Joseph Doherty 44f6408e1c docs(archreview): round-3 re-review at 12b0035a — 7 domain reports + 00-OVERALL rewritten in place, STATUS.md round-3 section
Every round-2 finding re-verified against code (73 closed / 31 partial / 97 carried);
matrix 19/28 cells up, one down. New Critical 03/S14 (AdminUI FallbackPolicy 401s every
mesh gRPC map on a login-enabled central; masked on every rig gate by DisableLogin=true).
New Highs 03/S15, 05/STAB-19, 05/STAB-18, 03/S16 — the stale-Good family at four seams.
2026-08-20 09:09:46 -04:00

460 lines
52 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Architecture Review 05 — Protocol Drivers
**Date:** 2026-08-19
**Commit:** `12b0035a` (master, clean tree)
**Updates:** the second update — round 1 ran 2026-07-08 at `9cad9ed0`, round 2 (re-review)
2026-07-12 at `f6eaa267`. ~292 commits touched this domain since round 2, including the R2
remediation waves (R2-01 S7 fault hardening, R2-09 PollGroupEngine v2 + S7 fork retirement,
R2-11 TagConfig consolidation + #457 strict parsing), the 05/STAB-3/4/5/8/9/16/17 and
CONV-4 targeted fixes, the #516 config-re-parse sweep, the #519/#517/#497 status-code work,
the comms-loss-watchdog driver legs (#527), and **four brand-new drivers**: MTConnect
(+ IWritable), MQTT incl. Sparkplug B (Driver.Mqtt + .Browser/.Contracts/.Transport),
the SQL poll driver (Driver.Sql + .Browser/.Contracts/.Dialect), and the Calculation
pseudo-driver.
**Scope:** the twelve cross-platform protocol drivers and their satellites —
`Driver.Modbus` (+ `.Addressing`, `.Contracts`, and the new RTU-over-TCP transport),
`Driver.S7`, `Driver.AbCip`, `Driver.AbLegacy`, `Driver.TwinCAT`, `Driver.FOCAS`,
`Driver.OpcUaClient` (+ `.Contracts`, `.Browser`, and the new `.Session` leaf),
`Driver.Mqtt` (+ `.Browser`, `.Contracts`, `.Transport`), `Driver.MTConnect`
(+ `.Contracts`), `Driver.Sql` (+ `.Browser`, `.Contracts`, `.Dialect`),
`Driver.Calculation` (+ `.Contracts`), and `src/Drivers/Cli/*`. Galaxy and
Historian.Gateway are out of scope (report 06).
**Method:** every prior finding — open or claimed-closed — was re-verified against current
code with file:line evidence; no remediation claim, commit message, or doc was trusted.
The four new drivers were fresh-reviewed to the same adversarial standard as the
incumbents (full driver reads, house failure-mode hunt: built-but-never-wired, optimistic
success, fatal-vs-transient misclassification, teardown leaks on reconnect,
fixture-shaped verification gaps).
---
## Prior-finding status (f6eaa267 → 12b0035a)
| ID | One-liner | Status @ 12b0035a |
|---|---|---|
| STAB-1 | S7 no reconnect path | **REMAINS FIXED** — the R2-01 shape survives the fork retirement: `EnsureConnectedAsync` (`S7Driver.cs:1912-1954`), `MarkConnectionDeadIfFatal`, probe backstop. |
| STAB-2 | TwinCAT native subs orphaned after reconnect | **REMAINS FIXED** — `NativeRegistration` replay intact; residuals STAB-16/17 now closed too (below). |
| STAB-3 | Modbus transport desync after timeout / TxId mismatch | **CLOSED** (`98f48601`) — per-op timeout tears the socket down and normalizes as `ModbusTransportDesyncException.DesyncReason.Timeout` (`ModbusTcpTransport.cs:182-191`); TxId mismatch / truncated frame likewise (`:153-161, :176-181`); a well-formed exception PDU correctly does NOT tear down (`:165-172`). The new RTU-over-TCP transport ships the same discipline from day one — CRC/unit-mismatch/truncation → desync + teardown, per-op timeout → teardown (`ModbusRtuOverTcpTransport.cs:160-177`). |
| STAB-4 | AbCip concurrent ops on shared libplctag handles | **CLOSED** (`e48609b0`+`00dcb547`) — per-runtime `SemaphoreSlim` via `DeviceState.GetRuntimeLock` taken on read (`AbCipDriver.cs:776`), RMW (`:856`), write (`:960`); the alarm projection routes through the driver's own locked `ReadAsync`/`WriteAsync` (`AbCipAlarmProjection.cs:21-24, :150, :231`), so the new bounded-parallel read window (`MaxConcurrentReads`, `:643-645`) composes with the locks instead of bypassing them. |
| STAB-5 | FOCAS fixed-tree caches plain `Dictionary`s | **CLOSED** (`4231afb2`) — all four are `ConcurrentDictionary` (`FocasDriver.cs:1585, :1591, :1593, :1595`). But two *other* FOCAS dictionaries stayed plain — new STAB-32. |
| STAB-6 | AbLegacy probe-shutdown race; S7 unsubscribe race | **PARTIAL** — the **S7 half is CLOSED** (fork retired; `PollGroupEngine.StopStateAsync` awaits the loop before disposing the CTS, `PollGroupEngine.cs:230-239`). The **AbLegacy half is STILL OPEN**: the probe task is still discarded at spawn (`_ = Task.Run(...)`, `AbLegacyDriver.cs:190`) and `ShutdownAsync` still cancels + disposes `ProbeCts` and the runtimes without awaiting loop exit (`:231-237`) — a winding-down loop can touch a disposed CTS and raise `OnHostStatusChanged` post-shutdown. AbCip's retained-`ProbeTask` fix still never propagated back. |
| STAB-7 | `InitializeAsync` ignores `driverConfigJson` (Modbus, AbLegacy); TwinCAT empty-config quirk | **MOSTLY CLOSED** (#516 sweep `d32d89c3`/`5184a2e1`) — Modbus re-parses (`ModbusDriver.cs:326-327`), AbLegacy re-parses (`AbLegacyDriver.cs`, "#516" comment + `ParseOptions` in `InitializeAsync`), Sql re-parses all-or-nothing via `ApplyBinding` (`SqlDriver.cs:362-366`), FOCAS via the `_rebind` seam (`FocasDriver.cs:190-195`), OpcUaClient (`OpcUaClientDriver.cs:204-205`). **The TwinCAT empty-config quirk survives verbatim**: `if (parsed.Devices.Count > 0 \|\| parsed.RawTags.Count > 0) _options = parsed;` (`TwinCATDriver.cs:121-126`) — a contentful zero-device config is silently discarded, so a deploy that deliberately empties a TwinCAT driver keeps serving the old device set (FOCAS fixed the same problem with a shape check; TwinCAT's content check is the bug). |
| STAB-8 | No reconnect backoff fleet-wide | **MOSTLY CLOSED** — engine-level capped-exponential failure backoff (`backoffCap: 30s`) is passed by all seven poll consumers, and per-device `ConnectionBackoff` connect throttles landed in AbCip (`AbCipDriver.cs:1147-1167`, single-flight cold connect under `ConnectGate` `:1121`), TwinCAT (`TwinCATDriver.cs:876-878, :909-913, :1147`), FOCAS (`FocasDriver.cs:1442-1473, :1548`). **The S7 leg alone is STILL OPEN**: `EnsureConnectedAsync` documents the seam and defers it (`S7Driver.cs:1896-1908` — "Deliberately NOT implemented driver-locally here") — and S7's engine backoff is unreachable anyway (new STAB-21), so a dead PLC still pays a full `_options.Timeout` connect attempt per read/write batch + probe tick. |
