Authoring FOCAS tags through /raw -> Browse device... produced tags the driver
could never read. Every committed tag read BadNodeIdUnknown forever, and the
failure was silent end to end: the AdminUI accepted it, the deploy gate sealed
green, and the driver reported Healthy with 0 errors while ignoring the tags.
Net effect: the whole fixed-tree surface could not be published through any v3
authoring path. Found cutting wonder-app-vd03 over to v3 against a real Makino
Pro 5 / Fanuc 30i, where 0 of 20 committed tags read while two hand-authored
MACRO: tags on the same device read Good.
A captured browse leaf's id IS its DriverAttributeInfo.FullName, and the fixed
tree emitted "{deviceHost}/{path}" there -- an internal cache key, not an
address. Both authoring paths wrote it verbatim into TagConfig.address, and
FocasAddress.TryParse accepts no such form, so the driver skipped the tags at
init.
Fixed at the emitter rather than by stripping the host at commit, which fixes
the browse-commit flow and the manual picker's tree-select together and leaves
one canonical address form:
- FocasAddress gains a fourth kind, FIXED:<path>, and moves to Contracts so the
AdminUI and ControlPlane can parse without referencing the runtime driver
(#526). A FIXED: read is served from the fixed-tree snapshot the poll loop
already maintains -- no area read, no connection. Writes refuse: nothing in
that tree is a writable location on the CNC.
- The address carries no device. A tag's device comes from its Device row, and
a second routing channel for one fact is what created this defect.
- An authored FIXED: tag arms the fixed-tree poll loop by itself. Enabled
defaults false and the browser force-enables it only for a browse, so the
operator would otherwise browse, commit, deploy, and land on a driver whose
loop never starts -- every tag Bad with a correct address.
- Fixed-tree values are now dated from the last answered poll and go
BadCommunicationError once it is stale (8 cadences, floored at 30s). The poll
loop swallows a failed tick by design, so a dead CNC would otherwise serve its
last snapshot as Good indefinitely -- harmless while nothing could bind to the
tree, not harmless now.
Guardrails, so this class cannot recur silently:
- FocasTagConfigModel.Validate() runs the real parser instead of a non-empty
check, and FocasTagDefinitionFactory.Inspect() warns at the deploy gate, which
covers CSV/API config that never touches the modal.
- The manual picker offered axis/spindle/program/status "parameter groups" --
none of which is a FOCAS addressing space -- and its own default value,
axis:5, was unusable. It now composes PMC / PARAM: / MACRO: through
FocasAddress, so what it emits is parseable by construction.
Tests assert addresses ROUND-TRIP through the parser rather than matching an
expected string: the previous FocasAddressBuilderTests pinned "axis:5" exactly,
which is how a green suite coexisted with a picker nobody could use. Verified
red-first against the old emitter. FOCAS 308, AdminUI 1095, ControlPlane 169,
Core 581 -- all pass, 0 warnings.
The remaining half of #540 -- a driver reporting Healthy/0 errors while
skipping tags at init -- is fleet-wide (eight drivers do this) and is filed
separately rather than patched per-driver.
OtOpcUa
OPC UA server (.NET 10 AnyCPU) that exposes a fleet of industrial drivers as a single OPC UA address space. Drivers ship in-process for AVEVA System Platform Galaxy (via the sibling mxaccessgw repo), Modbus TCP, Siemens S7, Allen-Bradley CIP (ControlLogix / CompactLogix), Allen-Bradley Legacy (SLC 500 / MicroLogix), Beckhoff TwinCAT (ADS), FANUC FOCAS, OPC UA Client (gateway), and MQTT (broker subscribe; Sparkplug B in progress).
A cross-platform client stack (.NET 10) — shared library, CLI, and Avalonia desktop app — connects to any OPC UA server.
