Joseph Doherty beb1c583b1 fix(opcuaclient): #676 live gate A1 — a sustained closed connection is a definitive loss
Live gate A1 (docker-dev, opc-plc restart / SIGINT / kill): the fast path never fired —
a real process stop delivers no session status; the keep-alives report
BadSecureChannelClosed (0x80860000) once, then BadConnectionClosed (0x80AE0000)
interleaved with BadNoCommunication for the whole outage.

Reproduced in-process with TcpStallProxy.HardClose (reset every connection, refuse new
ones; server and session alive behind it): the identical sequence, and the SDK 1.5.378
session never opens a new connection on its own (48 s with the proxy accepting again,
zero attempts) — a closed channel cannot recover in place.

The driver now treats BadSecureChannelClosed/BadConnectionClosed as definitive on the
SECOND closed-channel keep-alive failure in one outage (a good keep-alive resets the
count), raising ConnectionLost ~1 keep-alive after the drop. BadNoCommunication /
BadRequestTimeout / BadNotConnected (stall/pause) stay with the watchdog; the stall test
still sees no ConnectionLost. New wire test (hard close + reopen ⇒ raised once, SDK never
reconnects, reinit brings the identical value back Good) and unit tests (sustained raises
once; a single blip that recovers does not) — all red on the previous code. Docs updated.
2026-10-11 12:34:52 -04:00

345 lines
27 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# OPC UA Client (Gateway) Driver
Getting-started guide for the OPC UA Client driver. This is the short path — for
the full per-field spec read [`docs/v2/driver-specs.md §8`](../v2/driver-specs.md),
and for the test-harness map read [OpcUaClient-Test-Fixture.md](OpcUaClient-Test-Fixture.md).
## What it talks to
A **remote OPC UA server**. This driver runs the *opposite* direction from the
usual "server exposes PLC data" flow: it acts as an OPC UA **client**, opens a
`Session` against an upstream server, and re-exposes that server's address space
through the local OtOpcUa server. Browse, read, write, subscribe, alarm, and
history calls are passed through to the upstream endpoint.
It is built on the OPC Foundation UA .NET Standard reference SDK and runs
in-process in the OtOpcUa server's .NET 10 AnyCPU host — pure managed, no
out-of-process isolation.
> There is **no standalone driver CLI** for the OPC UA Client driver. To exercise
> a remote OPC UA endpoint by hand, point the general-purpose
> [Client CLI](../Client.CLI.md) at it directly.
## Project split
| Project | Target | Role |
|---------|--------|------|
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient/` | net10.0 | In-process driver — session lifetime, read / write / subscribe / alarm / history passthrough |
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Browser/` | net10.0 | `IDriverBrowser` — live address-picker browse used by the AdminUI |
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Contracts/` | net10.0 | Config records + enums bound from `DriverConfig` JSON |
## Minimum deployment
```jsonc
"Drivers": {
"upstream-1": {
"Type": "OpcUaClient",
"Config": {
"EndpointUrl": "opc.tcp://plc.internal:4840",
"SecurityPolicy": "None",
"SecurityMode": "None",
"AuthType": "Anonymous"
}
}
}
```
`EndpointUrls` (a list) takes precedence over the single-URL `EndpointUrl` and
provides ordered **failover** — the driver tries each candidate in turn at every
`InitializeAsync` (including the comms-loss watchdog's re-initialise), and the first to connect wins (e.g. a hot-standby pair on
4840 / 4841). See
`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Contracts/OpcUaClientDriverOptions.cs`
for every field (security policy/mode, auth type, session timeout, keep-alive,
browse root, node/depth caps). `ReconnectPeriod` was **deleted** (#676 — unused since #670 removed the SDK reconnect
handler, and the AdminUI no longer shows it); stored configs that still carry `reconnectPeriod` keep parsing in the
factory, the Test-Connect probe and the browse picker (unknown keys are skipped), and the form drops it on the next save.
### Endpoint address: the configured host and port win (#676)
GetEndpoints returns each endpoint with the URL the **server** believes it lives at. Behind NAT, a port map, a
container port publish or a proxy that address is unreachable from the client — or reachable but bypassing the proxy.