| STAB-9 | `PollGroupEngine` `onError` sink dead — no driver passes it | **CLOSED** (`9213c037`/`b494d09d`) — all seven poll consumers pass `onError: HandlePollError` routing to health + logger (Modbus `ModbusDriver.cs:158+`, S7 `S7Driver.cs:67-79`, AbCip `AbCipDriver.cs:158+`, AbLegacy `AbLegacyDriver.cs:75+`, TwinCAT `TwinCATDriver.cs:77-81`, FOCAS `FocasDriver.cs:118-122`, Sql `SqlDriver.cs:227-232`), plus `backoffCap` and the `onOverrun` meter closure. The parameter remains optional in the engine (`PollGroupEngine.cs:129`) but has no bare consumer left. |
| STAB-10 | AbLegacy never evicts failed tag handles | **CLOSED** (`a5a0f96d`) — `EvictRuntime` on non-zero status and transport exceptions on both read (`AbLegacyDriver.cs:315-316, :340-341`) and write (`:417-418, :442-443`) paths, mirroring AbCip (`:787-792`). |
| STAB-11 | RMW locks don't cover direct parent writes; AbCip DINT / TwinCAT 4-byte assumptions | **STILL OPEN, all parts** — AbCip: bit-RMW takes `GetRmwLock(parentName)` (`AbCipDriver.cs:1054`) but a direct write to the parent tag goes through `GetRuntimeLock(def.Name)` only (`:960`) — different lock dictionaries, no mutual exclusion → lost update; RMW is still BOOL-within-**DINT** only (`:942-944, :1043-1044`). TwinCAT: RMW still reads/writes the parent as 4-byte `UDInt` (`TwinCATDriver.cs:341-359`; `AdsTwinCATClient.cs:102` admits the width assumption) — a 4-byte write-back to a 2-byte WORD parent is not harmless — and only the `Bool`+`BitIndex` branch takes `_bitRmwLocks` (`:333-368`), direct parent writes bypass it (`:370-373`). |
| STAB-12 | Blocking/uncancellable teardown paths | **PARTIAL** — the TwinCAT probe-recycle compounding is **CLOSED** (`502a327f`): `RecycleClientAsync` waits on `ConnectGate` with the probe token (`TwinCATDriver.cs:1049-1052`). Still open: FOCAS's sync `Dispose()` close-PDU exchange on a `NetworkStream` with **no** timeout and no token (`Wire/FocasWireClient.cs:156-182`, `SendPdu`+`ReadPdu` at `:168-169`; zero `ReadTimeout`/`WriteTimeout` sets in the file) — a wedged CNC blocks Dispose indefinitely while holding `_lifetimeGate`; and TwinCAT's blocking SDK `Connect` ignoring token+timeout (`AdsTwinCATClient.cs:73-80`, self-documented as "the un-fixed root, carried" at `TwinCATDriver.cs:1050-1051`). |
| STAB-13 | (Positive) write-outcome surfacing universal; OpcUaClient reconnect strongest | **STILL HOLDS** — OpcUaClient per-item verbatim passthrough + `BadTimeout` "outcome unknown" on post-dispatch cancellation (`OpcUaClientDriver.cs:813-839`); reconnect machine intact (`:1997-2133`). The four new drivers all return per-item `WriteResult`s with named constants visible to `StatusCodeParityTests` (Sql is structurally read-only — `SqlDriver.cs:17-20`). But see STAB-22 (S7 write-health ordering) and STAB-26 (MQTT QoS-0 optimism). |
| STAB-14 | S7 connect-timeout OCE kills subscription polls (regression in Crit-3 fix) | **CLOSED** (R2-01 + PR #453) — connect timeout surfaces as `TimeoutException` at both connect sites (`S7Driver.cs:246, :1933-1942`); read/write ensure-wrappers rethrow OCE only on the caller's token (`:565, :1707`); the poll loop is now the shared engine whose OCE catches filter on the loop's own token (`PollGroupEngine.cs:266, :323` — the "STAB-14 engine guard" comment). The read-leg sibling: `S7OperationDeadline.RunAsync` wall-clocks **every** data-plane wire op — string/block/multi-var read, string/block write, probe (`IS7Plc.cs:142-177`) — via `WaitAsync` so control returns even when S7.Net ignores the token (`S7OperationDeadline.cs:48-58`). |
| STAB-15 | S7 fatal classification misses framing/desync + cancel-mid-PDU; probe never marks dead | **CLOSED** — `IsS7ConnectionFatal` (`S7Driver.cs:1994-2017`) classifies `TimeoutException`, `TPKTInvalidException`/`TPDUInvalidException`/`WrongNumberOfBytesException`, `PlcException{ConnectionError, WrongNumberReceivedBytes}` fatal, walks inners, and deliberately excludes `InvalidDataException`; mid-PDU cancellation marks `_plcDead` unconditionally at all four wire paths (`:652-663, :925-931, :1044-1050, :1750-1758`); the probe classifies + marks dead **under `_gate`** (`:2167-2180`). |
| STAB-16 | TwinCAT replay failure silent + never retried | **CLOSED** (`a06515ae`+`de297596`) — a failed intent is marked dead, publishes a Bad snapshot (`BadCommunicationError` via `OnUnavailable`, `TwinCATDriver.cs:962-970, :534-536`), degrades health, and is retried on the next successful probe tick (`RetryDeadRegistrationsAsync`, `:730, :989-1037`). Pinned by `TwinCATReconnectReplayTests`. Residual (info): the retry rides the probe loop, so `Probe.Enabled=false` silently disables STAB-16 recovery; default is enabled (`TwinCATDriverFactoryExtensions.cs:68`). |
| STAB-17 | Unsubscribe racing replay leaks a live ADS notification | **CLOSED** (`082ee99b`) — both replay sites re-check ownership after `SwapHandle` and retract an ownerless fresh handle (`TwinCATDriver.cs:947-952, :1008-1014`); handle transfer is `Interlocked.Exchange` (`:679-697`). All interleavings traced to exactly-once disposal; pinned by `UnsubscribeDuringReplay_DisposesFreshHandle_NoOrphan`. |
| PERF-1 | Five of seven drivers read one tag per wire round-trip | **PARTIAL** — **S7 closed** (span-grouped block reads, one PDU per contiguous block, `S7ReadSpanPlanner` + `ReadSpanAsync` `S7Driver.cs:608-619, :1037-1042`, on by default with `-1` opt-out validated at parse time; leftovers batch through multi-var PDUs chunked at 12 with a safe whole-chunk-falls-to-per-tag fallback `:932-938`); **AbCip improved** (bounded-parallel reads, `MaxConcurrentReads` default 8, `:643-645`) though still one CIP round-trip per tag; the engine gained a per-cycle batch callback consumed by Modbus/S7/AbCip/FOCAS (`IBatchSubscribable`). Still per-tag: **TwinCAT** (no ADS sum-read — sole occurrence is a doc citation, `AdsTwinCATClient.cs:116`), **FOCAS** (single-flight socket, `pmc_rdpmcrng` still fetches one value's width, `Wire/WireFocasClient.cs:302-317`), **AbLegacy** (no span coalescing). |
