Joseph Doherty 4b0be1335e fix(opcua): hold last-known-good when a deploy's artifact cannot be read (#485)
A transient ConfigDb error while loading a deployment's artifact emptied the
served address space. LoadArtifact caught the exception, logged "rebuild
becomes no-op" and returned zero bytes; those parsed to an EMPTY composition,
which the planner diffed against the live one as a PureRemove and the applier
faithfully executed — 16 nodes gone, while the log claimed nothing happened.

An artifact we could not obtain is not an empty configuration. Nothing
legitimate produces a zero-length blob (an operator who really deletes
everything still deploys a JSON document with empty arrays), so "no bytes" can
only mean "no answer". HandleRebuild now abandons the rebuild on one, leaving
both the materialised nodes and _lastApplied intact so the retry diffs against
what is actually being served. The loader's own log line is now true.

The two cases are logged differently: warn when there is a live address space
being protected, debug when nothing has been deployed to this node yet.

Covered by a RED-first actor test (verified failing: the load error tore down
eq-2's subtree), plus a positive control proving a READABLE artifact that
genuinely drops an equipment still removes it — the guard suppresses teardown
only when the read failed.

Found on the LocalDb Phase 1 follow-up live gate, which induced it by flapping
SQL; that gate's log is the production evidence for the seam.

Closes #485

Claude-Session: https://claude.ai/code/session_01GASWkNEi68FSCtvr6rLoEW
2026-07-21 02:29:39 -04:00

6.9 KiB

LocalDb Phase 1 follow-ups — live gate (docker-dev rig)

Closes the two limitations left open by 2026-07-20-localdb-phase1-live-gate.md (checks 4 and 8). Rig: local docker-dev/docker-compose.yml, 6 nodes rebuilt from fix/localdb-phase1-followups. site-a pair replicates; central + site-b stay default-OFF.

Safety rules followed (same as the Phase 1 gate): all DB inspection via docker cp of the db/-wal/-shm triplet, querying the copy — never host sqlite3 on the live WAL file.

Result

Both follow-ups closed, and the gate found a third defect — one that was unreachable until the first fix landed. Library ZB.MOM.WW.LocalDb went 0.1.10.1.20.1.3 in the course of this gate; both consumers (OtOpcUa, ScadaBridge) are pinned to 0.1.3.

# Check Result Evidence
8 Oplog stops growing on a default-OFF node PASS site-b-1 restarted twice with an unchanged cached artifact: oplog_depth 7 → 7 → 7, deployment_pointer.applied_at_utc frozen at 05:34:58 across both — the re-cache was skipped outright. Repeated on the 0.1.3 build after a real deploy: 13 → 13. Pre-fix this grew ~2 rows per restart forever, because a default-OFF node has no peer to ack and prune them.
8b …but a genuinely new deployment still writes (positive control) PASS A real config change (renamed tag SITEA-tag) produced rev 822bdf34, then 002c16b3. site-b-1's oplog 7 → 10 → 13 and its pointer advanced each time. The skip suppresses identical re-writes only; it is not a dead cache-write path.
4 A wiped node is back-filled by its peer, no new deploy, central down PASS (was ⚠️ PARTIAL) Precondition asserted first — site-a-1's oplog 0, needs_snapshot 0: the exact state that used to make back-fill impossible. Then SQL stopped, site-a-2's LocalDb volume destroyed, container recreated. a-1 logged Snapshot sent (as_of_seq 0, 4 rows) — a line that could not appear on 0.1.1. a-2 came back with pointer SITE-A / 475df87a @ 03:09:12 (a-1's original timestamp, not a re-derived one), chunks 2, and a __localdb_row_version dump byte-identical to a-1's, carrying origin node ids 6812ca9c and 935659a5 — the rebuilt node's own id appears nowhere, so the rows were replicated, not recreated.
4b …and the back-filled node then boots from cache PASS With SQL still down, site-a-2 logged RUNNING FROM CACHE — … booted deployment 475df87a… cached at 2026-07-21T03:09:12, raw subtree materialised (containers=16, tags=1). OPC UA browse of both nodes: 17 ns=2 nodes each, diff-identical — the rebuilt node serves exactly what its healthy peer does, from a configuration it never applied itself and could not have fetched.
4c The rebuilt node's OWN writes reach its peer PASS after a third fix (see below) On 0.1.2 this failed: a-1 held last_applied_remote = 10 while the rebuilt a-2's oplog was seqs 1,2,3 and its last_acked stayed 0 — never accepted. On 0.1.3, a-1 logs Replication peer identity changed (ebb10854 -> c85d8b1d): the peer was rebuilt … Resetting the inbound watermark, and after the next deploy a-1 shows last_applied_remote = 3 / a-2 shows last_acked = 3 with a drained oplog and identical row_versions.