The driver therefore rewrites the selected endpoint's **host and port** to the configured URL's whenever the schemes
match, keeping the advertised path (the SDK's own `CoreClientUtils.SelectEndpoint` rule, which the driver's
policy-aware endpoint selection used to bypass). A configured URL with **no port** keeps the advertised port (copying
the port-less `-1` would have sent the session to 4840). A different scheme is left alone; an unparseable advertised
URL falls back to the configured one. `OpcUaClientDriver.RewriteEndpointUrl`.
### Session lifetime
A single `Session` per driver instance; subscriptions multiplex onto it. Stored NodeIds embed the server-stable namespace **URI** (not the
session-relative `ns=N` index) so a remote namespace-table reorder across a
restart doesn't silently re-point references at the wrong namespace.
### Upstream outage and recovery (Gitea #670)
The session keep-alive (`KeepAliveInterval`, default 5 s) is the liveness signal:
- **Good keep-alive / any data or event notification** advances `DriverHealth.LastSuccessfulRead` — a
subscription-only driver never calls `ReadAsync`, so without this its read stamp froze at connect time.
- **Bad keep-alive** ⇒ health `Degraded` (`LastError = "keep-alive: <status>"`, read stamp preserved), host status
`Stopped`, and — **once per outage**, not per keep-alive — every subscribed ref is published `BadNoCommunication`
with its last value retained and **source + server timestamp = the detection time** (live-gate F1: stamped with the
last Good's source time it collided with that row's `(TagId, SourceTimeUtc)` history key and was never stored), plus a quality-only `BadNoCommunication` annotation (#626 pattern, no alarm-state
change, no `/alerts` row) on every subscribed alarm condition.
- **The session survives** (a network blip; the keep-alive turns Good again) ⇒ recovered in place: health `Healthy`,
the refs still Bad are re-read once and published Good (a server whose subscription survived does not resend an
unchanged value, and a `(value, status)` dedup downstream lets the identical value through), alarm quality goes
back Good and a `ConditionRefresh` re-reports anything missed. A notification that lands first wins over the read.
For a bounded **replay window** after such a recovery — max(30 s, 2 x the longest subscription keep-alive window) —
each ref is guarded by a high-water mark — its last Good upstream source time, raised by the recovery read and
advanced by every notification accepted in the window — and a notification whose source time is at or BELOW it
(equal included: OPC UA moves the source timestamp on every value or status change, so an equal one is a replay)
is dropped: the SDK was seen delivering a missed one 4–6 s late, which regressed the node (live-gate F2). The
guard holds for the WHOLE window — fresh notifications arrive ~1 s after recovery, before the late replay, so a
ref is never disarmed early (the F2 re-gate failed on exactly that). A notification with no source time passes
without moving the mark. Outside that window every notification is
accepted whatever its timestamp, so an upstream clock that steps backwards (NTP, a PLC clock reset) never
freezes a node. The outage Bad never moves the comparison; a re-initialise resets it.
⚠️ **By design, inside the window a notification whose source time EQUALS the last accepted one is dropped** — so a
status-only change that keeps the old source timestamp (not what OPC UA servers are supposed to do) is lost during
the window only (the trailing re-read below repairs it). When the window closes — or a second recovery re-arms it —
the driver logs ONE line, `post-recovery replay window closed — dropped N late notifications across M refs after
recovery`, at **Information when N > 0** and Debug otherwise, because the per-drop line is Debug and the
`stale_notification_dropped` counter is OTel-only, which made the guard unobservable on the docker-dev rig (#676).
A re-arm starts the count afresh.
- **Trailing re-read after an in-place recovery (#676).** Found by the TCP-stall wire test: a change the server
published just after the stall ended rode a Publish response that had been in flight across the stall; the SDK
timed that request out (`BadTimeout`), discarded the response and never republished the message (the following
keep-alives moved the sequence number past it), so the node stayed **Good on the pre-change value indefinitely**.
`Timeout + KeepAliveInterval` after the recovery — when every request in flight across the stall has completed or
timed out — every subscribed ref is read once more and published when its **(value, status) differs** from the last
value delivered for that ref **and is not older** than it. Any status counts: a Good→Bad/Uncertain change lost in the
pipeline is as stale as a lost value. "Older" compares source timestamps only when both carry one; a read with no
source timestamp (a server that does not send them) is the server's current state and counts as newer. An **equal**
source timestamp with different content IS published — it is the server's current state, not a replay, and it repairs
the equal-timestamp status-only change the replay guard drops by design. An identical (value, status) is never
republished. A ref that received ANY delivery while the read was in flight is skipped (a per-ref delivery counter is
captured before the read is issued): without source timestamps the read's sample cannot be ordered against that
notification, and publishing it would regress the node. An Information line names how many refs it had to repair. The trailing read and the replay-guard disarm
timer run on the driver clock and are cancelled when the session is released (re-initialise / shutdown / dispose).