| PERF-2 | AbCip whole-UDT read exists in two never-joined halves | **STILL OPEN** — the planner still relies on declaration-order offsets (`AbCipUdtReadPlanner.cs:27`), the fast path is still opt-in-and-dangerous (`AbCipDriverOptions.cs:72-79`), and the Template-Object true-offset cache still feeds discovery only. |
| PERF-3 | S7 forked poll loop diffs arrays by reference | **CLOSED** — the fork is deleted (`85ef74ea`); the shared engine compares arrays structurally (`PollGroupEngine.cs:425-431`). |
| PERF-4 | OpcUaClient serializes all traffic on one global gate | **STILL OPEN** — `_gate = new SemaphoreSlim(1,1)` (`OpcUaClientDriver.cs:120`) taken by every wire path (reads `:685`, writes `:773`, discovery `:907` — held across the *entire* recursive browse —, subs `:1254`, alarms `:1446-1520`, HistoryRead `:1724`, events `:1896`). |
| PERF-5 | OpcUaClient discovery enrichment un-chunked Read + silent degrade | **STILL OPEN** — `pending.Count * 4` ReadValueIds in one call (`:1097-1109`); the wholesale catch registers everything Int32/ViewOnly with **no log line** (`:1117-1125, :1162-1172`); the ":932 the SDK chunks automatically" comment remains unsubstantiated. |
| PERF-6 | Per-tick allocation churn (TwinCAT symbol re-parse) | **STILL OPEN** — `TwinCATSymbolPath.TryParse` per hot call (`TwinCATDriver.cs:264, :328, :520`; allocations in `TwinCATSymbolPath.cs:21-96`); FOCAS's `_parsedAddressesByTagName` fix never propagated. |
| PERF-7 | Deadband only in Modbus | **STILL OPEN** — publish-suppression deadband remains Modbus-only (`ShouldPublish`, honoured on the batch path too — `_cycleBatchItems` buffers only what `ShouldPublish` passed, `ModbusDriver.cs:158-177`); MQTT re-implements unchanged-value suppression locally for Plain mode; the engine itself has none. |
| CONV-1 | S7 forked the poll loop; fork diverged both ways | **CLOSED** (`85ef74ea`) — the fork is deleted; S7 is a normal `PollGroupEngine` consumer (`S7Driver.cs:67-79`); the engine absorbed the fork's backoff + failure-health (via `onError`) and kept the structural diff + drain-before-dispose it always had. (But see STAB-21: S7's absorbed backoff is unreachable.) |
| CONV-2 | Three config-parse strictness tiers; silent enum defaulting ×6 | **CLOSED** (R2-11 + #457 + the #549/#551/#556/#559 authoring chain) — the six copy-pasted `ReadEnum`s are replaced by shared `TagConfigJson.TryReadEnumStrict` (present-but-invalid ⇒ reject ⇒ `BadNodeIdUnknown`); the four new drivers use the strict readers from day one (e.g. `SqlEquipmentTagParser.cs:49-50`); the Modbus probe parses the factory DTO shape incl. transport mode (`ModbusDriverProbe.cs:33-63`); Sql/Mqtt/MTConnect probes document DTO parity (`SqlDriverProbe.cs:12-16`). Residual: MTConnect's probe JSON options are *stricter* than its factory's (new CONV-9). |
| CONV-3 | Four factories take no `ILoggerFactory` → NullLogger in production | **STILL OPEN — same four** — `S7DriverFactoryExtensions.cs:20`, `TwinCATDriverFactoryExtensions.cs:19`, `AbCipDriverFactoryExtensions.cs:21`, `FocasDriverFactoryExtensions.cs:37` all take `(DriverFactoryRegistry)` only; `DriverFactoryBootstrap.cs:171-188` calls them bare while the other **eight** get `loggerFactory`. Costlier every round: S7's reconnect/span logs, TwinCAT's replay-retry warnings, FOCAS's capability-gate + skipped-tag warnings all run blind in production, and FOCAS's `BuildClientFactory` uses the no-logger `WireFocasClientFactory` ctor even though a logger-taking ctor exists precisely because "the previous no-arg factory path discarded them" (`FocasDriverFactoryExtensions.cs:141`, `WireFocasClient.cs:409-414`). |
| CONV-4 | `ResolveHost` mis-keys equipment-tag refs in every multi-device driver | **CLOSED** (`9262dd25`+`e69d3b3b`) — all resolve through `EquipmentTagRefResolver` to the parsed def's host: Modbus per-unit (`ModbusDriver.cs:226-235`, `{host}:{port}/unit{n}`; equipment tags now carry `unitId`), AbCip (`AbCipDriver.cs:604-610`), AbLegacy (`AbLegacyDriver.cs:621-626`), TwinCAT/FOCAS (same commit, resolver-backed). Per-host breaker isolation is real for equipment tags now. |
| CONV-5 | Health-field publication idioms drift | **PARTIAL, still drifting** — conforming: Modbus (`ModbusDriver.cs:433-438`), Mqtt (`MqttDriver.cs:1486-1489`), MTConnect (`MTConnectDriver.cs:3205-3208`), FOCAS (converted — `FocasDriver.cs:157, :183` + `Volatile.Read` in `GetHealth`), AbLegacy (`volatile`, `:40-45`), and **Sql sets the new high bar** with a CAS retry loop that a lost-update race motivated (`SqlDriver.cs:836-845`, Driver.Sql-010). Still plain fields: S7 (`S7Driver.cs:181`), AbCip (`AbCipDriver.cs:113`), TwinCAT (`TwinCATDriver.cs:52`), OpcUaClient (`OpcUaClientDriver.cs:147`). |
| CONV-6 | OpcUaClient.Contracts drags the OPC UA SDK | **CLOSED** (`b4a03b4b`) — `NamespaceMap` moved to the new `Driver.OpcUaClient.Session` leaf which carries the sole SDK ref; Contracts references only Core.Abstractions, pinned by `ContractsIsDependencyLightTests`. |
| CONV-7 | CLI harness divergences | **STILL OPEN** — six harnesses unchanged: `ParseValue` copy-pasted ×6 (`*/Commands/WriteCommand.cs`), AbLegacy still validation-free, AbCip's `Timeout` init-setter still throws (`AbCipCommandBase.cs:44`). None of the four new drivers (nor OpcUaClient) has a CLI. |
| CONV-8 | Dead config knobs + stale scaffold docs; no options `Validate()` | **PARTIAL** — `DisableFC23` is still a no-op but now honestly documented "Reserved / no-op" (`ModbusDriverOptions.cs:91-97`); AbCip `ConnectionSize` doc now claims "Honoured by the driver layer" (`AbCipDriverOptions.cs:120-122`) — unverified this round; stale scaffold docs remain (`AbLegacyDriver.cs:12` "ship in PRs 2 and 3", `OpcUaClientDriver.cs:13` "PR 66 ships"). Options validation improved materially where it matters: the Sql factory validates every knob incl. the inverted-deadline gate (`SqlDriverFactoryExtensions.cs:236-278`), S7 validates span options at parse time, R2-02 clamps resilience knobs. |
| UNDER-1 | FOCAS advertises writes it cannot perform | **CLOSED (reshaped)** — discovery forces `ViewOnly` on every emitter (`FocasDriver.cs:692-702, :751, :771, :810`); the wire still refuses (`WireFocasClient.cs:71-73`) and `FIXED:` writes are refused pre-wire (`FocasDriver.cs:543-547`); deploy inspection warns on authored `writable:true` (`FocasTagDefinitionFactory.cs:250-251`). The internal write gate honours the key by design as the seam for a future writable backend — with the wire refusing, nothing misleads. |
