docs(717): Mode=Unset re-check after c569f806 (no change); a leaving node reports 0
T13b: the isolated otopcua-t13b pair with OpcUa:Redundancy:Mode absent, on origin/master f826af8e
(it contains c569f806) and A/B on c569f806^ (687256d6). Every check passes on both builds:
- levels 250/240;
- Good data on both nodes;
- writes, Acknowledge, AddComment and alarm delivery on the Secondary;
- graceful stop: the survivor reaches 250 259 ms after Leaving (pre-fix 270 ms);
- crash: 250 at +43.6 s (pre-fix +42.8 s), with no demotion at auto-down;
- rejoin at 240 with no failback.
The role-decision changes are gated on IsWarm and do not run under Unset.

Plan L5, the design's section 4.3 and the Warm table in Redundancy.md now say a Leaving/Exiting node
reports ServiceLevel 0, not 90 (ComputeWarm returns 0 for any member that is not Up/Joining; T13 note A).

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
2026-11-13 06:44:46 -05:00

374 lines
26 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Warm non-transparent redundancy (Gitea #717): implementation plan
Status: **APPROVED by the owner 2026-11-13** (#717), together with `2026-11-11-warm-redundancy-717-design.md`
(referred to below as "the spec", with § references). The spec's §9 records the owner's answers: writes and Part 9
methods are refused `BadInvalidState` under Warm, promote-while-unreachable is on by default, the standby status is
`BadOutOfService`, there is no ConfigDb migration, and the bands are as drafted.
Every task ships **dark**: `OpcUa:Redundancy:Mode` defaults to `Unset`, so merging any task changes no deployed
behaviour.
Conventions:
- **Wire tests** use a real OPC Foundation client session against a loopback `OtOpcUaSdkServer`, in
`tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests` (the home of `DualEndpointTests`,
`ConditionRefreshDeferralWireTests` and `FolderConditionRefreshWireTests`).
- **Actor tests** go in `tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests` and
`tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests`.
- Every gate gets an **allow** leg as well as a deny leg (the vacuous-test rule), and a mutation check: revert the
production line and confirm the test fails.
## T0: SDK 2.0.1 re-proof spikes (throwaway, separately approved)
The 1.5.378.106 spikes do not carry over (spec §10). Write throwaway loopback fixtures against **2.0.1**, outside
`src/`. No product edits. Each fixture is rerun independently and its evidence is recorded in
`docs/plans/evidence/2026-11-xx-717-sdk2/`.
- **a. Metadata graph.** Build it via `CreateMainNodeManagerFactory` + `AddBehaviourToPredefinedNodeAsync`. Check
Read/Browse/Translate of `i=2296` (HasTypeDefinition 2039), `i=3709`, and `i=11314` for both Warm and None. The
passive `i=11314` visit must resolve to the constructed instance.
- **b. Read projection coverage.** Cover Read, the initial sample on create, the change fan-out after
`ClearChangeMasks`, ResendData, queue size 1 vs. N, an AggregateFilter item, and Sampling → Reporting. Decide
between `OnSimpleReadValue` and a `ReadValueAttribute` override, and record which async callback paths 2.0.1
takes.
- **c. Provenance.** Stamp items through the 2.0.1 `MonitoredItemFactory` / `MonitoredItemCreateDecision`. Exercise
ModifyMonitoredItems handle change, delete/reuse, TransferSubscriptions (`IMonitoredItemTransferCoordinator`),
and a restore.
- **d. Publish/Republish.** Override `PublishAsync`/`RepublishAsync` with the 2.0.1 signatures (`RequestLifetime`).
Cover the first-delivery choice, first delivery through Republish, an ack followed by `BadMessageNotAvailable`,
and a cancelled or failed response.
- **e. Events.** Exercise the stamp/deliver split under the #855 per-item folder path and the #854 Server-object
cut. Run the promotion refresh on all three item kinds, and a client ConditionRefresh/2 while Standby.
**Exit:** a short results note per fixture, and an owner go/no-go. A "no" on (c) or (d) re-opens D4's mechanism.
D4 itself stays an owner decision.
