Turns the Phase 6.1 Stream B.4 pure-logic ScheduledRecycleScheduler (shipped in PR #79) into a running background feature. A Tier C driver registers its scheduler at startup; the hosted service ticks every TickInterval (default 1 min) and invokes TickAsync on each registered scheduler. Server.Hosting: - ScheduledRecycleHostedService : BackgroundService. AddScheduler(s) must be called before StartAsync — registering post-start throws InvalidOperationException to avoid "some ticks saw my scheduler, some didn't" races. ExecuteAsync loops on Task.Delay(TickInterval, _timeProvider, stoppingToken) + delegates to a public TickOnceAsync method for one tick. - TickOnceAsync extracted as the unit-of-work so tests drive it directly without needing to synchronize with FakeTimeProvider + BackgroundService timing semantics. - Exception isolation: if one scheduler throws, the loop logs + continues to the next scheduler. A flaky supervisor can't take down the tick for every other Tier C driver. - Diagnostics: TickCount + SchedulerCount properties for tests + logs. Tests (7 new ScheduledRecycleHostedServiceTests, all pass): - TickOnce before interval doesn't fire; TickCount still advances. - TickOnce at/after interval fires the underlying scheduler exactly once. - Multiple ticks accumulate count. - AddScheduler after StartAsync throws. - Throwing scheduler doesn't poison its neighbours (logs + continues). - SchedulerCount matches registrations. - Empty scheduler list ticks cleanly (no-op + counter advances). Full solution dotnet test: 1193 passing (was 1186, +7). Pre-existing Client.CLI Subscribe flake unchanged. Production wiring (Program.cs): builder.Services.AddSingleton<ScheduledRecycleHostedService>(); builder.Services.AddHostedService(sp => sp.GetRequiredService<ScheduledRecycleHostedService>()); // During DI configuration, once Tier C drivers + their ScheduledRecycleSchedulers // are resolved, call host.AddScheduler(scheduler) for each. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
LmxOpcUa
OPC UA server and cross-platform client tools for AVEVA System Platform (Wonderware) Galaxy. The server exposes Galaxy tags via MXAccess as an OPC UA address space. The client stack provides a shared library, CLI tool, and Avalonia desktop application for browsing, reading/writing, subscriptions, alarms, and historical data.
Architecture
OPC UA Clients
(CLI, Desktop UI, 3rd-party)
|
v
+-----------------+ +------------------+ +-----------------+
| Galaxy Repo DB |---->| OPC UA Server |<--->| MXAccess Client |
| (SQL Server) | | (address space) | | (STA + COM) |
+-----------------+ +------------------+ +-----------------+
| |
+-------+--------+ +---------+---------+
| Status Dashboard| | Historian Runtime |
| (HTTP/JSON) | | (SQL Server) |
+----------------+ +-------------------+
Contained Name vs Tag Name
| Browse Path (contained names) | Runtime Reference (tag name) |
|---|---|
TestMachine_001/DelmiaReceiver/DownloadPath |
DelmiaReceiver_001.DownloadPath |
TestMachine_001/MESReceiver/MoveInBatchID |
MESReceiver_001.MoveInBatchID |
Server
The OPC UA server runs on .NET Framework 4.8 (x86) and bridges the Galaxy runtime to OPC UA clients.
Server Prerequisites
- .NET Framework 4.8 SDK
- AVEVA System Platform with ArchestrA Framework installed
- Galaxy repository database (SQL Server, Windows Auth)
- MXAccess COM registered (
LMXProxy.LMXProxyServer) - Wonderware Historian (optional, for historical data access)
- Windows (required for COM interop and MXAccess)
Build and Run Server
dotnet restore ZB.MOM.WW.LmxOpcUa.slnx
dotnet build src/ZB.MOM.WW.LmxOpcUa.Host
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Host
The server starts on opc.tcp://localhost:4840/LmxOpcUa with the None security profile by default. Configure Security.Profiles in appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt for transport security. See Security Guide.
Install as Windows Service
cd src/ZB.MOM.WW.LmxOpcUa.Host/bin/Debug/net48
ZB.MOM.WW.LmxOpcUa.Host.exe install
ZB.MOM.WW.LmxOpcUa.Host.exe start
Service logon requirement: The service must run under a Windows account that has access to the AVEVA Galaxy and Historian. The default LocalSystem account can connect to MXAccess and SQL Server but cannot authenticate with the Historian SDK (HCAP). Configure the service to "Log on as" a domain or local user that is a recognized ArchestrA platform user. This can be set in services.msc or during install with ZB.MOM.WW.LmxOpcUa.Host.exe install -username DOMAIN\user -password ***.