| UNDER-2 | OpcUaClient `UnsMappingTable` mandatory-but-unconsumed | **STILL OPEN** — validated mandatory (`OpcUaClientDriver.cs:411, :420`), consumed nowhere (repo-wide grep: option + validator + tests only). |
| UNDER-3 | OpcUaClient alarm filter compares mismatched NodeId encodings | **STILL OPEN** — verbatim ordinal set of caller refs (`:1406`) vs session-relative `ns=N;…` rendering (`:1609-1610`); stored refs are `nsu=` (`:879`); production caller passes v3 refs (`DriverInstanceActor.cs:1146`); no `_namespaceMap` conversion on the path — any non-empty filter still drops every event. |
| UNDER-4 | S7 authored-array/write/UInt32 gaps | **PARTIAL** — `ArrayCount` **closed** (`S7DriverOptions.cs:178-185`, factory `S7TagDefinitionFactory.ReadArrayCount :255-269`, discovery surfaces `IsArray`/`ArrayDim` `S7Driver.cs:2059-2068`, single block-read array path `:1227-1244`). Array *writes* still unsupported but now loud (init guard `:463-469`; `NotSupportedException` → `BadNotSupported` `:1805-1808`). `UInt32 → Int32` still lossy, now documented (`:2077-2080`). |
| UNDER-5 | AbCip alarm-ack outcomes discarded | **STILL OPEN** — `_ = await _driver.WriteAsync(requests, …)` verbatim (`AbCipAlarmProjection.cs:150`); a failed ack is still invisible to operator/health/Part 9 caller. The discovery residuals also persist: with `EnableControllerBrowse` on, the multi-device `await foreach` has no per-device try/catch (`AbCipDriver.cs:1265+` — one unreachable PLC faults the whole `DiscoverAsync`). The #468/#539/#534 chain did land (controller-browse gate unblocked, authored EtherNet/IP port honoured — `BuildCreateParams` uses `ParsedAddress.Port`, `AbCipDriver.cs:1617`). |
| UNDER-6 | Equipment-tag parsers lag the authored-tag feature set | **CLOSED** — R2-11 gave all six incumbents shared readers + the `writable` key (FOCAS forced read-only, see UNDER-1) + `Inspect()` warnings; FOCAS equipment tags run the capability-matrix pre-flight (`FocasDriver.cs:251-258`); the #549/#551 chain made authoring never accept what the runtime rejects, service-enforced. The four new drivers shipped with parser/authoring parity from the start. |
| UNDER-7 | Live-risk assumptions documented but ungated | **PARTIAL** — FOCAS servo-load scaling and timer endianness are now **live-verified** ("Validated against a live 31i-B 2026-06-25", `WireFocasClient.cs:934-941, :917-924`). Still unverified: TwinCAT array read shape (`AdsTwinCATClient.cs:113-116`), Flat-mode `SubSymbols` (`:270-276`, gated only by `EnableControllerBrowse` defaulting false), FOCAS `cnc_getfigure` (`WireFocasClient.cs:391-395`, soft-degrades), AbLegacy array-decode assumptions, and the TwinCAT replay path (still fake-client-only — no TC3 fixture). |
| UNDER-8 | Test coverage codec-heavy, failure-path-light | **SUBSTANTIALLY IMPROVED** — the four new drivers arrive with the best failure-path coverage in the subsystem (MQTT ~541 tests/27 files + 5 live-integration suites + a project-owned Sparkplug simulator; MTConnect ~408 tests incl. deterministic teardown/backoff/blocked-subscriber suites + a self-skipping cppagent integration; Sql ~263+54 unit + 3-dialect docker integration incl. a blackhole-timeout suite; Calculation 44). S7 gained deadline/migration/span-parity/live-outage suites. Remaining gaps: still **zero AbLegacy reconnect tests** (STAB-6 lives there), no S7/AbCip concurrency suites, no test pins S7's write-health ordering (STAB-22) or backoff engagement (STAB-21), no DTD-hardening test for MTConnect's probe parser (UNDER-11), and the Sql fixtures cover only text key columns / unbound topByTimestamp on Postgres (the STAB-24 blind spot). |
| UNDER-9 | OpcUaClient 2,154-line monolith; PKCS#12-only identity | **STILL OPEN, one leg worse** — 2,230 lines now; `TransferSubscriptionsOnReconnect` is still never set (SDK default `false`) while the `OnReconnectComplete` doc-comment (`:2020-2022`) now affirmatively claims it defaults `true` — the reconnect path does not do what the driver believes; `BuildCertificateIdentity` still loads PKCS#12 only (`:559-560`) while its own comment promises a PEM fallback that does not exist (`:556-558`). |
---
## Architecture overview — what changed since round 2
**PollGroupEngine v2** (`src/Core/ZB.MOM.WW.OtOpcUa.Core.Abstractions/PollGroupEngine.cs`,
484 lines) is the round's structural win: fixed-**rate** pacing with an overrun counter +
`onOverrun` sink (`:37-56, :351-358`), capped-exponential failure backoff via
`ConnectionBackoff` on the failure branch only (`:287-295`), the teardown-token-filtered
OCE catches that make the S7 fork retirement safe (`:262-266, :321-323`), an optional
per-cycle `onBatch` callback (raised once, after all per-tag callbacks, never empty,
`:415-416`), a non-blocking `UnsubscribeAsync` that drains before disposing (`:191-239`),
and structural array comparison (`:425-431`). Seven drivers consume it uniformly with
`onError` + `backoffCap: 30s` + a meter-wired `onOverrun`.
**The four new drivers** are, on conventions, the best code in the subsystem — each has a
single config-parse authority shared by factory/probe/driver, strict enum reads, a
Contracts-side `Inspect()` wired into the deploy gate, named status constants covered by
the reflection `StatusCodeParityTests` (`tests/Core/ZB.MOM.WW.OtOpcUa.Core.Abstractions.Tests/StatusCodeParityTests.cs` —
scans every `Driver.*` dll; note its own warning that inline literals are invisible to it),
`ISkippedTagReporter` (now implemented by **all twelve** drivers, #541), and health
surfaces designed around the #527 comms-loss watchdog's conjunction (Sql's
`IsAnswerEvidence` classification, `SqlDriver.cs:743-749`, is the most carefully reasoned
`LastSuccessfulRead` semantics in the fleet). The Sql injection boundary is genuinely
airtight in design: identifiers reach SQL text only through `ISqlDialect.QuoteIdentifier`
(control/format-char rejection incl. the Trojan-Source class, `SqlServerDialect.cs:129-155`)
*after* the §8.1 catalog gate has rewritten them to catalog spellings
(`SqlDriver.cs:953-996` — polls resolve only against the validated table, `:319`), and all
values are bound parameters (`SqlGroupPlanner.cs:17-26`).