The third defect (the reason this gate was worth running)

0.1.2 made back-fill work, which for the first time let a rebuilt node be observed writing. It turned out its writes went nowhere.

last_applied_remote_seq is a watermark in the peer's seq space, and a rebuilt peer is a new database whose oplog numbers from 1. Two independent bugs stacked, and fixing either alone leaves the data stuck:

  1. The healthy node kept advertising the old peer's watermark. The sending side seeds its pump directly from that number (_sentThruSeq), so the rebuilt node skipped its entire oplog. → the watermark (and the observed peer clock) is now reset when the peer's node id changes. last_acked_seq is deliberately not reset: it describes our own oplog's pruned horizon and is exactly what 0.1.2 keys the snapshot decision off — clearing it would switch back-fill back off.
  2. A peer claiming to have applied more of our stream than we have ever produced can only be remembering a previous incarnation of us. → that claim is now rejected in favour of pumping from the start; LWW makes the re-send harmless. This mirrors the clamp RecordPeerAckAsync already applies to acks.

Both were reproduced offline as a RED test before fixing (SnapshotResyncTests.RebuiltPeer_OwnWritesReachTheHealthyNode_DespiteTheOldPeersWatermark).

Why offline tests could not have found it first: the wiped-peer scenario had no test because the scenario was believed impossible to recover from — it was a documented limitation, not a bug. The gate is what turned the limitation into a reproducible case, and the second defect only existed behind the first.

Unrelated finding (NOT a follow-up of this work — pre-existing; lmxopcua issue #485, since FIXED)

While SQL was being stopped and started to drive check 4, site-b-1 took a deploy whose artifact load hit a transient ConfigDb error, and emptied its served address space:

[06:11:20 ERR] An error occurred using the connection to database 'OtOpcUa' on server 'sql,1433'.
[06:11:20 WRN] OpcUaPublish: failed to load artifact for deployment 43d54397…; rebuild becomes no-op
[06:11:20 INF] AddressSpaceApplier: applied plan (kind=PureRemove, added=0, removed=16, rebuild=True)

The log says "rebuild becomes no-op" and the applier then removed all 16 nodes — those two disagree. The cache layer behaved correctly and refused to store the bad artifact ("not caching deployment … its artifact was empty or could not be loaded, so it is not a usable last-known-good configuration"), and the node recovered fully on restart (containers=16). But a transient ConfigDb blip emptying the served address space instead of holding last-known-good is the same failure class as the Phase 1 gate's check-3 defect. Untouched by this work — site-b-1 has replication off entirely — and induced by this gate's own SQL flapping.

Fixed (issue #485): OpcUaPublishActor.HandleRebuild now treats an artifact it could not obtain as no answer rather than an empty configuration, and abandons the rebuild with the served address space (and _lastApplied) intact. Nothing legitimate produces a zero-length blob — an operator who really deletes everything still deploys a JSON document with empty arrays — so "no bytes" can only mean the read failed. The log excerpt above is now impossible: the PureRemove never runs, and the loader's own "the rebuild is abandoned" line is finally true. Covered by OpcUaPublishActorRebuildTests.Rebuild_keeps_the_last_known_good_address_space_when_the_artifact_load_fails, with a positive control proving a readable artifact that genuinely drops an equipment still tears its subtree down.