**T0 run 2026-11-13: (a) and (b) pass; (c) and (d) are no-go as written.** SDK 2.0.1 hands every Publish and Republish
a fresh clone of the cached message and pools the notification payloads, so provenance and the first-delivery choice
cannot be keyed by object. An alternative, keyed by `(SubscriptionId, SequenceNumber)` with a clone-surviving
provenance token, passed the same spike. **The owner adopted it on 2026-11-13**; spec §4.6 and T2/T7 below describe
it. Evidence: `docs/plans/evidence/2026-11-13-717-sdk2/RESULTS.md`.
## T1: Configuration, validation, effective self URI
**Files:**
- `src/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer/OpcUaApplicationHost.cs`: options at `:29-121`. Add
`OpcUaRedundancyOptions Redundancy` (`Mode`; `PromoteWhilePrimaryUnreachable`, default `true`, owner answer Q2).
- `src/Server/ZB.MOM.WW.OtOpcUa.Host/Configuration/OpcUaApplicationHostOptionsValidator.cs`.
- A post-load check in `StartAsync` (`:218-250`) against the effective `ApplicationConfiguration.ApplicationUri`.
**Rules (spec §3):**
- `Hot` and unknown values fail host start.
- `Warm` requires at least one peer, all URIs distinct, self not listed as a peer, and the `driver` role.
- `None` requires no peers.
**Tests:**
- A validator matrix.
- An XML `ApplicationConfigPath` whose URI differs from the options value, proving the effective URI is used.
- A boot-banner log assertion.
## T2: Standard redundancy metadata graph
**Files:**
- `src/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer/OtOpcUaSdkServer.cs`: in the existing `OnNodeManagerStartedAsync`
override, install the T0a graph per mode through `IPredefinedNodeSubtypeReplacer.ReplacePredefinedInstanceSubtypeAsync`
(no `CreateMainNodeManagerFactory` override is needed on 2.0.1).
- Under `Warm`, the initial `Server.ServiceLevel` is set to **1** in the same pass (spec §4.3). `Unset` must not
touch the graph. Under `None` the SDK's orphan `i=11314` (T0a finding) is deleted so it is absent by NodeId too.
**Tests (wire):**
- Per mode, check the `i=3709` value, the `i=2296` type definition, the presence or absence of `i=11314`, its
value order `[effectiveSelf, peers…]`, and that it is read-only (a Write returns `BadNotWritable`).
- `ServerArray` (`i=2254`) is unchanged; extend `DualEndpointTests`.
- A Warm server's ServiceLevel reads 1 before the first publish.
- Security profiles and startup are unaffected under `Unset` (golden read of today's values).
## T3: Ordered redundancy snapshots (spec §4.2)
**Files:**
- `src/Core/ZB.MOM.WW.OtOpcUa.Commons/Messages/Redundancy/RedundancyStateChanged.cs` (`:9-11`): add an optional
`SnapshotRevision? Revision` (additive).
- `RedundancyStateActor.cs`:
- stamp the revision in `PublishIfDirty` (`:105-113`);
- set `IncarnationTick` in `PreStart`;
- read the host's `UpNumber` from `Cluster.SelfMember`.
- Subscribers: accept only a newer revision in `OpcUaPublishActor.HandleRedundancyStateChanged` (`:1494-1498`) and
`DriverHostActor.OnRedundancyStateChanged` (`:2555`).
- An unrevisioned snapshot keeps today's handling for the existing gates.
**Tests:**
- Ordering unit tests: an older singleton incarnation's heartbeat after a newer snapshot is dropped; a same-process
singleton restart advances.
- A **real 2-node cluster** handover test (pattern: `RedundancyPrimaryElectionTests`). It holds back the old
incarnation's last publish through the `_broadcastOverride` seam (`:111`) and asserts the subscriber keeps the
new Primary.
- Serialization round-trip of the extended message, plus a mixed-version decode with the field absent.
- The pinned assumption: a removed node cannot rejoin without a new `ActorSystem`.