### Per-driver conformance matrix (updated)
| Aspect | Modbus | S7 | AbCip | AbLegacy | TwinCAT | FOCAS | OpcUaClient | Mqtt | MTConnect | Sql | Calculation |
|---|---|---|---|---|---|---|---|---|---|---|---|
| Subscription model | PollGroupEngine | PollGroupEngine (**fork deleted**) | PollGroupEngine | PollGroupEngine | native ADS + engine fallback | PollGroupEngine | MonitoredItems | **broker push** | **/sample stream pump** | PollGroupEngine | dependency-mux push |
| onError→health / backoffCap | yes/yes | yes/yes (but see STAB-21) | yes/yes | yes/yes | yes/yes | yes/yes | n/a | n/a | n/a | yes/yes | n/a |
| Batch subscribe (`IBatchSubscribable`) | yes | yes | yes | no | no | yes | no | no | no | no | no |
| Connect-attempt throttle | transport backoff | **no (STAB-8 residual)** | ConnectionBackoff | evict-parity only | ConnectionBackoff | ConnectionBackoff | SessionReconnectHandler | bounded reconnect loop | bounded backoff | n/a (per-poll open) | n/a |
| Config re-parse on Initialize (#516) | yes | yes | yes | yes | **empty-config quirk** | yes | yes | yes | yes | yes (all-or-nothing) | fallback bug (STAB-28) |
| Factory `Register` takes `ILoggerFactory` | yes | **no** | **no** | yes | **no** | **no** | yes | yes | yes | yes | yes |
| Health idiom | Volatile | **plain** | **plain** | volatile | **plain** | Volatile | **plain** | Volatile | Volatile | **CAS loop (best)** | derived |
| Writes | per-item + RMW | per-item (health ordering: STAB-22) | per-item + RMW | per-item + RMW | per-item + RMW | refused at wire | verbatim passthrough | QoS-0 publish (STAB-26) | HTTP PUT, double-gated | **structurally read-only** | n/a |
| `ISkippedTagReporter` | yes | yes | yes | yes | yes | yes | yes | yes | yes | yes (two-stage union) | yes |
| CLI harness | yes | yes | yes | yes | yes | yes | no | no | no | no | no |
---
## Findings
Severity scale unchanged: **Critical** = live data-loss/unavailability in a realistic
field scenario; **High** = correctness or stability defect likely to bite; **Medium** =
architectural debt / divergence with concrete failure modes; **Low** = hygiene.
New IDs continue the existing numbering (STAB-18+, PERF-8+, CONV-9+, UNDER-10+).
### 1. Stability
**STAB-18 — High — NEW — MQTT has no initial-push analogue of the poll engine's
`forceRaise`, so a ref latched Bad recovers only when the plant value changes.**
`DriverHostActor.FanCommsLossToDependencyMux` forces `BadNoCommunication` into the mux for
every ref of a disconnected driver and documents its recovery contract as riding "a fresh
subscription whose PollGroupEngine initial push runs with `forceRaise: true`"
(`DriverHostActor.cs:1310-1318`). MQTT has no poll engine: `MqttSubscriptionManager.SubscribeAsync`
(`MqttSubscriptionManager.cs:325-365`) and `SparkplugIngestor.SubscribeAsync`
(`SparkplugIngestor.cs:470-506`) record handles and push nothing, nothing in production
calls `IReadable.ReadAsync`, and Plain-mode delivery then actively suppresses the one
message that would recover the ref — `Deliver` skips `Raise` when value+status match the
driver-owned last-value cache (`MqttSubscriptionManager.cs:762-767`), which survives
reconnects and redeploys by design. Concrete shapes: (a) after a #527 watchdog reconnect,
the retained-seed replay carries the identical value → suppressed → scripted-alarm /
virtual-tag inputs latched Bad by the #481 class never recover; (b) after a full
address-space rebuild, nodes reseed `BadWaitingForInitialData` and an unchanged republish
never re-raises — the exact "prod-inert after redeploy → Bad forever" class the v3 Batch 4
live gate already caught once at the host layer. Sparkplug shares shape (b) for quiet
metrics (a rebuild triggers no rebirth). *Recommendation:* on (re)subscribe, republish the
cached snapshots for the subscription's refs (the push-model `forceRaise`), or clear
suppression memory per re-subscribe.
**STAB-19 — High — NEW — Calculation launders dependency quality to Good, defeating the
system's own comms-loss fan-out.** `CalculationDriver.OnDependencyValue` never reads its
`statusCode` parameter (`CalculationDriver.cs:330-352`), and the feeding seam hardcodes
`statusCode: 0u` behind a comment — "Quality is stripped at the mux boundary" — that is
factually wrong (`DependencyConsumerMuxAdapter.cs:71-72`): `DependencyValueChanged` has
carried `StatusCode` since #478/#519 and `DependencyMuxActor` forwards it
(`DependencyMuxActor.cs:114, :150`). `DriverHostActor.FanCommsLossToDependencyMux`
(`DriverHostActor.cs:1334-1359`) deliberately pushes `BadNoCommunication` + null value so
dependents see comms loss — a calc tag receives that as an *arrived, Good, null*:
(a) the warm-up gate is defeated (`_arrivedDeps.Add` at `:336` fires for a value that
never arrived); (b) the common `(double)ctx.GetTag("x").Value` idiom NREs on the null →
a spurious "script threw" storm — the exact noise class the `a836e0d9` warm-up gate was
built to eliminate; (c) a null-tolerant script publishes a **Good** output computed from a
dead input, and a slow-moving input that dies leaves the calc output stale-Good
indefinitely. `CalculationEvaluator.BuildReadCache` (`:181-187`) additionally stamps every
dep Good with eval-time timestamps. *Recommendation:* thread the real status through the
adapter, hold the warm-up gate open for Bad arrivals, and degrade the calc output quality
when an input is Bad.
**STAB-20 — Medium — NEW — MTConnect: a Subscribe racing a lifecycle rebuild can orphan
the /sample pump on a disposed client, permanently.** `SubscribeAsync` deliberately runs
outside `_lifecycle` and starts the pump under `_subscriptionLock`
(`MTConnectDriver.cs:1043-1049`); the rebuild path runs stop-pump → `TeardownCoreAsync`
(disposes the client) → `StartCoreAsync` (`:551-555, :599-607`), and the actor invokes
initialize on a fire-and-forget task (the driver's own #517 comment, `:2741-2743`) — so a
Subscribe can land between stop and teardown, bind the old client, and then
`StartCoreAsync`'s start is a no-op because a live pump exists (`:1809`
`if (_pumpTask is { IsCompleted: false }) return;`). Every `SampleAsync` on the disposed
client throws ODE → classified Transient → the stray pump reconnect-loops at max backoff
against a dead object forever; reads keep succeeding (advancing `LastSuccessfulRead`), so
the watchdog never trips and nothing self-heals until the next lifecycle call.
*Recommendation:* generation-stamp the pump with its `AgentSession` and let
`StartCoreAsync` supersede a pump from an older session.
**STAB-21 — Medium — NEW — S7's poll-failure backoff is unreachable: the engine backs off
only when the reader throws, and S7's reader never throws for device faults.**
`consecutiveFailures` increments only in the engine's catch (`PollGroupEngine.cs:287-289,
:324-329`); `S7Driver.ReadAsync` by design returns a fully-degraded batch on a failed
(re)connect (`S7Driver.cs:566-571`) and absorbs every per-tag/span/multi-var fault into
result stamps — its only throws are caller-cancellation OCE. With the PLC down, backoff
never engages and each cycle immediately follows the previous one after a full
`_options.Timeout` (default 5 s) connect attempt, per subscription, plus the probe every
5 s, all serialized on `_gate` — this is what makes the STAB-8 S7 residual bite. The ctor
comment (`S7Driver.cs:63-66`) claiming the migration brought backoff to S7 overstates what
is reachable, and `SustainedPollFailure_DegradesHealth` never exercises the branch.