- **No older value is ever delivered after a newer one.** The paths that publish upstream data — live notifications,
the recovery read, the trailing read and the comms-loss Bad fan — make their "may I publish this?" decision and the
publish inside one driver-wide critical section. A single lock rather than one per ref: it also serialises delivery
across subscriptions (the SDK dispatches each subscription's messages on its own worker), which is cheap because each
section is a dictionary update plus a subscriber `Tell` and nothing awaits under it. Subscribers run inside it — the
host's handler only `Tell`s an actor — so a subscriber must never block on, or call back into, the driver.
- **The session does not come back** (an upstream restart: the server forgot the session) ⇒ the driver stays
`Degraded` with its read stamp frozen, which is the #527 comms-loss watchdog's trip condition; `DriverInstanceActor`
runs `ShutdownAsync` + `InitializeAsync` (retried every 10 s while the server is down) and re-subscribes data +
alarms; the new subscription's initial values come back Good. Alarm last-told state survives the re-initialise
(#619), so the post-subscribe `ConditionRefresh` raises no un-ack flicker; the host's reconnect annotation restores
condition quality.
- **Fast recovery for a DEFINITIVELY lost session (#676).** The driver implements `IDriverConnectionLossSource` and
raises `ConnectionLost` — **once per session**, re-armed by a re-initialise — when the loss is certain, so the host
re-initialises at once instead of after the watchdog's 90 s. Definitive means: a keep-alive status of
`BadSessionIdInvalid` / `BadSessionClosed` / `BadSessionNotActivated` (the server forgot, closed or never activated
the session) or `BadServerHalted`, or a subscription the **server** reported gone (below). `BadServerHalted` is on the list
because it was **measured**: on the restart wire test a gracefully stopped server reports `BadServerHalted` (and the
keep-alives alternate it with `BadNoCommunication`), and the SDK never re-opens a channel the server halted — 15 s
after the server was back, the same session still failed every request with `BadServerHalted`; `BadSessionIdInvalid`
never arrived.
**A CLOSED connection is definitive too, once sustained (live gate A1).** Against a real opc-plc on docker-dev, none of
`docker restart`, a graceful SIGINT stop (opc-plc itself logged `BadServerHalted`) or `docker kill` delivered a
session status to the client: the keep-alives reported `BadSecureChannelClosed` (0x80860000) once, then
`BadConnectionClosed` (0x80AE0000) interleaved with `BadNoCommunication` for the whole outage, so the first cut of the
fast path never fired and recovery took 91–127 s. Reproduced in-process with `TcpStallProxy.HardClose` (every
connection reset, new ones refused, the server AND its session still alive behind it): the same sequence, and the SDK
1.5.378 session **never opens a new connection by itself** — 48 s after the proxy accepted connections again, not one
attempt. So a closed channel can never recover in place; on the **second** closed-channel keep-alive failure in one
outage (`IsClosedChannel`; a good keep-alive resets the count, so a single transient does not count) the driver raises
`ConnectionLost` — about one keep-alive interval after the connection dropped. Everything else —
`BadNoCommunication`, `BadNotConnected`, `BadRequestTimeout`/`BadTimeout` (what a stalled or paused link produces) —
is **ambiguous** (the link may resume and keep its session, see the stall test) and stays with the watchdog.
Consequence: a restarted, stopped or killed upstream is re-initialised within roughly one keep-alive plus one
reconnect interval instead of ~100 s; a pause (`docker pause`, a congested link) still recovers in place. ⚠️ **Known gap:** the host acts on the signal only while the driver is
`Connected`, and the driver raises it once per session — so a definitive loss raised while the host is not
Connected (e.g. `BadServerHalted` on the fresh session before the host has processed the successful initialise) is
swallowed and that session falls back to the watchdog. Re-raising on later keep-alives would close it but was left out
to keep the once-per-session contract simple; the cost is the pre-#676 recovery time, in a narrow window.