## T4: Warm role verdict and ServiceLevel bands (spec §4.1, §4.3)
**Files:**
- New `src/Server/ZB.MOM.WW.OtOpcUa.Runtime/Redundancy/WarmRoleAuthority.cs`: a pure function of membership view,
accepted snapshot, `EndpointListening` and `SelfMember` status.
- `src/Core/ZB.MOM.WW.OtOpcUa.Cluster/Redundancy/ServiceLevelCalculator.cs`: add `ComputeWarm(inputs, isActive)`.
`Compute` itself is unchanged.
- `OpcUaPublishActor.RecomputeServiceLevel` (`:1576-1636`) branches on mode. It subscribes to `MemberUp/Removed`
and to reachability (owner answer Q2) so the verdict re-derives on membership changes, not only on snapshots.
**Tests:**
- A truth table covering every row of §4.3 and the invariant *max(Standby) < min(Active serving)*.
- Membership/snapshot disagreement gives Standby, plus the 20 s Warning.
- Boot with an unknown role gives Standby; a lone node goes Active after its own snapshot.
- `None`/`Unset` produce byte-identical output to today's `ServiceLevelCalculatorTests`.
- DB-less mode (#721 timer) is covered.
## T5: Standby projection seam and transition sequencer (spec §4.7)
**Files:**
- New `src/Core/ZB.MOM.WW.OtOpcUa.Commons/OpcUa/IStandbyProjection.cs`, with a deferred/late-bound adapter that
mirrors `DeferredServiceLevelPublisher` and retains the latest state across binding (the #719 lesson).
- Bound in `src/Server/ZB.MOM.WW.OtOpcUa.Host/OpcUa/OtOpcUaServerHostedService.cs` next to the ServiceLevel binding.
- `OpcUaPublishActor` runs promotion and demotion as one serialized handler, in the §4.7 step order.
**Tests (actor, with a recording fake):**
- The exact step order for both directions.
- A ServiceLevel publish failure halts a promotion before the Active level and retries; a demotion continues.
- A burst of alternating verdicts converges on the last one.
- Binding after the first transition replays the current state.
## T6: Per-tag read projection (spec §4.4)
**Files:**
- `src/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer/EquipmentVariableState.cs`: the hook decided in T0b, reading a
node-manager-wide volatile projection flag. Stored `Value` is never modified.
- `OtOpcUaNodeManager` implements `IStandbyProjection.SetDataProjection`.
- Owner answer Q1: under Warm, the ordinary-tag write handler refuses a write on the Standby with `BadInvalidState`
before it reaches the node-write gateway. `Unset`/`None` keep the #5 optimistic path.
**Tests (wire):**
- Warm Standby: a Write returns `BadInvalidState` and the gateway is never called; on the Active node the same Write
reaches the gateway; under `Unset` a node that is not Primary still takes today's optimistic path.
- Standby Read of a raw tag, a UNS reference, a virtual tag and a Calculation tag returns `BadOutOfService`/null.
- A Standby Read of a condition child, `i=2267` or `i=3709` stays Good.
- A Read with an IndexRange on an array tag is projected; a DataEncoding request is projected.
- Acquisition continues: flip to Active and the latest value is read without any new driver publish.
- ACL on: a denied node is still `BadUserAccessDenied` and the projection never leaks existence.
## T7: Ordinary-tag marker and first-delivery decision record (spec §4.6, D4)
The T0-adopted alternative (owner, 2026-11-13). The 1.5 object-keyed provenance and choice table are not used.
**Files:**
- `OtOpcUaNodeManager`: replace `m_monitoredItemManager` with a `MonitoredNodeMonitoredItemManager` subclass that
re-implements `IMonitoredItemManager.CreateMonitoredItem` and creates a custom sampled item for ordinary-tag
(`EquipmentVariableState`) `Value` items only. Its `Publish` runs base first and then sets
`MonitoredItemNotification.Message` to an `OrdinaryTagMarker(ClientHandle, DataValue)`.