*Recommendation:* wire `ConnectionBackoff.ShouldAttempt/RecordFailure/RecordSuccess` into
`EnsureConnectedAsync` under `_gate` (the FOCAS/TwinCAT/AbCip shape) — exactly where the
code comment already says it belongs.
**STAB-22 — Medium — NEW — S7 write-path health is per-item last-writer-wins, and the next
read pass erases a write-side Faulted.** `WriteAsync` stamps `_health` inside each item's
catch (`S7Driver.cs:1770-1772` Faulted PUT/GET-denied, `:1782, :1791` Degraded) with no
outcome accumulator — item 2's transport Degraded overwrites item 1's operator-actionable
Faulted in the same batch, the exact ordering bug the read pass was refactored to kill
(`ReadPassOutcome`, `:703-711`, worst-state-wins with rank Healthy<Degraded<Faulted
`:783-788`). Worse, the next successful read pass writes Healthy unconditionally
(`:686-692`), so a write-only PUT/GET denial (readable CPU, write-protected) is erased
within one poll interval. The read-pass fix's own rationale applies verbatim to writes,
unaddressed, and no test pins the ordering.
**STAB-23 — Medium — NEW — FOCAS `ShutdownAsync` never joins its three fire-and-forget
loops: narrow two-socket leak + generation overlap on Reinitialize.** `InitializeAsync`
starts probe / recycle / fixed-tree loops as `_ = Task.Run(...)` (`FocasDriver.cs:280,
:290, :308`) and `ShutdownAsync` (`:330-362`) only cancels + disposes the CTSes before
`state.DisposeClient()` and `_devices.Clear()`. A loop past its last cancellation
checkpoint can re-enter `EnsureConnectedAsync`, find the just-disposed client, and connect
a fresh `SynchronizedFocasClient` (two TCP sockets) that nothing ever disposes; after
`ReinitializeAsync` the stale-generation loop can briefly run alongside the new
generation's against the same CNC. TwinCAT closed exactly this hole by retaining and
awaiting `ProbeTask` (`TwinCATDriver.cs:167-168, :201-214`). Same fix, three loops.
**STAB-24 — Medium — NEW — Sql: text-bound parameters break numeric key/where columns on
Postgres, and the fixture cannot show it.** Both value-bearing fields are captured as text
(`SqlEquipmentTagParser.ReadScalar`, `SqlEquipmentTagParser.cs:130-138`) and bound as CLR
strings (`SqlPollReader.cs:401-408`); the reader's own comment asserts "the provider
coerces on the way in" (`:533-535`) — true for SqlClient (implicit conversion) and ODP.NET
(VARCHAR2→NUMBER), **false for Npgsql**: Postgres does not implicitly cast text↔integer in
comparisons, so `WHERE station_id = $1(text)` / `keycol IN ($1..)` against an
`integer` column fails with *operator does not exist* → the whole group returns
`GroupResult.Failed` → every member publishes `BadCommunicationError` on every poll, with
health guidance pointing the operator at "the table/column, the grant" (`SqlDriver.cs:664-676`)
— the wrong system. The design explicitly intends numeric key columns ("an INTEGER station
id, say"). The Postgres integration fixture uses a `varchar` key column and only the
unbound `topByTimestamp` wide-row selector
(`tests/.../Sql.IntegrationTests/Docker/postgres/seed-pg.sql:56-72`,
`PostgresReadTests.cs:278-280`) — the house fixture-shaped-verification failure mode.
*Recommendation:* bind with a provider type inferred from the catalog column type (the
gate already reads it), or cast the parameter in the emitted SQL for the Postgres dialect;
add integer-key legs to the Postgres/Oracle fixtures.
**STAB-25 — Medium — NEW — MQTT Sparkplug writes encode with the authored/default data
type, never the birth-declared type.** The read path resolves
`def.DataTypeAuthored ? def.DataType : birthType` (`SparkplugIngestor.cs:1238`), but the
write path consults only `def.DataType` (`MqttWriteEncoder.cs:209`). A Sparkplug tag
authored without `dataType` — the supported shape `UntilStable` discovery exists for —
defaults to `String` (`MqttTagDefinitionFactory.cs:235`), so a write to a birth-declared
`Int32` metric goes out as `Datatype=String`/`StringValue="42"` — and the encoder's own
remarks (`MqttWriteEncoder.cs:241-246`) name a silently-dropped command as "the failure
mode this whole feature must not have". *Recommendation:* resolve the write datatype
through the birth binding the way `PublishMetric` does.
**STAB-26 — Medium — NEW — MQTT writes are QoS-0 fire-and-forget yet return Good.**
`MqttWriteEncoder.WriteQos = 0` (`MqttWriteEncoder.cs:77`) for Plain and NCMD/DCMD;
`WriteAsync` returns `Good` when `PublishAsync` completes (`MqttDriver.cs:731-733`) —
at QoS 0 that means "bytes reached the socket", so during a half-open TCP session the
write vanishes, the driver reports success, and the server's write-outcome
self-correction (#5) never reverts. The optimistic posture is documented
(`MqttDriver.cs:677-691`) and Sparkplug NCMD arguably wants QoS 0, but for Plain-mode
`writeTopic` publishes QoS 1 would make Good mean "broker accepted" at trivial cost — and
the QoS is a non-configurable constant.
**STAB-27 — Medium — NEW — MQTT Sparkplug primary-host claim retries at 1 Hz forever with
no backoff.** `SparkplugPrimaryHost.RoleSampleInterval` is 1 s (`SparkplugPrimaryHost.cs:67`);
a broker that accepts CONNECT but refuses the STATE publish (an ACL without
`spBv1.0/STATE/#` — the driver's own docs call this "the ordinary way this happens",
`MqttDriver.cs:1357-1359`) produces a 1 Hz connect/teardown loop plus one warning per tick
(`SparkplugPrimaryHost.cs:335-343`) — ~86k warnings/day, no escalation. The ingest
connection's supervisor has exponential backoff; the claim loop has none.
**STAB-28 — Medium — NEW — Calculation's malformed-reinit fallback reverts to the
construction-time tag set.** `_options` is `readonly`; `ParseOptions`'s fallback
(`CalculationDriver.cs:236`) returns `RawTags = _options.RawTags` under the comment
"keeping the current tag table" — but after one successful delta the ctor set is stale, so
a second, malformed delta actively rebuilds back to the *spawn-time* tags
(`RebuildTagTable`, `:286`), silently un-deploying every tag added since. Latent (the host
emits well-formed merged config), but the fallback exists exactly for the case it
mishandles.
**STAB-29 — Medium — NEW — Calculation's `_pending` queue is unbounded with no per-tag
coalescing.** Every dep arrival enqueues one `PendingEvaluation` (with its own snapshot
dictionary) per change-triggered dependent (`CalculationDriver.cs:344-349`), drained by a
single pump at worst one per `RunTimeout` (2 s default). A fast-ticking dependency feeding
a slow script grows memory and publish latency without bound and publishes stale results
in trigger order. No cap, no coalesce, no queue-depth diagnostic — the timer path has both
an in-flight skip and a `SkippedTickCount` metric (`CalculationTimerScheduler.cs:62-87`);
the change path has neither.
