a connection would be bound silently:
|
||
|
||
- `discoveryServerUri` set: only endpoints of the server with that ApplicationUri are used.
|
||
- unset and exactly one distinct server discovered: that server is used.
|
||
- unset and more than one: the connect attempt **fails** with an error naming the discovered ApplicationUris and
|
||
telling the operator to set `discoveryServerUri`.
|
||
|
||
A discovery *network* failure (LDS down) is logged and non-fatal — the static list is used (note it is retried on
|
||
every `InitializeAsync`, including comms-loss reconnects). The discovery channel itself is always unsecured (spec).
|
||
|
||
### Diagnostics counters (#276)
|
||
|
||
Session/publish events are published on the shared OTel meter as the counter
|
||
`otopcua.driver.opcuaclient.events`, tagged `driver_instance` (the driver instance id) and `event` =
|
||
`publish_response`, `notification` (items), `data_change`, `bad_status_value`, `publish_error`,
|
||
`keepalive_miss`, `keepalive_recovered` (a bad keep-alive followed by a good one on the same session),
|
||
`stale_notification_dropped` (a late replay dropped inside the post-recovery window, see above). A climbing
|
||
`keepalive_miss` / `keepalive_recovered` rate is the signature of a flapping upstream (`reconnect_*` were removed with
|
||
the reconnect handler, #670). They are not part of `DriverHealth` or the
|
||
`/hosts` panel.
|
||
|
||
## Testing
|
||
|
||
- **Unit tests** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Tests/`
|
||
cover the session lifecycle, namespace remapping, alarm/history passthrough,
|
||
and config binding against a faked SDK session.
|
||
- **Integration fixture** — exercises the driver against a reference OPC UA
|
||
server (opc-plc) on the shared docker host; see
|
||
[OpcUaClient-Test-Fixture.md](OpcUaClient-Test-Fixture.md) for the coverage map.
|
||
- **Wire tests against the in-process server** — `tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests/`
|
||
`OpcUaClientDriver*WireTests` (no Docker). `OpcUaClientDriverStallWireTests` (#676) covers the in-place blip that
|
||
used to be live-gate-only: the driver connects through `TcpStallProxy`, an in-test TCP forwarder whose pause holds
|
||
every byte without closing anything (which only works because of the endpoint rewrite above); it asserts one Bad,
|
||
a frozen read stamp, recovery on the SAME session, the identical value republished Good, a change published right
|
||
after recovery still arriving, and no source-time regression once the SDK's late backlog flush has arrived. Its
|
||
second test uses `HardClose` (reset every connection, refuse new ones) — the shape of a real process stop — and
|
||
asserts the live-gate status sequence, that the SDK never reconnects on its own once the proxy accepts again,
|
||
`ConnectionLost` exactly once, and the re-initialise bringing the identical value back Good.
|
||
`OpcUaClientDriverReconnectWireTests` covers the server restart (incl. the `BadServerHalted` → `ConnectionLost` signal)
|
||
and the subscription-lost case.
|
||
|
||
## Further reading
|
||
|
||
- [`docs/v2/driver-specs.md §8`](../v2/driver-specs.md) — full per-field spec,
|
||
namespace-assignment rules, and cascading-quality detail
|
||
- [OpcUaClient-Test-Fixture.md](OpcUaClient-Test-Fixture.md) — test-harness map
|
||
- [Client.CLI.md](../Client.CLI.md) — general-purpose OPC UA client CLI for
|
||
ad-hoc browsing of any endpoint
|