- `OtOpcUaSdkServer.cs`: `PublishAsync`/`RepublishAsync` overrides and a new `FirstDeliveryRecord` keyed by
`(SubscriptionId, SequenceNumber)`, pruned by `AvailableSequenceNumbers` and bounded.
- Wire into `OtOpcUaNodeManager.CreateMonitoredItems` / `OnMonitoredItemCreated` without disturbing ACL filtering
or `_liveItems`.
**Tests (wire):**
- Queued Good samples, a ClientHandle change, then demotion: the first Publish carries `BadOutOfService`, and a
Republish returns the same projected payload.
- Prebuilt sequences (`maxNotificationsPerPublish=1`), then demotion: the next Publish is projected, and Republish
returns the recorded projected choice. A Republish of a prebuilt, never-sent number is `BadMessageNotAvailable`.
- Good delivered while Active, then demotion: Republish returns the original Good; after an ack it is
`BadMessageNotAvailable`.
- A mixed subscription (ordinary tag + `i=2267` + condition-child item): only ordinary-tag items are rewritten.
- The marker is validated: a notification whose marker names another handle or value is not rewritten (unit).
- **SDK-field regression pin:** the helper survives `CoreUtils.Clone` and is not encoded by the binary encoder.
- The record is bounded, and pruned against `AvailableSequenceNumbers`.
- Concurrent Publish and role flip, by a stress loop with a deterministic barrier, not sleeps.
## T8: Promotion and demotion of live data items
**Files:**
- `OtOpcUaNodeManager`: `IStandbyProjection.QueueCurrentToLiveItems(bool projected)` iterates `_liveItems`. It
reuses the QueueValue-with-`ignoreFilters` pattern (`:7303`), **not** detach or `MonitoringMode.Disabled`; the
disabled-mode-drops-queue lesson applies. ACL-suppressed items are skipped.
**Tests (wire):**
- Demotion delivers exactly one `BadOutOfService` per item, then silence while values keep changing internally.
- Promotion delivers the current Good value without a driver publish.
- An ACL-stood-down item receives nothing either way.
- A DeadbandFilter item still receives the promotion value.
## T9: Alarm event suppression and promotion refresh (spec §4.5, D3, D5)
**Files (`OtOpcUaNodeManager`):**
- Split `ReportConditionEvent` (`:1376`) into stamp and deliver; deliver is gated by the projection flag.
- Audit all callers (`:1254`, `:1341`, `:2842`, `:4659`) and `WireMethodTransitionReporting`.
- `IStandbyProjection.RefreshAllEventItems()` runs the existing `ConditionRefresh` (`:6586`) Server-object path and
`RefreshDirectItems` (`:6974`) over every live event item, from `_allEventsItems` and `_eventItems`.
- `ReportToServerObject` (`:6060`) is untouched.
- Owner answer Q4: under Warm, every Part 9 condition method (native or scripted) is refused `BadInvalidState` on
the Standby before it changes condition state.
**Tests (wire, ACL off and on):**
- Warm Standby: Acknowledge and a shelving method on a scripted condition return `BadInvalidState` and route no
command; the Active node accepts them; `Unset` keeps today's scripted-method acceptance.
- A new alarm on the Standby reaches no Server-object, folder or direct item.
- Model-change and audit events are still delivered on the Standby.
- A client ConditionRefresh **and** ConditionRefresh2 on the Standby return Start, retained, End (D5).
- Promotion gives Start, retained, End on all three item kinds, followed by new events.
- An ACL-denied condition is absent from the promotion refresh.
- A condition raised and cleared (Retain=false) while Standby is not replayed.
- An event reported while Active but deferred (#838, via `NotifierStall`) is still delivered after demotion.
- A Standby-stamped EventId is accepted by Acknowledge after promotion.
- The `RingEventQueueFactory` path is untouched (`RingEventMonitoredItemQueueParityTests` stay green).
- Re-run `EventQueueOverflowAclWireTests` and `ConditionMethodEventTests`.
## T10: Deploy-time mode cross-check and observability (spec §3, §7)
**Files:**
- `src/Server/ZB.MOM.WW.OtOpcUa.Runtime/Drivers/DeploymentArtifact.cs`: read this node's cluster
`RedundancyMode` from the `Clusters` array.