**STAB-30 — Low — NEW — MQTT lifecycle residuals.** (a) `ShutdownAsync`'s wedged-gate
fallback lacks the `_disposed`-flag defence `DisposeAsync` has (`MqttDriver.cs:385-416` vs
`:999-1003`) — a wedged initialize can complete after shutdown returns and publish a live
connection on a driver the host believes stopped (self-heals on the next lifecycle call).
(b) A failed `ConnectAsync` in `InitializeCoreAsync` abandons the never-published
`MqttConnection` undisposed (`:992` vs the disposing sibling paths `:1001, :1021-1025`).
(c) A later subscription's stronger QoS on an already-subscribed topic is silently
deferred to the next reconnect (`MqttSubscriptionManager.cs:361, :554-572`). (d) A
transient failure of the *initial* SUBSCRIBE degrades tags to `BadCommunicationError` with
no retry until the connection drops (`:311-316, :581-651` — deliberate for permanent ACL
refusals, but it also covers a broker hiccup; contrast Sparkplug, where a refused group
filter faults the initialize into the resilience retry loop).
**STAB-31 — Low — NEW — TwinCAT sync `Dispose` can dispose `ConnectGate` under a live
probe loop.** `Dispose()` waits at most 2 s for `ProbeTask` (`TwinCATDriver.cs:1104-1107`)
then unconditionally `DisposeGate()` (`:1111`); a probe wedged in the blocking SDK
`Connect` (STAB-12c) then throws `ObjectDisposedException` from its next
`ConnectGate.WaitAsync` (`:1052, :993`), which the loop shields only as OCE (`:739-740`) —
the ODE escapes as an unobserved task exception and the loop dies silently. `ShutdownAsync`
(unbounded await) is safe; only sync `Dispose` has the hole.
**STAB-32 — Low — NEW — FOCAS: sync-over-async `Dispose` and two plain shared
dictionaries.** `public void Dispose() => DisposeAsync().AsTask().GetAwaiter().GetResult();`
(`FocasDriver.cs:1478`) — the exact pattern TwinCAT's own comment forbids for the OPC UA
stack thread (`TwinCATDriver.cs:1081-1087`), compounded by STAB-12b's unbounded close-PDU.
And `_devices` / `_tagsByRawPath` are plain `Dictionary`s (`FocasDriver.cs:47, :50`) read
concurrently by data paths, `GetHostStatuses`, and the alarm scan while
`ShutdownAsync`/`InitializeAsync` clear/repopulate them — TwinCAT hardened the same two
fields to `ConcurrentDictionary` with an explicit rationale (`TwinCATDriver.cs:30-37`).
**STAB-33 — Low — NEW — S7 residuals from the fresh pass.** (a) `InitializeAsync`
overwrites `Plc` and `_probeCts`/`_probeTask` without disposing existing ones
(`S7Driver.cs:264, :286-291`) — currently safe because every production path tears down
first, but it violates the dispose-before-overwrite rule Modbus/MQTT now embody
(`ModbusDriver.cs:298-319`) and is one refactor from live. (b) The probe loop reports
`HostState.Stopped` on mere gate contention — an OCE from `_gate.WaitAsync` under the 2 s
probe deadline falls into the bare catch (`:2185-2187`) and flaps host state while a long
span read holds the gate. (c) `IsAccessDenied` classifies any `PlcException` whose message
chain contains "not allowed" as PUT/GET-denied → latched Faulted (`:2028-2039`) — the
broad arm widens the false-positive surface over the specific
"Accessing object not allowed" pattern.
**STAB-34 — Low — NEW — Calculation minor residuals.** One-stale-publish race across
reinit for surviving tags (state-existence guard only, `CalculationDriver.cs:524`);
`GetHealth` is Healthy whenever `_running` — a driver whose every evaluation fails stays
Healthy with only Bad quality + script logs as evidence (defensible per CLAUDE.md, but
there is no Degraded surface at all), and `_lastComputeUtc` (`DateTime?`, `:103`) is
written under `_lock` but read lock-free (`:319-321`); value dedup uses
`Equals(st.LastValue, value)` (`:551`) so array results republish every evaluation; the
deploy-time Tarjan gate is the sole cycle defence (no runtime damping).
**STAB-35 — Low — NEW — PollGroupEngine records a change as seen before delivering it, so
a throwing subscriber loses that change permanently — and only Modbus defends its
bridge.** `state.LastValues[tagRef] = current;` precedes `_onChange(...)`
(`PollGroupEngine.cs:404-411`); an `OnDataChange` subscriber that throws unwinds
`PollOnceAsync` mid-loop — the throwing tag's change is marked seen but never delivered
(no re-raise until the next value change), later tags in the cycle are skipped, and for
batch-wired drivers the cycle's `onBatch` never fires. Modbus wraps its bridge in
try/catch precisely for this (`ModbusDriver.cs:158-177`, with the cross-cycle-contamination
rationale); the other six consumers invoke `OnDataChange?.Invoke` unguarded.
### 2. Performance
*(PERF-1/2/4/5/6/7 verdicts in the table above; the substantive change is S7's span +
multi-var batching and AbCip's bounded-parallel reads.)*
**PERF-8 — Medium — NEW — MQTT's `MaxPayloadBytes` bounds decode work only, and the
Sparkplug path has no publish suppression.** `MqttClientOptionsFactory.BuildClientOptions`
(`:63-68`) never calls `WithMaximumPacketSize`, so a multi-MB retained blob is fully
received and buffered by MQTTnet before the handler's one-comparison refusal — and the
in-code remark still calls the cap "a constructor knob, not yet an operator-facing one"
(`MqttSubscriptionManager.cs:184-190`) when the options key has existed for some time,
hiding that only the protocol-layer half is missing. Separately, Sparkplug ingest bypasses
the Plain-mode unchanged-value suppression entirely (documented at `:759-761`), so every
rebirth re-fans full birth-value sets downstream.
### 3. Conventions
*(CONV-1/2/4/6 closed; CONV-3/7 open; CONV-5/8 partial — table above.)*
**CONV-9 — Low — NEW — MTConnect's probe parses a stricter JSON dialect than its
factory.** The probe's `JsonOptions` (`MTConnectDriverProbe.cs:96-101`) lack
`ReadCommentHandling.Skip`/`AllowTrailingCommas` that the driver's have
(`MTConnectDriver.cs:169-174`) — a config carrying a comment or trailing comma deploys
fine but Test Connect reports "Config JSON is invalid": the inverse of the documented
"reachable ≠ deployable" gap, and a violation of the probe-parity rule the fleet
otherwise now follows.
