Joseph Doherty 8d92e00e38 Task #253 — E2E CLI test scripts + FOCAS test-client CLI
The driver-layer integration tests confirm the driver sees the PLC, and
the Client.CLI tests confirm the client sees the server. Nothing glued
them end-to-end until this PR.

- scripts/e2e/_common.ps1: shared helpers — CLI invocation (published-
  binary OR `dotnet run` fallback), Test-Probe / Test-DriverLoopback /
  Test-ServerBridge (all return @{Passed;Reason} hashtables).
- scripts/e2e/test-<modbus|abcip|ablegacy|s7|focas|twincat>.ps1: per-
  driver three-stage script (probe → driver-loopback → server-bridge).
  AB Legacy / FOCAS / TwinCAT are gated behind *_TRUST_WIRE env vars
  since they need real hardware (#222) or a licensed runtime (#221).
- scripts/e2e/test-phase7-virtualtags.ps1: writes a Modbus HR, reads
  the server-side VirtualTag (VT = input * 2) back via OPC UA, triggers
  + clears a scripted alarm. Exercises the Phase 7 CachedTagUpstreamSource
  + ScriptedAlarmEngine path.
- scripts/e2e/test-all.ps1: reads e2e-config.json sidecar, runs each
  present driver, prints a FINAL MATRIX (PASS/FAIL/SKIP). Missing
  sections SKIP rather than fail hard.
- scripts/e2e/e2e-config.sample.json: commented sample — each dev's
  NodeIds are local-seed-specific so e2e-config.json is .gitignore-d.
- scripts/e2e/README.md: full walkthrough — prereqs, three-stage design,
  env-var gates, expected matrix, why this is separate from `dotnet test`.

Tasks #249-#251 shipped Modbus/AbCip/AbLegacy/S7/TwinCAT CLIs but left
FOCAS out. Since test-focas.ps1 needs it, the 6th CLI ships here:

- src/ZB.MOM.WW.OtOpcUa.Driver.FOCAS.Cli: probe/read/write/subscribe
  commands, AssemblyName `otopcua-focas-cli`. WriteCommand.ParseValue
  handles the full FocasDataType enum (Bit/Byte/Int16/Int32/Float32/
  Float64/String — no UInt variants; the FOCAS protocol exposes signed
  PMC + Fanuc-Float only). Default DataType is Int16 to match the PMC
  register convention.

Full-solution build clean (0 errors). FOCAS CLI wired into
ZB.MOM.WW.OtOpcUa.slnx. No .Tests project for the FOCAS CLI yet —
symmetric with how ProbeCommand has no unit-testable pure logic in the
other 5 CLIs either; WriteCommand.ParseValue parity will land in a
follow-up to keep this PR scoped.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-21 09:51:13 -04:00

82 lines
2.7 KiB
PowerShell

#Requires -Version 7.0
<#
.SYNOPSIS
End-to-end CLI test for the TwinCAT (Beckhoff ADS) driver.
.DESCRIPTION
Requires a reachable AMS router (local TwinCAT XAR, Beckhoff.TwinCAT.Ads.
TcpRouter NuGet, or an authorised remote AMS route) + a live TwinCAT
runtime on -AmsNetId. Without one the driver surfaces a transport error
on InitializeAsync + the script's probe fails.
Set TWINCAT_TRUST_WIRE=1 to promise the endpoint is live. Without it the
script skips (task #221 tracks the 7-day-trial CI fixture — until that
lands, TwinCAT testing is a manual operator task).
.PARAMETER AmsNetId
AMS Net ID of the target (e.g. 127.0.0.1.1.1 for local XAR,
192.168.1.40.1.1 for a remote PLC).
.PARAMETER AmsPort
AMS port. Default 851 (TC3 PLC runtime). TC2 uses 801.
.PARAMETER SymbolPath
TwinCAT symbol to exercise. Default 'MAIN.iCounter' — substitute with
whatever your project actually declares.
.PARAMETER OpcUaUrl
OtOpcUa server endpoint.
.PARAMETER BridgeNodeId
NodeId at which the server publishes the Symbol.
#>
param(
[string]$AmsNetId = "127.0.0.1.1.1",
[int]$AmsPort = 851,
[string]$SymbolPath = "MAIN.iCounter",
[string]$OpcUaUrl = "opc.tcp://localhost:4840",
[Parameter(Mandatory)] [string]$BridgeNodeId
)
$ErrorActionPreference = "Stop"
. "$PSScriptRoot/_common.ps1"
if (-not ($env:TWINCAT_TRUST_WIRE -eq "1" -or $env:TWINCAT_TRUST_WIRE -eq "true")) {
Write-Skip "TWINCAT_TRUST_WIRE not set — requires reachable AMS router + live TC runtime (task #221 tracks the CI fixture). Set =1 once the router is up."
exit 0
}
$twinCatCli = Get-CliInvocation `
-ProjectFolder "src/ZB.MOM.WW.OtOpcUa.Driver.TwinCAT.Cli" `
-ExeName "otopcua-twincat-cli"
$opcUaCli = Get-CliInvocation `
-ProjectFolder "src/ZB.MOM.WW.OtOpcUa.Client.CLI" `
-ExeName "otopcua-cli"
$commonTc = @("-n", $AmsNetId, "-p", $AmsPort)
$results = @()
$results += Test-Probe `
-Cli $twinCatCli `
-ProbeArgs (@("probe") + $commonTc + @("-s", $SymbolPath, "--type", "DInt"))
$writeValue = Get-Random -Minimum 1 -Maximum 9999
$results += Test-DriverLoopback `
-Cli $twinCatCli `
-WriteArgs (@("write") + $commonTc + @("-s", $SymbolPath, "-t", "DInt", "-v", $writeValue)) `
-ReadArgs (@("read") + $commonTc + @("-s", $SymbolPath, "-t", "DInt")) `
-ExpectedValue "$writeValue"
$bridgeValue = Get-Random -Minimum 10000 -Maximum 19999
$results += Test-ServerBridge `
-DriverCli $twinCatCli `
-DriverWriteArgs (@("write") + $commonTc + @("-s", $SymbolPath, "-t", "DInt", "-v", $bridgeValue)) `
-OpcUaCli $opcUaCli `
-OpcUaUrl $OpcUaUrl `
-OpcUaNodeId $BridgeNodeId `
-ExpectedValue "$bridgeValue"
Write-Summary -Title "TwinCAT e2e" -Results $results
if ($results | Where-Object { -not $_.Passed }) { exit 1 }