- `OpcUaPublishActor` compares it with the local mode at apply.
- `src/Core/ZB.MOM.WW.OtOpcUa.Commons/Observability/OtOpcUaTelemetry.cs`: add the six instruments.
**Tests:**
- A mismatch logs an Error and records the metric.
- Each counter fires on its path. Use a `MeterListener` filtered by **instrument instance**, never by meter name
alone (the #503 lesson).
## T11: ScadaBridge prerequisite (cross-repo)
- **Filed as ScadaBridge#138** (2026-11-13). A ScadaBridge issue (`type:feature`, `cross-repo`, `priority:p1`, linked to #717). The DCL becomes
ServiceLevel-aware: monitor `i=2267`, and fail over when it is below 200 for a configurable window while the
other endpoint reports higher. Also add a test for an unsolicited RefreshStart/End on existing alarm items
(spec §5).
- File the lmxopcua companion as `blocked` + `cross-repo`.
- **The Warm flip in T13/rollout is gated on that issue being deployed.**
## T12: Documentation and index
- `docs/Redundancy.md`: rewrite the `:9` block, add a Warm contract section, update the tiers table. Remove the
generic "standby / no device contact / exactly-once" wording that contradicts acquisition and at-least-once
(c7794).
- `docs/OpcUaServer.md:70`, `docs/Configuration.md` (the new keys), and `docs/security.md` (ns=0 stays ungated;
projection order vs. ACL).
- `.claude/rules/cluster-topology.md` §Redundancy.
- `docs/plans/phase-6-3-redundancy-interop-plan.md` A2/A4/A5b: under Warm, A2 expects 90 and A4/A5b become
testable. Add `docs/v2/redundancy-interop-playbook.md`.
- Umbrella: update the OtOpcUa row and `sister-project-history/otopcua.md` in `../scadaproj` on **its `main`**,
pushed (root `CLAUDE.md` procedure).
## T13: Live gate on docker-dev (central pair, `:4840` / `:4841`)
**Overlay:** `docker-dev/docker-compose.warm.yml`, central-1/2 only. It sets `OpcUa__Redundancy__Mode=Warm`. The base
compose file already gives each central its own `OpcUa__ApplicationUri=urn:OtOpcUa:central-1|2` (matching
`seed-clusters.sql`) and its partner in `OpcUa__PeerApplicationUris__0` (lmxopcua#801, after spec §2 was written). Login is disabled on the rig, so drive
everything yourself. Use `otopcua-cli` from `src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI` against both ports.
| Leg | Procedure | Pass |
|---|---|---|
| L1 metadata | `redundancy` on :4840 and :4841 | `RedundancySupport=Warm`. ServerUriArray is self first and differs per node. Same URIs in both. |
| L2 bands | `read -n i=2267` on both | Primary 250, Standby 90 |
| L3 standby data | `read` and `subscribe` of a raw tag and its UNS reference on the Standby | `BadOutOfService`/null; the Primary shows Good at the same moment |
| L4 standby alarms | `alarms` on both. Trip a scripted alarm via its source tag. | Event on the Primary only. A ConditionRefresh on the Standby lists it as retained (D5). |
| L5 manual failover | AdminUI manual failover (`docs/Redundancy.md` §Manual failover). Keep the CLI subscriptions open on both. | Old Primary: SL drops to 0 (a Leaving/Exiting member is not Up/Joining, so `ServiceLevelCalculator.ComputeWarm` returns 0; T13 note A), then `BadOutOfService`, with no Good delivered after the drop. New Primary: Good values, then RefreshStart / retained / RefreshEnd, then SL 250, in that order (timestamps). |
| L6 crash | `docker kill central-<primary>` | The survivor goes Active once the Primary is unreachable (`PromoteWhilePrimaryUnreachable`, owner answer Q2). Record the measured gap. |
| L7 rejoin | Restart the killed node | It comes back Standby (90) and never shows 250 or 255. The boot read is 1 or 90. |
| L8 standalone | site-b-2 (or a one-node overlay) with `Mode=None` | `RedundancySupport=None`, no `i=11314`, data Good |
| L9 Unset control | Another node left on `Unset` | Byte-identical to pre-change: SL 240/250, SDK-default `i=3709` |
| L10 writes/history | Write and HistoryRead on the Standby | The write is refused `BadInvalidState` (owner answer Q1); HistoryRead is Good. |
| L11 transfer | A UserName session's subscription on the Standby is taken over by a second session of the same identity (TransferSubscriptions), then the node is demoted/promoted | The transferred items keep their marker; a demotion still projects; a promotion delivers Good. |
| L12 durable restore | A durable subscription, if the rig's SDK configuration enables them, across a node restart | The restored items are created through the custom item (projected on the Standby). If durable subscriptions are not enabled on the rig, record that and leave the leg open. |
Record evidence in `docs/plans/2026-11-xx-warm-redundancy-717-live-gate.md`. Do **not** mark G8/G9 (#615); they
need CTT and a production client (Ignition 8.3 / ScadaBridge after T11).
