The sidecar was set to PlatformTarget=x86 + Prefer32Bit=true to mirror v1's Driver.Galaxy.Host bitness, which itself was x86 only because of MXAccess COM. PR 7.2 retired Galaxy.Host, so that constraint is gone. AVEVA Historian 2020 ships an x64 build of every SDK assembly the sidecar needs (lib\aahClientManaged.dll + aahClient.dll + aahClientCommon.dll sourced from C:\Program Files (x86)\Wonderware\Historian\x64\; the remaining three SDK assemblies — Historian.CBE / DPAPI / ArchestrA.CloudHistorian.Contract — are pure-managed AnyCPU and load in either bitness). Drop PlatformTarget to x64 on both the sidecar project and its test project; running 37/37 historian tests + the live install confirms the SDK loads and serves the named pipe in a 64-bit-native process. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
OtOpcUa
OPC UA server (.NET 10 AnyCPU) that exposes a fleet of industrial drivers as a single OPC UA address space. Drivers ship in-process for AVEVA System Platform Galaxy (via the sibling mxaccessgw repo), Modbus TCP, Siemens S7, Allen-Bradley CIP (ControlLogix / CompactLogix), Allen-Bradley Legacy (SLC 500 / MicroLogix), Beckhoff TwinCAT (ADS), FANUC FOCAS, and OPC UA Client (gateway).
A cross-platform client stack (.NET 10) — shared library, CLI, and Avalonia desktop app — connects to any OPC UA server.
Architecture
OPC UA Clients (CLI, Desktop UI, 3rd-party)
|
v
+-------------------------------------+
| OtOpcUa.Server (.NET 10 AnyCPU) |
| address space + capability fan-out|
+-------------------------------------+
| | | | | | | |
Galaxy Modbus S7 AbCip AbLeg TwinCAT FOCAS OpcUaClient
|
v
mxaccessgw (sibling repo, gRPC)
|
v
MXAccess COM (x86 worker, on AVEVA box)
Galaxy is the only driver with an external runtime: it speaks gRPC to a separately installed mxaccessgw server (sibling repo at c:\Users\dohertj2\Desktop\mxaccessgw\) which owns the MXAccess COM apartment and the x86/STA bitness constraint server-side. Everything in this repo is platform-agnostic .NET 10.
Prerequisites
- .NET 10 SDK (server, drivers, clients all target .NET 10)
- SQL Server reachable for the central config DB
- For Galaxy specifically: a running
mxaccessgwdeployment — see docs/v2/Galaxy.ParityRig.md - For Wonderware Historian read-back: optional
OtOpcUaWonderwareHistoriansidecar — see docs/ServiceHosting.md
Quick Start
dotnet restore ZB.MOM.WW.OtOpcUa.slnx
dotnet build ZB.MOM.WW.OtOpcUa.slnx
dotnet test ZB.MOM.WW.OtOpcUa.slnx
# Run the server in dev (foreground)
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Server
The server starts on opc.tcp://localhost:4840 with the None security profile. Configure Security.Profiles in src/ZB.MOM.WW.OtOpcUa.Server/appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt. See docs/security.md.
Install as Windows Services
Production deployment is driven by scripts/install/Install-Services.ps1, which registers the OtOpcUa server service (and optionally the OtOpcUaWonderwareHistorian sidecar) under a chosen service account. Galaxy support requires a separately installed mxaccessgw — neither this repo nor the install script provisions it.
.\scripts\install\Install-Services.ps1 `
-InstallRoot 'C:\Program Files\OtOpcUa' `
-ServiceAccount 'DOMAIN\svc-otopcua'
Add -InstallWonderwareHistorian for the historian sidecar. See the script header and docs/ServiceHosting.md for full options.
Client CLI
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840 -r -d 3
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode"
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -v 42
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -i 500
See docs/Client.CLI.md and docs/Client.UI.md.
Documentation
Architecture deep-dives
| Topic | Doc |
|---|---|
| OPC UA server composition, namespace fan-out, Polly invoker | docs/OpcUaServer.md |
| Address space layout | docs/AddressSpace.md |
| Read / Write dispatch (driver vs virtual vs scripted-alarm) | docs/ReadWriteOperations.md |
| Incremental sync (driver-backend rediscovery + config publishes) | docs/IncrementalSync.md |
| Service hosting (Server + Admin + optional historian sidecar) | docs/ServiceHosting.md |
| Security (transport, LDAP, certificates) | docs/security.md |
| Redundancy | docs/Redundancy.md |
| Status dashboard | docs/StatusDashboard.md |
Drivers
| Topic | Doc |
|---|---|
| Driver specs (per-driver capability surface, config, addressing) | docs/v2/driver-specs.md |
| Galaxy driver | docs/drivers/Galaxy.md |
| Modbus / S7 / AbCip / AbLegacy / TwinCAT / FOCAS / OpcUaClient | docs/drivers/ |
| Galaxy parity rig (mxaccessgw setup) | docs/v2/Galaxy.ParityRig.md |
| Galaxy performance + tracing | docs/v2/Galaxy.Performance.md |
Clients
| Topic | Doc |
|---|---|
| Client CLI | docs/Client.CLI.md |
| Client UI (Avalonia desktop) | docs/Client.UI.md |
v1 archive
The original v1 in-process MXAccess docs (Galaxy.Host topology, Configuration env vars, AlarmTracking, DataTypeMapping, HistoricalDataAccess, Subscriptions, etc.) are preserved under docs/v1/ — historical reference only. PR 7.2 retired the v1 architecture on 2026-04-30; current state is documented in the sections above.
License
Internal use only.