Run Server Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.IntegrationTests
Client Stack
The client stack is cross-platform (.NET 10) and consists of three projects sharing a common IOpcUaClientService abstraction. No AVEVA software or COM is required — the clients connect to any OPC UA server.
Client Prerequisites
- .NET 10 SDK
- No platform-specific dependencies (runs on Windows, macOS, Linux)
Build All Clients
dotnet build src/ZB.MOM.WW.LmxOpcUa.Client.Shared
dotnet build src/ZB.MOM.WW.LmxOpcUa.Client.CLI
dotnet build src/ZB.MOM.WW.LmxOpcUa.Client.UI
Run Client Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.Client.Shared.Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.Client.CLI.Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.Client.UI.Tests
Client CLI
# Connect
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840/LmxOpcUa
# Browse Galaxy hierarchy
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=ZB" -r -d 5
# Read a tag
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestMachine_001.MachineID"
# Write a tag
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestChildObject.TestString" -v "Hello"
# Subscribe to changes
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestChildObject.TestInt" -i 500
# Read historical data
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- historyread -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestMachine_001.TestHistoryValue" --start "2026-03-25" --end "2026-03-30"
# Subscribe to alarm events
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- alarms -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestMachine_001" --refresh
# Query redundancy state
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- redundancy -u opc.tcp://localhost:4840/LmxOpcUa
Client UI
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.UI
The desktop application provides browse tree, subscriptions, alarm monitoring, history reads, and write dialogs. See Client UI Documentation for details.
Project Structure
src/
ZB.MOM.WW.LmxOpcUa.Host/ OPC UA server (.NET Framework 4.8, x86)
Configuration/ Config binding and validation
Domain/ Interfaces, DTOs, enums, mappers
Historian/ Wonderware Historian data source
Metrics/ Performance tracking (rolling P95)
MxAccess/ STA thread, COM interop, subscriptions
GalaxyRepository/ SQL queries, change detection
OpcUa/ Server, node manager, address space, alarms, diff
Status/ HTTP dashboard, health checks
ZB.MOM.WW.LmxOpcUa.Client.Shared/ Shared OPC UA client library (.NET 10)
ZB.MOM.WW.LmxOpcUa.Client.CLI/ Command-line client (.NET 10)
ZB.MOM.WW.LmxOpcUa.Client.UI/ Avalonia desktop client (.NET 10)
tests/
ZB.MOM.WW.LmxOpcUa.Tests/ Server unit + integration tests
ZB.MOM.WW.LmxOpcUa.IntegrationTests/ Server integration tests (live DB)
ZB.MOM.WW.LmxOpcUa.Client.Shared.Tests/ Shared library tests
ZB.MOM.WW.LmxOpcUa.Client.CLI.Tests/ CLI command tests
ZB.MOM.WW.LmxOpcUa.Client.UI.Tests/ UI ViewModel + headless tests
gr/ Galaxy repository docs, SQL queries, schema
Documentation
Server
| Component | Description |
|---|---|
| OPC UA Server | Endpoint, sessions, security policy, server lifecycle |
| Address Space | Hierarchy nodes, variable nodes, primitive grouping, NodeId scheme |
| Galaxy Repository | SQL queries, deployed package chain, change detection |
| MXAccess Bridge | STA thread, COM interop, subscriptions, reconnection |
| Data Type Mapping | Galaxy to OPC UA types, arrays, security classification |
| Read/Write Operations | Value reads, writes, access level enforcement, array element writes |
| Subscriptions | Ref-counted MXAccess subscriptions, data change dispatch |
| Alarm Tracking | AlarmConditionState nodes, InAlarm monitoring, event reporting |
| Historical Data Access | Historian data source, HistoryReadRaw, HistoryReadProcessed |
| Incremental Sync | Diff computation, subtree teardown/rebuild, subscription preservation |
| Configuration | appsettings.json binding, feature flags, validation |
| Status Dashboard | HTTP server, health checks, metrics reporting |
| Service Hosting | TopShelf, startup/shutdown sequence, error handling |
| Security | Transport security profiles, certificate trust, production hardening |
| Redundancy | Non-transparent warm/hot redundancy, ServiceLevel, paired deployment |
Client
| Component | Description |
|---|---|
| Client CLI | Connect, browse, read, write, subscribe, historyread, alarms, redundancy commands |
| Client UI | Avalonia desktop client: browse, subscribe, alarms, history, write values |
Reference
- Galaxy Repository Queries — SQL queries for hierarchy, attributes, and change detection
- Data Type Mapping — Galaxy to OPC UA type mapping with security classification
License
Internal use only.