lmxopcua/docs/plans/2026-10-09-pluggable-historian-live-gate.md
T
Joseph Doherty 5fdf205caa test(historian): live gate PASSED on docker-dev (SqlServer backend); CLI prints node-level HistoryUpdate result
Gate: Primary-only typed recording with real status, raw+UNS HistoryRead/Processed parity, HistoryUpdate
insert/duplicate/replace/delete + WriteOperate-only and anonymous denied, failover at 1x, Modbus device loss
stored as BadCommunicationError then a BadNoCommunication outage marker. Gate found the CLI hid the
node-level refusal code (fixed + pinned) and a pre-existing OpcUaClient comms-loss gap (filed separately).
docker-dev compose gains ServerHistorian__Backend / __SqlServer__ConnectionString (default Gateway).

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-09 15:14:46 -04:00

134 lines
6.8 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Pluggable historian — live gate (T15), 2026-10-09
**Verdict: PASSED.** All six legs passed on the docker-dev rig. The rig ran `feat/pluggable-historian` at
`e2011a65` (plus the gate CLI fix), with the central pair on image `923f5f09e805`, rebuilt for this gate. The SQL Server backend
pointed at the rig's `sql` container (database `OtOpcUaHistorian`).
The gate also found two defects:
- A display gap in Client.CLI `historyupdate`. It is fixed in the same change.
- An OpcUaClient driver comms-loss gap that predates this work. It is filed separately.
## Setup
- `CREATE DATABASE OtOpcUaHistorian` on `otopcua-dev-sql-1`. The schema `hist` was auto-created by the
bootstrapper on first use: `SchemaVersion`, `Tag`, `Sample`, `Event`.
- `docker-dev/docker-compose.yml` gained `ServerHistorian__Backend` (`OTOPCUA_HISTORIAN_BACKEND`, default
`Gateway`) and `ServerHistorian__SqlServer__ConnectionString` (`OTOPCUA_HISTORIAN_SQL`).
- Central-1 and central-2 were started with:
```
OTOPCUA_HISTORIAN_ENABLED=true OTOPCUA_HISTORIAN_BACKEND=SqlServer OTOPCUA_CONTHIST_ENABLED=true \
docker compose -f docker-dev/docker-compose.yml up -d central-1 central-2
```
Both containers ran the new image, with `Backend=SqlServer`.
- Cluster `MAIN` fixtures: opc-plc (`opcplc/plc/FastUInt1`, UInt32, about 1 Hz) and pymodbus `standard`
(`pymodbus/plc/HR5`).
- New Calculation String tag `Calc/eng/FastLabel` = `"v" + FastUInt1`. `FastUInt1`, `FastLabel` and later
`HR5` were marked `isHistorized`. A UNS reference `a/l/e1/FastUInt1` was added. The configuration was
deployed headlessly (`deploy.sh`), and the tags were provisioned:
- `hist.Tag` 1 = FastLabel (DataType 9, String)
- `hist.Tag` 2 = FastUInt1 (5, Int64)
- `hist.Tag` 3 = HR5 (4)
- Two data-plane API keys were minted for this gate, each with a `Cluster`-scoped grant:
- `gate-historyupdate`: ReadOnly | HistoryUpdate (4239)
- `gate-writeop`: ReadOnly | WriteOperate (159)
ACL flag off, which is the rig default.
## 1. Recording: Primary-only, typed, real status, one row per value
- Rows carry real kinds and statuses:
- `ValueKind=2` Int64 `477`/`479`/…, status `0`
- `ValueKind=4` String `v477`/`v479`/…, status `0`
- startup `ValueKind=0` Empty, with `0x80320000` (BadWaitingForInitialData) and `0x80310000`
- Primary-only:
- Central-2 was the driver Primary, and its outbox held `hlog.log.0`.
- Central-1's outbox directory was empty, and it logged "this node is not the recording Primary … suppressing
value capture".
- One row per published value, checked over 82 s:
- 79 Good FastUInt1 rows and 79 Good FastLabel rows.
- All 79 pair one-to-one: same `SourceTimeUtc`, `StrValue = 'v' + IntValue`.
- 0 duplicate values.
## 2. HistoryRead through the raw and UNS NodeIds
These reads went to central-1 (`:4840`). Central-2's `:4841` returns "Server did not return the
certificate used to create the secure channel" to the CLI; that rig port-mapping quirk is unrelated.
