New exception_injector.py — standalone pure-Python-stdlib Modbus/TCP server shipped alongside the pymodbus image. Speaks the wire protocol directly (MBAP header parse + FC 01/02/03/04/05/06/15/16 dispatch + store-backed happy-path reads/writes + spec-enforced length caps) and looks up each (fc, starting-address) against a rules list loaded from JSON; a matching rule makes the server respond [fc|0x80, exception_code] instead of the normal response. Zero runtime dependencies outside the stdlib — the Dockerfile just COPY's the script into /fixtures/ alongside the pymodbus profile JSONs, no new pip install needed. ~200 lines. New exception_injection.json profile carries rules for every exception code on FC03 (addresses 1000-1007, one per code), FC06 (2000-2001 for CPU-PROGRAM-mode and busy), and FC16 (3000 for server failure). New exception_injection compose profile binds :5020 like every other service + runs python /fixtures/exception_injector.py --config /fixtures/exception_injection.json. New ExceptionInjectionTests.cs in Modbus.IntegrationTests — 11 tests. Eight FC03-read theories exercise every exception code 0x01/0x02/0x03/0x04/0x05/0x06/0x0A/0x0B asserting the driver's expected OPC UA StatusCode mapping (BadNotSupported/BadOutOfRange/BadOutOfRange/BadDeviceFailure/BadDeviceFailure/BadDeviceFailure/BadCommunicationError/BadCommunicationError). Two FC06-write theories cover the write path for 0x04 (Server Failure, CPU in PROGRAM mode) + 0x06 (Server Busy). One sanity-check read at address 5 confirms the injector isn't globally broken + non-injected reads round-trip cleanly with Value=5/StatusCode=Good. All tests follow the MODBUS_SIM_PROFILE=exception_injection skip guard so they no-op on a fresh clone without Docker running. Docker/README.md gains an §Exception injection section explaining what pymodbus can and cannot emit, what the injector does, where the rules live, and how to append new ones. docs/drivers/Modbus-Test-Fixture.md follow-up item #2 (extend pymodbus profiles to inject exceptions) gets a shipped strikethrough with the new coverage inventory; the unit-level section adds ExceptionInjectionTests next to DL205ExceptionCodeTests so the split-of-responsibilities is explicit (DL205 test = natural out-of-range via dl205 profile, ExceptionInjectionTests = every other code via the injector). Test baselines: Modbus unit 182/182 green (unchanged); Modbus integration with exception_injection profile live 11/11 new tests green. Existing DL205/S7/Mitsubishi integration tests unaffected since they skip on MODBUS_SIM_PROFILE mismatch. Found + fixed during validation: a stale native pymodbus simulator from April 18 was still listening on port 5020 on IPv6 localhost (Windows was load-balancing between it + the Docker IPv4 forward, making injected exceptions intermittently come back as pymodbus's default 0x02). Killed the leftover. Documented the debugging path in the commit as a note for anyone who hits the same "my tests see exception 0x02 but the injector log has no request" symptom. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
LmxOpcUa
OPC UA server and cross-platform client tools for AVEVA System Platform (Wonderware) Galaxy. The server exposes Galaxy tags via MXAccess as an OPC UA address space. The client stack provides a shared library, CLI tool, and Avalonia desktop application for browsing, reading/writing, subscriptions, alarms, and historical data.
Architecture
OPC UA Clients
(CLI, Desktop UI, 3rd-party)
|
v
+-----------------+ +------------------+ +-----------------+
| Galaxy Repo DB |---->| OPC UA Server |<--->| MXAccess Client |
| (SQL Server) | | (address space) | | (STA + COM) |
+-----------------+ +------------------+ +-----------------+
| |
+-------+--------+ +---------+---------+
| Status Dashboard| | Historian Runtime |
| (HTTP/JSON) | | (SQL Server) |
+----------------+ +-------------------+
Contained Name vs Tag Name
| Browse Path (contained names) | Runtime Reference (tag name) |
|---|---|
TestMachine_001/DelmiaReceiver/DownloadPath |
DelmiaReceiver_001.DownloadPath |
TestMachine_001/MESReceiver/MoveInBatchID |
MESReceiver_001.MoveInBatchID |
Server
The OPC UA server runs on .NET Framework 4.8 (x86) and bridges the Galaxy runtime to OPC UA clients.
Server Prerequisites
- .NET Framework 4.8 SDK
- AVEVA System Platform with ArchestrA Framework installed
- Galaxy repository database (SQL Server, Windows Auth)
- MXAccess COM registered (
LMXProxy.LMXProxyServer) - Wonderware Historian (optional, for historical data access)
- Windows (required for COM interop and MXAccess)
Build and Run Server
dotnet restore ZB.MOM.WW.LmxOpcUa.slnx
dotnet build src/ZB.MOM.WW.LmxOpcUa.Host
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Host
The server starts on opc.tcp://localhost:4840/LmxOpcUa with the None security profile by default. Configure Security.Profiles in appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt for transport security. See Security Guide.
