otopcua-ablegacy-cli — AB Legacy (PCCC) test client

Ad-hoc probe / read / write / subscribe tool for SLC 500 / MicroLogix 1100 / MicroLogix 1400 / PLC-5 devices, talking to the same AbLegacyDriver the OtOpcUa server uses (libplctag PCCC back-end).

Third of four driver test-client CLIs. Shares Driver.Cli.Common with the others.

Build + run

dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Cli -- --help

Common flags

Flag Default Purpose
-g / --gateway required Canonical ab://host[:port]/cip-path
-P / --plc-type Slc500 Slc500 / MicroLogix / Plc5 / LogixPccc
--timeout-ms 5000 Per-operation timeout
--verbose off Serilog debug output

Family ↔ CIP-path cheat sheet:

  • SLC 5/05 / PLC-51,0
  • MicroLogix 1100 / 1400 — empty path (ab://host/) — they use direct EIP with no backplane
  • LogixPccc1,0 (Logix controller accessed via the PCCC compatibility layer; rare)

PCCC address primer

File letters imply data type; type flag still required so the CLI knows how to parse your --value.

File Type CLI --type
N signed int16 Int
F float32 Float
B bit-packed (B3:0/3 addresses bit 3 of word 0) Bit
L long int32 (SLC 5/05+ only) Long
A analog int (semantically like N) AnalogInt
ST ASCII string (82-byte + length header) String
T timer sub-element (T4:0.ACC / .PRE / .EN / .DN) TimerElement
C counter sub-element (C5:0.ACC / .PRE / .CU / .CD / .DN) CounterElement
R control sub-element (R6:0.LEN / .POS / .EN / .DN / .ER) ControlElement

Commands

probe

# SLC 5/05 — default probe address N7:0
otopcua-ablegacy-cli probe -g ab://192.168.1.20/1,0

# MicroLogix 1100 — status file first word
otopcua-ablegacy-cli probe -g ab://192.168.1.30/ -P MicroLogix -a S:0

read

# Integer
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a N7:10 -t Int

# Float
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a F8:0 -t Float

# Bit-within-word
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a B3:0/3 -t Bit

# Long (SLC 5/05+)
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a L19:0 -t Long

# Timer ACC
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a T4:0.ACC -t TimerElement

write

otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a N7:10 -t Int -v 42
otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a F8:0 -t Float -v 3.14
otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a B3:0/3 -t Bit -v on

Writes to timer / counter / control sub-elements land at the wire level but the PLC's runtime semantics (EN/DN edge-triggering, preset reload) are PLC-managed — use with caution.

subscribe

otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a N7:10 -t Int -i 500

Deadband

PR 8 — per-tag absolute / percent change filter on top of the polled subscription. The driver caches the last published value per tag and suppresses OnDataChange notifications until the new sample crosses the configured threshold.

Flag Effect
--deadband-absolute <value> Suppress until `
--deadband-percent <value> Suppress until `

Booleans bypass the filter entirely (every transition publishes); strings + status changes always publish; first-seen always publishes; both flags set → either passing triggers a publish (Kepware-style logical OR).

# Float — drop sub-0.5 jitter from the noisy load-cell address.
otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a F8:0 -t Float -i 500 `
    --deadband-absolute 0.5

# Integer — only fire on >= 5% deviation from the last reported value.
otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a N7:10 -t Int -i 500 `
    --deadband-percent 5

Array reads

PR 7 — one PCCC frame can carry up to ~120 words. Address an array tag with either the Rockwell-native ,N suffix or the libplctag-native [N] suffix on the word number; both forms canonicalise to [N] when the driver hands the tag to libplctag, and the parser caps N at 120.

# Rockwell `,N` form — "10 consecutive words starting at N7:0"
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0,10" -t Int

# libplctag `[N]` form — same wire result
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0[10]" -t Int

# Float / Long arrays — same suffix syntax, narrower frame ceiling on Float (~60 elements)
# and Long (~60 elements) because each element is 4 bytes vs Int's 2.
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "F8:0,4" -t Float
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "L19:0,4" -t Long

# --array-length override — pin the element count from config rather than the address
# suffix. Wins over the parsed `,N` / `[N]` value when both are set; useful for keeping the
# address string compact while bumping the element count from a tags config file.
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0" --array-length 10 -t Int

Array tags reject sub-element references (T4:0,5.ACC) and bit suffixes (N7:0,10/3) at parse time — both combinations are semantically meaningless against a contiguous block.

For B-files the Rockwell convention is "one BOOL per word, not per bit": B3:0,10 returns bool[10] (one per word's non-zero state), not bool[160].

Known caveat — ab_server upstream gap

The integration-fixture ab_server Docker container accepts TCP but its PCCC dispatcher doesn't actually respond — see tests/...AbLegacy.IntegrationTests/Docker/README.md. Point --gateway at real hardware or an RSEmulate 500 box for end-to-end wire-level validation. The CLI itself is correct regardless of which endpoint you target.