- **The subscription dies but the session lives** (an outage longer than the subscription lifetime —
`LifetimeCount` x publishing interval, often well under the session timeout — or a server that drops it) ⇒ keep-alives
stay Good, so they cannot be the signal. A `PublishError` of `BadNoSubscription` (while subscriptions are tracked) or
`BadSubscriptionIdInvalid` naming a tracked subscription, or a tracked subscription whose SDK `PublishingStopped`
persists for one more subscription keep-alive window + 5 s across good keep-alives, declares it lost: `Degraded`
(`"subscription lost: …"`), the outage published once, and — sticky until the session is released — **nothing**
advances `LastSuccessfulRead` any more (not good keep-alives, not a sibling subscription's notifications), so the
watchdog's re-initialise recreates it. Both detectors are wire-tested independently. A subscription the **server**
reported gone (`BadNoSubscription` / `BadSubscriptionIdInvalid`) never comes back on its session, so that also raises
`ConnectionLost` (#676) and the re-initialise happens at once; the `PublishingStopped` **heuristic** is an inference
from silence and keeps going through the watchdog.
- An in-place recovery is bound to the session whose keep-alive recovered: one overtaken by a re-initialise neither
publishes, nor degrades, nor re-arms the outage latch of the new session.
There is **no in-driver reconnect** any more. The SDK's `SessionReconnectHandler` (removed) retried forever in SDK
1.5.378 (its "exhausted" path was unreachable), recreated sessions by cloning subscriptions the driver never
re-tracked, and kept health `Healthy` throughout — so on docker-dev a stopped opc-plc left nodes Good on their last
value indefinitely and they never recovered. A teardown against a lost session skips the wire deletes and `CloseSession`
(bounded to 5 s otherwise). SDK warnings (keep-alive / publish / channel errors) now reach the driver's own logger,
rate-limited to 20 per minute with a suppressed-count note; the per-driver SDK logger factory is disposed with the
driver.
### Namespace assignment (retired, Gitea #648)
Earlier versions required a per-instance `TargetNamespaceKind` (`Equipment` +
a mandatory `UnsMappingTable`, or `SystemPlatform` + an empty table). Both
options are **removed**: nothing ever read the mapping table beyond the startup
check, and in v3 the raw-to-UNS projection is explicit (`UnsTagReference`), so
the choice carried no behaviour — it only made a config without the key fail
`Initialize`. Remote nodes are authored as `/raw` tags bound by their upstream
`nodeId`; there is no namespace field on the driver, the AdminUI form or the
seed.
Stored `DriverConfig` JSON that still carries `targetNamespaceKind` or
`unsMappingTable` keeps working: the keys are unknown and ignored on parse and
initialise (the AdminUI form drops them on the next save). Pinned by
`OpcUaClientReinitConfigAdoptionTests.Legacy_namespace_keys_are_ignored_by_parse_and_initialise`.
## Capability surface
`OpcUaClientDriver : IDriver, ITagDiscovery, IReadable, IWritable, ISubscribable, IHostConnectivityProbe, IAlarmSource, IDriverConnectionLossSource`
(`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient/OpcUaClientDriver.cs:31`).
| Capability | Path | Notes |
|------------|------|-------|
| `ITagDiscovery` | `DiscoverAsync` (recursive browse) | Mirrors the upstream tree from `BrowseRoot` (default `ObjectsFolder` i=85), bounded by `MaxDiscoveredNodes` / `MaxBrowseDepth` |
| `IReadable` | `ReadAsync` → `Session.ReadAsync` | Upstream `StatusCode`s pass through verbatim (cascading-quality rule) |
| `IWritable` | `WriteAsync` → `Session.WriteAsync` | Passthrough write |
| `ISubscribable` | native OPC UA subscriptions / monitored items | The remote server pushes data changes |
| `IHostConnectivityProbe` | session keep-alive | Host key is the endpoint URL actually connected to after the failover sweep |
| `IAlarmSource` | `SubscribeAlarmsAsync` (EventFilter) + `AcknowledgeAsync` | Subscribes to upstream alarm/condition events and forwards acks |
> **Native alarms (#619).** An alarm raw tag is `TagConfig` `{ "nodeId": "<upstream SourceNode>", "alarm": {...} }`.