Install as Windows Service
cd src/ZB.MOM.WW.LmxOpcUa.Host/bin/Debug/net48
ZB.MOM.WW.LmxOpcUa.Host.exe install
ZB.MOM.WW.LmxOpcUa.Host.exe start
Service logon requirement: The service must run under a Windows account that has access to the AVEVA Galaxy and Historian. The default LocalSystem account can connect to MXAccess and SQL Server but cannot authenticate with the Historian SDK (HCAP). Configure the service to "Log on as" a domain or local user that is a recognized ArchestrA platform user. This can be set in services.msc or during install with ZB.MOM.WW.LmxOpcUa.Host.exe install -username DOMAIN\user -password ***.
Run Server Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.IntegrationTests
Client Stack
The client stack is cross-platform (.NET 10) and consists of three projects sharing a common IOpcUaClientService abstraction. No AVEVA software or COM is required — the clients connect to any OPC UA server.
Client Prerequisites
- .NET 10 SDK
- No platform-specific dependencies (runs on Windows, macOS, Linux)
Build All Clients
dotnet build src/ZB.MOM.WW.LmxOpcUa.Client.Shared
dotnet build src/ZB.MOM.WW.LmxOpcUa.Client.CLI
dotnet build src/ZB.MOM.WW.LmxOpcUa.Client.UI
Run Client Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.Client.Shared.Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.Client.CLI.Tests
dotnet test tests/ZB.MOM.WW.LmxOpcUa.Client.UI.Tests
Client CLI
# Connect
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840/LmxOpcUa
# Browse Galaxy hierarchy
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=ZB" -r -d 5
# Read a tag
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestMachine_001.MachineID"
# Write a tag
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestChildObject.TestString" -v "Hello"
# Subscribe to changes
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestChildObject.TestInt" -i 500
# Read historical data
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- historyread -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestMachine_001.TestHistoryValue" --start "2026-03-25" --end "2026-03-30"
# Subscribe to alarm events
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- alarms -u opc.tcp://localhost:4840/LmxOpcUa -n "ns=3;s=TestMachine_001" --refresh
# Query redundancy state
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.CLI -- redundancy -u opc.tcp://localhost:4840/LmxOpcUa
Client UI
dotnet run --project src/ZB.MOM.WW.LmxOpcUa.Client.UI
The desktop application provides browse tree, subscriptions, alarm monitoring, history reads, and write dialogs. See Client UI Documentation for details.
Project Structure
src/
ZB.MOM.WW.LmxOpcUa.Host/ OPC UA server (.NET Framework 4.8, x86)
Configuration/ Config binding and validation
Domain/ Interfaces, DTOs, enums, mappers
Historian/ Wonderware Historian data source
Metrics/ Performance tracking (rolling P95)
MxAccess/ STA thread, COM interop, subscriptions
GalaxyRepository/ SQL queries, change detection
OpcUa/ Server, node manager, address space, alarms, diff
Status/ HTTP dashboard, health checks
ZB.MOM.WW.LmxOpcUa.Client.Shared/ Shared OPC UA client library (.NET 10)
ZB.MOM.WW.LmxOpcUa.Client.CLI/ Command-line client (.NET 10)
ZB.MOM.WW.LmxOpcUa.Client.UI/ Avalonia desktop client (.NET 10)
tests/
ZB.MOM.WW.LmxOpcUa.Tests/ Server unit + integration tests
ZB.MOM.WW.LmxOpcUa.IntegrationTests/ Server integration tests (live DB)
ZB.MOM.WW.LmxOpcUa.Client.Shared.Tests/ Shared library tests
ZB.MOM.WW.LmxOpcUa.Client.CLI.Tests/ CLI command tests
ZB.MOM.WW.LmxOpcUa.Client.UI.Tests/ UI ViewModel + headless tests
gr/ Galaxy repository docs, SQL queries, schema
Documentation
Server
| Component | Description |
|---|---|
| OPC UA Server | Endpoint, sessions, security policy, server lifecycle |
| Address Space | Hierarchy nodes, variable nodes, primitive grouping, NodeId scheme |
| Galaxy Repository | SQL queries, deployed package chain, change detection |
| MXAccess Bridge | STA thread, COM interop, subscriptions, reconnection |
| Data Type Mapping | Galaxy to OPC UA types, arrays, security classification |
| Read/Write Operations | Value reads, writes, access level enforcement, array element writes |
| Subscriptions | Ref-counted MXAccess subscriptions, data change dispatch |
| Alarm Tracking | AlarmConditionState nodes, InAlarm monitoring, event reporting |
| Historical Data Access | Historian data source, HistoryReadRaw, HistoryReadProcessed |
| Incremental Sync | Diff computation, subtree teardown/rebuild, subscription preservation |
| Configuration | appsettings.json binding, feature flags, validation |
| Status Dashboard | HTTP server, health checks, metrics reporting |
| Service Hosting | TopShelf, startup/shutdown sequence, error handling |
| Security | Transport security profiles, certificate trust, production hardening |
| Redundancy | Non-transparent warm/hot redundancy, ServiceLevel, paired deployment |
Client
| Component | Description |
|---|---|
| Client CLI | Connect, browse, read, write, subscribe, historyread, alarms, redundancy commands |
| Client UI | Avalonia desktop client: browse, subscribe, alarms, history, write values |
Reference
- Galaxy Repository Queries — SQL queries for hierarchy, attributes, and change detection
- Data Type Mapping — Galaxy to OPC UA type mapping with security classification
License