- Raw read 19:00:40–19:00:50 on `ns=2;s=opcplc/plc/FastUInt1` and on `ns=3;s=a/l/e1/FastUInt1`:
- Identical 8 rows (493…502). Only the header line differs.
- They equal the `hist.Sample` rows exactly.
- The gaps (497, 501) come from the driver's 1 s sampling of a 1 s counter. They are in the stored rows and
in the publish stream alike.
- Average at 10 s, 19:00:40–19:01:10, through both NodeIds:
- Both return `497.125 / 507.5 / 517.5`, Good.
- These equal a direct SQL `AVG` per 10 s bucket (8, 10 and 10 samples).
## 3. HistoryUpdate
These calls went to central-1 with `-U apikey`. Each was checked by `historyread` and by direct SQL.
| Call | Result | Confirmed |
|---|---|---|
| insert 18:00:00 = 42 (`gate-historyupdate`) | `GoodEntryInserted` | row `42`, status 0 |
| repeat insert = 43 | `BadEntryExists`, exit 1 | row still `42` |
| replace 18:00:00 = 99 | `GoodEntryReplaced` | read and SQL show `99` |
| replace 18:00:30 (no entry) | `BadNoEntryExists` | — |
| delete-at-time 18:00:00 | `Good`, exit 0 | read returns 0 values; SQL row gone |
| insert with `gate-writeop` (WriteOperate only) | Node result `BadUserAccessDenied`, exit 1 | no row |
| insert, anonymous | Node result `BadUserAccessDenied`, exit 1 | no row |
**Gate finding (fixed):** the CLI printed only "(no result returned)" for a refused node. The refusal
reason is in the node-level result, and the CLI never showed it. `HistoryUpdateCommand` now prints
`Node result: <code>`, pinned by `Execute_NodeLevelDenial_PrintsNodeResult`. The rows above are from the
fixed build.
## 4. Failover
- 19:03:08: `docker stop` central-2, the Primary.
- 19:02:58: central-1 logged "this node is now the recording Primary … resuming value capture". It was
promoted when central-2 began leaving. Its outbox appeared, and recording continued with no gap
(633 → 644 …).
- Central-2 was restarted and rejoined as standby:
- Its `hlog.log.0` stayed frozen at 22528 bytes.
- Central-1's grew (13824 → 15360).
- Rate over the whole sequence was 1×. Per-30 s counts of FastUInt1 from 19:02:00 on: 30, 29, 29, 30, 30. There
was no doubling during or after the failover.
## 5. Device loss: driver Bad sample and comms-loss outage marker
This leg ran on Modbus (`HR5`), as planned. Stopping `otopcua-pymodbus-standard` at 19:09:00 produced:
| SourceTimeUtc | ValueKind | Value | Status |
|---|---|---|---|
| 19:08:38.2408 | 2 | 5 | `0x00000000` |
| 19:09:00.2649 | 0 (Empty) | NULL | `0x80050000` BadCommunicationError (driver's own Bad publish) |
| 19:10:38.2327 | 0 (Empty) | NULL | `0x80310000` BadNoCommunication (#527 watchdog outage marker, ~98 s later) |
| 19:12:38.4474 | 2 | 5 | `0x00000000` (fixture restarted 19:12:37; recovery re-publish) |
This confirms design §9.10 as amended: comms loss is historized as an outage marker. The plan's original
leg-6 text predated that correction.
Reads over the outage:
- Raw `historyread` shows Bad/Good/Bad/Bad/Good.
- Average at 120 s gives `5 Uncertain` / `(null) Bad` / `5 Good`.
The outage is visible and is not bridged.
**Gate finding (pre-existing, filed separately):** stopping opc-plc first produced NO Bad sample. The
OpcUaClient driver kept serving `FastUInt1 = 745`, status Good, for more than 3.5 minutes. It did not
recover after opc-plc was restarted either. Its session loss never reaches the node status or driver
health, so the #527 watchdog cannot fire. This is unrelated to the historian; Modbus behaves as designed.
## Restore
- The rig was restored afterwards:
- central-1 and central-2 were recreated with the compose defaults (historian off).
- The gate tags, script, UNS reference, API keys and ACL rows were removed.
- The `HR5` and `FastUInt1` TagConfigs were reverted.
- The configuration was redeployed.
- `OtOpcUaHistorian` was dropped.
- The opc-plc and pymodbus fixtures were stopped (normally down).
- The compose keys stay, defaulting to `Gateway`.