Files
lmxopcua/service_info.md
Joseph Doherty a55153d7d5 Add configurable non-transparent OPC UA server redundancy
Separates ApplicationUri from namespace identity so each instance in a
redundant pair has a unique server URI while sharing the same Galaxy
namespace. Exposes RedundancySupport, ServerUriArray, and dynamic
ServiceLevel through the standard OPC UA server object. ServiceLevel
is computed from role (Primary/Secondary) and runtime health (MXAccess
and DB connectivity). Adds CLI redundancy command, second deployed
service instance, and 31 new tests including paired-server integration.

Co-Authored-By: Claude Opus 4.6 (1M context) <noreply@anthropic.com>
2026-03-28 13:32:17 -04:00

95 lines
3.4 KiB
Markdown

# Service Update Summary
Updated service instance: `C:\publish\lmxopcua\instance1`
Update time: `2026-03-25 12:54-12:55 America/New_York`
Backup created before deploy: `C:\publish\lmxopcua\backups\20260325-125444`
Configuration preserved:
- `C:\publish\lmxopcua\instance1\appsettings.json` was not overwritten.
Deployed binary:
- `C:\publish\lmxopcua\instance1\ZB.MOM.WW.LmxOpcUa.Host.exe`
- Last write time: `2026-03-25 12:53:58`
- Size: `143360`
Windows service:
- Name: `LmxOpcUa`
- Display name: `LMX OPC UA Server`
- Account: `LocalSystem`
- Status after update: `Running`
- Process ID after restart: `29236`
Restart evidence:
- Service log file: `C:\publish\lmxopcua\instance1\logs\lmxopcua-20260325_004.log`
- Last startup line: `2026-03-25 12:55:08.619 -04:00 [INF] The LmxOpcUa service was started.`
## CLI Verification
Endpoint from deployed config:
- `opc.tcp://localhost:4840/LmxOpcUa`
CLI used:
- `C:\Users\dohertj2\Desktop\lmxopcua\tools\opcuacli-dotnet\bin\Debug\net10.0\opcuacli-dotnet.exe`
Commands run:
```powershell
opcuacli-dotnet.exe connect -u opc.tcp://localhost:4840/LmxOpcUa
opcuacli-dotnet.exe read -u opc.tcp://localhost:4840/LmxOpcUa -n 'ns=1;s=MESReceiver_001.MoveInPartNumbers'
opcuacli-dotnet.exe read -u opc.tcp://localhost:4840/LmxOpcUa -n 'ns=1;s=MESReceiver_001.MoveInPartNumbers[]'
```
Observed results:
- `connect`: succeeded, server reported as `LmxOpcUa`.
- `read ns=1;s=MESReceiver_001.MoveInPartNumbers`: succeeded with good status `0x00000000`.
- `read ns=1;s=MESReceiver_001.MoveInPartNumbers[]`: failed with `BadNodeIdUnknown` (`0x80340000`).
---
## Instance 2 (Redundant Secondary)
Deployed: `2026-03-28`
Deployment path: `C:\publish\lmxopcua\instance2`
Configuration:
- `OpcUa.Port`: `4841`
- `OpcUa.ServerName`: `LmxOpcUa2`
- `OpcUa.ApplicationUri`: `urn:localhost:LmxOpcUa:instance2`
- `Dashboard.Port`: `8082`
- `MxAccess.ClientName`: `LmxOpcUa2`
- `Redundancy.Enabled`: `true`
- `Redundancy.Mode`: `Warm`
- `Redundancy.Role`: `Secondary`
- `Redundancy.ServerUris`: `["urn:localhost:LmxOpcUa:instance1", "urn:localhost:LmxOpcUa:instance2"]`
Windows service:
- Name: `LmxOpcUa2`
- Display name: `LMX OPC UA Server (Instance 2)`
- Account: `LocalSystem`
- Endpoint: `opc.tcp://localhost:4841/LmxOpcUa`
Instance 1 redundancy update (same date):
- `OpcUa.ApplicationUri`: `urn:localhost:LmxOpcUa:instance1`
- `Redundancy.Enabled`: `true`
- `Redundancy.Mode`: `Warm`
- `Redundancy.Role`: `Primary`
- `Redundancy.ServerUris`: `["urn:localhost:LmxOpcUa:instance1", "urn:localhost:LmxOpcUa:instance2"]`
CLI verification:
```
opcuacli-dotnet.exe redundancy -u opc.tcp://localhost:4840/LmxOpcUa
→ Redundancy Mode: Warm, Service Level: 200, Application URI: urn:localhost:LmxOpcUa:instance1
opcuacli-dotnet.exe redundancy -u opc.tcp://localhost:4841/LmxOpcUa
→ Redundancy Mode: Warm, Service Level: 150, Application URI: urn:localhost:LmxOpcUa:instance2
```
Both instances report the same `ServerUriArray` and expose the same Galaxy namespace (`urn:ZB:LmxOpcUa`).
## Notes
The service deployment and restart succeeded. The live CLI checks confirm the endpoint is reachable and that the array node identifier has changed to the bracketless form. The array value on the live service still prints as blank even though the status is good, so if this environment should have populated `MoveInPartNumbers`, the runtime data path still needs follow-up investigation.