## Rollout
1. Merge T1–T12 dark (`Unset` default). The full CI floor applies.
2. Deploy the ScadaBridge T11 change everywhere ScadaBridge reads OtOpcUa.
3. Upgrade **both** nodes of a pair to a revision-capable build (T3) before flipping either one.
4. Flip both nodes of one docker-dev pair, then run T13. After that, flip one non-production site pair.
5. Production is a separate, owner-approved change per pair. Flip the **Secondary first**, then the Primary, in
one window.
A mixed window (one `Warm`, one `Unset`) is tolerable: the Unset node serves Good at 240/250. But do not leave it
that way, because `ServerUriArray` then exists on only one node.
## Rollback
Set `OpcUa:Redundancy:Mode=Unset` on both nodes and restart them. The setting is startup-static, so there is
nothing persistent to undo: no schema changes and no artifact changes. The `Revision` field stays and is harmless,
because unrevisioned handling is preserved. Rolling back ScadaBridge is independent; its ServiceLevel-aware
failover also works against `Unset` servers.
## Implementation status (2026-11-13)
T1–T10 and T12 are implemented on `master`, default-off (`OpcUa:Redundancy:Mode` defaults to `Unset`, pinned by
`WarmRedundancyWireTests.Unset_is_todays_server_exactly` and `OpcUaPublishActorWarmTests.Unset_never_drives_the_projection_and_keeps_todays_levels`).
T11 is ScadaBridge#138 (separate). **T13 ran 2026-11-13** on an isolated two-node pair (not the shared docker-dev rig):
every applicable leg passes after `c569f806`, which fixes two crash-failover defects the gate found. The survivor no
longer demotes when auto-down removes the Primary, and the verdict reads its own cluster events instead of the lagging
read view. Evidence: `docs/plans/evidence/2026-11-13-717-t13/RESULTS.md`. L8 (None) was not run, and L12 is not
applicable (durable subscriptions are off). G8/G9 (#615) stay open.
Test homes: `WarmStandbyUnitTests` (OpcUaServer.Tests: marker, rewrite, decision record, the SDK-field regression pin,
option rules), `WarmRedundancyWireTests` (OpcUaServer.IntegrationTests: metadata per mode, read projection, write and
Part 9 refusal, the three T0 demotion timings, live-item queue, alarm suppression/refresh, effective-URI XML load),
`WarmRedundancyRevisionTests` + `WarmServiceLevelBandTests` (ControlPlane.Tests), `WarmRoleAuthorityTests` +
`OpcUaPublishActorWarmTests` (Runtime.Tests), `OpcUaRedundancyValidationTests` (Host.IntegrationTests). The deferred
depth below adds `WarmSingletonHandoverTests` (ControlPlane.Tests), `WarmRedundancyMetricsTests` (Runtime.Tests),
`WarmStandbyCloneMatrixTests` (OpcUaServer.Tests), `WarmRedundancyWireTests.Deferred.cs` and `WarmRedundancyPooledWireTests`
(OpcUaServer.IntegrationTests).