### 4. Underdeveloped areas
*(UNDER-1/6 closed; UNDER-2/3/5 open; UNDER-4/7/8/9 partial — table above.)*
**UNDER-10 — Medium — NEW — S7's deploy-time `Inspect` does not cover the init-time config
guards, so a clean-inspecting tag can fault the whole driver.**
`S7TagDefinitionFactory.Inspect` warns only for blobs `FromTagConfig` rejects
(`S7TagDefinitionFactory.cs:161-201`), but `FromTagConfig` accepts a `Float64`+`isArray`
blob, a non-byte-anchored wide scalar, a mis-typed Timer/Counter, and a writable array —
each of which then throws at driver init in `RejectUnsupportedTagConfigs`
(`S7Driver.cs:407-469`, guards a–e), faulting the entire instance and taking every other
tag on it to Bad — contradicting the mapper's own "one bad tag must not fail the whole
driver init" philosophy three lines up (`:204-205`). This is the authoring-vs-deploy-gate
drift class the repo has closed elsewhere (#535→#559), reopened for exactly the blobs with
the worst blast radius.
**UNDER-11 — Low — NEW — MTConnect deferred/ungated edges.** DTD hardening is real in the
streams parser (`DtdProcessing.Prohibit`, `MTConnectStreamsParser.cs:131-138`) but the
probe parser inherits it only via `XDocument` defaults and **no test feeds an
entity-expansion document** — a refactor onto a permissive `XmlReader` passes every test.
A credentialed `AgentUri` is carefully redacted but non-functional (`HttpClient` never
converts URI userinfo to an Authorization header) and there are no TLS trust knobs. No
host-resolution seam: default `SocketsHttpHandler` with infinite
`PooledConnectionLifetime` means a DNS-repointed agent name is re-resolved only when a
connection drops — a healthy long-lived `/sample` stream to a stale IP persists
indefinitely. And an authorable `AccessLevel=ReadWrite` tag on a write-disabled instance
advertises writable and honestly fails (`BadNotWritable` + revert) with no deploy-gate
warning. An Agent write *refusal* (401/403) and unreachability also share
`BadCommunicationError` (`MTConnectDriver.cs:86-89, :787-789`) where
`BadUserAccessDenied` would tell the operator over the wire.
**UNDER-12 — Low — NEW — Every valid MQTT Sparkplug tag materializes writable.**
Sparkplug `CanWrite` is "binding tuple complete" (`MqttDriver.cs:648-650`), which every
mapped tag satisfies, so read-only sensor metrics all advertise
`SecurityClassification.Operate`. Defensible under Sparkplug command semantics and gated
server-side by `WriteOperate`/ACLs — but Plain mode has a per-tag opt-in (`writeTopic`
absent ⇒ ViewOnly) and Sparkplug has no equivalent opt-out.
---
## Maturity ratings
| Dimension | Rating (1-5) | Prior | Justification |
|---|---|---|---|
| Stability | **3.5** | 3 | Every carried High from rounds 1–2 is now verifiably closed in code — STAB-3/4/5/14/15 (the desync/locking/classification class), STAB-16/17, STAB-9/10, most of 7/8/12 — with tests that pin the fixes, and the comms-loss-watchdog driver legs (Modbus/MQTT dispose-before-overwrite, honest `LastSuccessfulRead` semantics) landed. Held below 4 because the two new push drivers each ship one High of the classic house type (STAB-18 MQTT no-initial-push recovery gap; STAB-19 Calculation quality laundering — both "the signal exists end-to-end and is discarded at the last seam"), the AbLegacy shutdown race and STAB-11 RMW class persist untouched, and S7's backoff is dead code (STAB-21). |
| Performance | **3** | 2 | Real batching finally landed where it was cheapest and hottest: S7 span-grouped block reads + multi-var leftovers (on by default, live-gated), AbCip bounded-parallel reads, engine-level per-cycle batch fan-out consumed by four drivers, fixed-rate pacing with an overrun meter. Still open: TwinCAT sum-read / FOCAS PMC ranges / AbLegacy spans (per-tag on serialized links), the AbCip UDT planner⇄template join, the OpcUaClient global gate + un-chunked enrichment, TwinCAT per-call symbol re-parse. |
| Conventions | **4** | 3 | The template is now enforced rather than aspirational: one config-parse authority per driver (probe parity), strict enum parsing fleet-wide (#457), Contracts-side `Inspect()` deploy gates, reflection-guarded status constants (#497/#519), `ISkippedTagReporter` ×12, `DriverTypeNames` keying, and the four new drivers are exemplary citizens (MQTT and MTConnect arguably now define the template). Docked for the unchanged CONV-3 logger asymmetry (S7/TwinCAT/AbCip/FOCAS still run blind in production — more expensive every round), the four-way health-idiom drift, the CLI divergence, and CONV-9/UNDER-10 gate-drift residuals. |
| Underdeveloped areas | **3.5** | 3 | UNDER-1 and UNDER-6 closed properly (forced-ViewOnly discovery + capability pre-flight + authoring parity), FOCAS's riskiest scalings live-verified, and the new drivers' deferrals are declared-and-loud rather than silent (MTConnect DATA_SET→`BadNotSupported`, Sql's reserved providers failing at construction with a naming message). Still carried: `UnsMappingTable` (advertised feature that does not exist), the OpcUaClient alarm-filter encoding mismatch, AbCip ack-outcome discard, the unverified-against-hardware TwinCAT set, AbLegacy's zero reconnect tests — and the OpcUaClient reconnect comment now actively misstates `TransferSubscriptionsOnReconnect`'s default. |
---
## Recommended remediation order
1. **STAB-18 + STAB-19 together — the "signal discarded at the last seam" pair.** MQTT
needs a re-subscribe initial push (or suppression reset); Calculation needs the real
`statusCode` threaded through `DependencyConsumerMuxAdapter` and honoured. Both defeat
the host's comms-loss fan-out contract that the rest of the system relies on, and both
are invisible to unit tests that never drive the reconnect/rebuild path.
2. **STAB-21 + STAB-8(S7) — wire `ConnectionBackoff` into `EnsureConnectedAsync`** (the
comment already names the seam) so S7 stops paying a 5 s connect per batch against a
dead PLC and the engine's backoff branch becomes reachable; add the missing
backoff-engagement test.
3. **STAB-24 — Sql Postgres typed-parameter binding** + integer-key fixture legs; this is
a wrong-guidance correctness bug on a shipped dialect, currently masked by the fixture.
4. **STAB-22 — S7 write-pass `ReadPassOutcome` sibling** (worst-state-wins accumulator on
`WriteAsync`, and stop the read pass erasing write-side Faulted).
5. **STAB-20 — MTConnect pump generation stamp**; STAB-23 — FOCAS loop joins (port
TwinCAT's retained-task shape); STAB-6 — the same fix finally applied to AbLegacy's
probe loop.
6. **CONV-3 — one line per factory** (S7/TwinCAT/AbCip/FOCAS `Register(registry,
loggerFactory)`): now a prerequisite for *four* recovery mechanisms being observable in
production at all.
7. **STAB-25/26/27 — MQTT write honesty + claim backoff**; UNDER-10 — S7 Inspect/init-guard
parity (the #535→#559 arc's method applies directly).
8. **STAB-11 — RMW lock unification** (route direct parent writes through the RMW lock;
width-aware TwinCAT RMW) — unchanged three rounds running; either fix it or demote it
to a documented limitation with a deploy-gate warning.
9. Sweep the carried one-liners: UNDER-2 delete the `UnsMappingTable` gate, UNDER-3
alarm-filter encoding, UNDER-5 ack outcomes + per-device browse fault isolation,
PERF-5 chunk+log, UNDER-9 fix the two misleading comments (TransferSubscriptions, PEM),
STAB-7 TwinCAT empty-config quirk, CONV-9 probe JSON parity.