Architecture
OPC UA Clients (CLI, Desktop UI, 3rd-party)
|
v
+-------------------------------------+
| OtOpcUa.Server (.NET 10 AnyCPU) |
| address space + capability fan-out|
+-------------------------------------+
| | | | | | | |
Galaxy Modbus S7 AbCip AbLeg TwinCAT FOCAS OpcUaClient MQTT
|
v
mxaccessgw (sibling repo, gRPC)
|
v
MXAccess COM (x86 worker, on AVEVA box)
Galaxy is the only driver with an external runtime: it speaks gRPC to a separately installed mxaccessgw server (sibling repo at c:\Users\dohertj2\Desktop\mxaccessgw\) which owns the MXAccess COM apartment and the x86/STA bitness constraint server-side. Everything in this repo is platform-agnostic .NET 10.
Prerequisites
- .NET 10 SDK (server, drivers, clients all target .NET 10)
- SQL Server reachable for the central config DB
- For Galaxy specifically: a running
mxaccessgwdeployment — see docs/v2/Galaxy.ParityRig.md - For historian read-back / alarm history / continuous historization: a running
ZB.MOM.WW.HistorianGatewaydeployment (the sole historian backend; consumed as theZB.MOM.WW.HistorianGateway.ClientgRPC package). It must runRuntimeDb:Enabled=true+RuntimeDb:EventReadsEnabled=true, and the API key must carryhistorian:read+historian:write+historian:tags:writescopes.
Quick Start
dotnet restore ZB.MOM.WW.OtOpcUa.slnx
dotnet build ZB.MOM.WW.OtOpcUa.slnx
dotnet test ZB.MOM.WW.OtOpcUa.slnx
# Run the server in dev (foreground)
dotnet run --project src/Server/ZB.MOM.WW.OtOpcUa.Host
The server starts on opc.tcp://localhost:4840 with the None security profile. Configure Security.Profiles in src/Server/ZB.MOM.WW.OtOpcUa.Host/appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt. See docs/security.md.
Install as Windows Services
Production deployment is driven by scripts/install/Install-Services.ps1, which registers the OtOpcUa server service under a chosen service account. Historian support requires a separately deployed ZB.MOM.WW.HistorianGateway and Galaxy support a separately installed mxaccessgw — neither this repo nor the install script provisions them.
.\scripts\install\Install-Services.ps1 `
-InstallRoot 'C:\Program Files\OtOpcUa' `
-ServiceAccount 'DOMAIN\svc-otopcua'
The historian backend is the external ZB.MOM.WW.HistorianGateway (not installed by this script). See the script header and docs/ServiceHosting.md for full options.
Client CLI
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840 -r -d 3
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode"
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -v 42
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -i 500
See docs/Client.CLI.md and docs/Client.UI.md.
Documentation
Architecture deep-dives
| Topic | Doc |
|---|---|
| OPC UA server composition, namespace fan-out, Polly invoker | docs/OpcUaServer.md |
| Address space layout | docs/AddressSpace.md |
| Read / Write dispatch (driver vs virtual vs scripted-alarm) | docs/ReadWriteOperations.md |
| Incremental sync (driver-backend rediscovery + config publishes) | docs/IncrementalSync.md |
| Service hosting (Server + Admin; external HistorianGateway backend) | docs/ServiceHosting.md |
| Security (transport, LDAP, certificates) | docs/security.md |
| Redundancy | docs/Redundancy.md |
| Status dashboard | docs/StatusDashboard.md |
Drivers
| Topic | Doc |
|---|---|
| Driver specs (per-driver capability surface, config, addressing) | docs/v2/driver-specs.md |
| Galaxy driver | docs/drivers/Galaxy.md |
| Modbus / S7 / AbCip / AbLegacy / TwinCAT / FOCAS / OpcUaClient / MQTT | docs/drivers/ |
| Galaxy parity rig (mxaccessgw setup) | docs/v2/Galaxy.ParityRig.md |
| Galaxy performance + tracing | docs/v2/Galaxy.Performance.md |
Clients
| Topic | Doc |
|---|---|
| Client CLI | docs/Client.CLI.md |
| Client UI (Avalonia desktop) | docs/Client.UI.md |
v1 archive
The original v1 in-process MXAccess docs (Galaxy.Host topology, Configuration env vars, AlarmTracking, DataTypeMapping, HistoricalDataAccess, Subscriptions, etc.) are preserved under docs/v1/ — historical reference only. PR 7.2 retired the v1 architecture on 2026-04-30; current state is documented in the sections above.
License
Internal use only.