**Deferred coverage added (2026-11-13, in-process, no docker).** Each test was mutation-checked against a deliberately
broken implementation and failed. No product bug was found.
- **T3:** `WarmSingletonHandoverTests` (ControlPlane.Tests). A real 2-node cluster runs the redundancy singleton under
`ClusterSingletonManager` on both nodes. The old incarnation's last publish is held back through the broadcast seam,
its node is downed, and the singleton hands over. The held publish is then delivered to a real Warm
`OpcUaPublishActor` on the survivor. That publish is the older revision but has the higher sequence. The survivor
stays Active. The second test pins that a removed node cannot rejoin from its old ActorSystem. A new ActorSystem on
the same address rejoins as a younger member, with a higher up-number. Mutations killed:
- the gate accepts older revisions;
- the revision drops the up-number and incarnation (sequence only);
- for the pin, skipping the Down (a harness negative control).
- **T6:** `A_DataEncoding_read_and_item_are_projected_…` (wire). On the Standby, a Binary or XML DataEncoding read of
a structured (EUInformation) tag is projected. An encoding a scalar cannot take still returns the base read's own
`BadDataEncodingUnsupported`. An item created with `DefaultXml` gets the projected value on the Standby, and on
promotion it receives the value read through its own encoding (TypeId `i=888`). Mutations killed:
- DataEncoding reads are not projected;
- the promotion queue ignores the item's DataEncoding.
- **T7:**
- `An_item_deleted_between_queue_and_publish_…` (wire). The deleted item's queued samples never surface. Its
sibling is still first-delivered projected, and a Republish gives the same result.
- `WarmRedundancyPooledWireTests.A_client_handle_reused_after_delete_…` (wire, non-parallel collection). A marked
payload goes back through SDK 2.0.1's process-wide payload pool, and its ClientHandle is reused by an `i=2267`
item. That item stays Good. The test first asserts that the pool really hands out a marked payload.
- `WarmStandbyCloneMatrixTests` (unit). One delivered clone carries two DataChangeNotifications (one with
DiagnosticInfos), an EventNotificationList and a StatusChangeNotification. Only marked values are rewritten.
Diagnostics, events and status pass through in order. Neither the clone nor the cached message is mutated, and
the result encodes. Two clones project to identical bytes. A recycled payload's stale marker, rented through the
real pool with the same handle, never validates.
- Mutations killed:
- the marker is not validated (wire and unit);
- the marker is not set;
- DiagnosticInfos are dropped;
- non-data payloads are dropped;
- the rewrite happens in place;
- only the first DataChangeNotification is rewritten.
- **T8:** `An_ACL_stood_down_item_receives_nothing_…` (wire). An item that `RevalidateMonitoredItems` stood down gets
nothing from a demotion or a promotion (`QueueCurrentToLiveItems` returns 1, not 2). Its permitted sibling gets
both. Once the grant is restored, the next demotion reaches the item. Mutation killed: stood-down items are not
skipped.
- **T10:**
- `WarmRedundancyMetricsTests` (Runtime.Tests, non-parallel collection) checks four things:
- `warm_transition`, with direction and reason (`agreed` / `snapshot`), and no count on a same-role snapshot;
- the `warm_role` gauge, -1, then 0, then 1, then 0;
- `snapshot_rejected` at the publish actor for `older_revision` and `unrevisioned`;
- at `DriverHostActor`, a stale snapshot is dropped under Warm and counted, and its role view does not move. The
Unset control does move. This is the first actor test of the driver host's ordering gate.
- `WarmRedundancyPooledWireTests` checks `standby.projected_notifications`: it equals the rewritten count, counts
again on Republish, and stays 0 while Active. It also checks `standby.suppressed_alarm_events`: one per withheld
transition, none once Active.
- Every listener selects by instrument instance.
- Mutations killed: each counter's `Add` was removed, the direction tag inverted, the gauge never set, and the
driver-host gate ignored.
Still open (live-only, T13): the durable restore, TransferSubscriptions under one identity, and the rig legs.