> The host subscribes with RawPaths and routes on (driver, RawPath), so the driver matches each
> event's `ConditionId` (then its `SourceNode`) against the tag's authored `nodeId` and reports the **RawPath** as
> `ConditionId`. Author `nodeId` as the upstream **condition** node for a 1:1 mapping (required when one source carries
> several conditions, e.g. Hi + HiHi); authoring the **source** node folds every condition of that source into one
> tag. `Acknowledge` is called on the condition node of the last event seen for the RawPath **with that event's
> EventId** (Part 9 §5.7.3). The event's `ActiveState/Id` + `AckedState/Id` are selected and turned into the
> `Raise`/`Acknowledge`/`Clear`/`Retrigger` kinds the host projector consumes (without a kind no upstream alarm could ever
> show active); the kinds are emitted from the state **last told to the host** per RawPath, so an identical re-delivery
> emits nothing (no re-raise, which would un-ack). An inactive → active+acked move is ONE `ActiveAcknowledged` (#656; it
> used to be `Raise` + `Acknowledge`, a client-visible unacked intermediate); a move into inactive+unacked is ONE
> `InactiveUnacknowledged` (#657; it used to be `Raise`/`Retrigger` + `Clear`, an Active flicker). The first event per
> condition after a start or deploy respawn is flagged `IsRestatement` and states the upstream condition so it lands
> from whatever the host retained: an inactive+acked one goes out as `Clear` + `Acknowledge` (#657; it used to be an
> `Unspecified` the host wrote as "Activated", and a retained-Active host condition stayed Active). So the host writes no
> duplicate row when its condition already shows that state (see `docs/AlarmTracking.md`). Condition **branch** events (non-null `BranchId`) are ignored.
> **`ConditionRefresh`** is called after the event item is created, after a keep-alive outage the session survived, and on a
> `RefreshRequired` event, so a condition already active upstream is reported at subscribe; `RefreshStart`/`RefreshEnd`
> markers are dropped. A server without it (`BadNotSupported`/`BadMethodInvalid`/…) is logged once and tolerated.
> Last-told state survives a re-initialise (the host re-subscribes the same set over nodes it did not rebuild) and is
> forgotten when the subscribed set changes (the host rebuilt, recreating the nodes inactive). Index keys are server-stable (`nsu=`), so a namespace reorder across a re-initialise keeps
> matching. docker-dev seeds an opc-plc driver (`MAIN-opcua`); the alarm tag is
> created only when `@OpcPlcAlarmSourceNodeId` is set in `docker-dev/seed/seed-clusters.sql`.
> This driver does **not** implement `IRediscoverable` — there is no
> push-driven rediscovery signal from a remote OPC UA server in this driver.
### History: not supported (Gitea #655)
This driver does **not** proxy the upstream server's HistoryRead. The server serves
HistoryRead only through the server-wide `IHistorianDataSource` (see `docs/Historian.md`);
drivers carry no history capability, and the former `IHistoryProvider` passthrough
(Raw / Processed / AtTime / Events) was never dispatched to and has been deleted.
`isHistorized` on an OpcUaClient tag means OtOpcUa records the value into the historian
from now on (numeric only), not that upstream history is forwarded. A tag without
`isHistorized` has no HistoryRead access bit and answers `BadHistoryOperationUnsupported`.
If upstream-history proxying is wanted later, it needs a new intent key, a dispatch path
through `DriverHostActor`, and a continuation-point rework — see #655.
### Certificate trust
`AutoAcceptCertificates` accepts any self-signed / untrusted server certificate.
It is **dev-only** — leave it `false` in production so a MITM against the
opc.tcp channel fails closed. The SDK rejects a **revoked** certificate
(`BadCertificateRevoked` / `BadCertificateIssuerRevoked`) before the auto-accept handler runs, and the handler
also refuses them explicitly — defence in depth (#277), not a behaviour change.
`CertificateValidation` (defaults change nothing):
| Key | Default | Meaning |
|---|---|---|
| `rejectUnknownRevocationStatus` | `false` | Reject a server certificate whose revocation status cannot be determined (no CRL for its issuer, or a stale one). Leave `false` for brownfield sites without CRL infrastructure. **Only effective with `autoAcceptCertificates` off** — the auto-accept handler accepts every suppressible error, including revocation-unknown. |
| `issuerStorePath` | `null` (= `%LocalAppData%/OtOpcUa/pki/issuers`) | Directory used as the trusted-issuer store. The SDK reads issuer CRLs (`*.crl`) from its `crl/` sub-folder, so this is how an operator points the driver at a managed CRL set. |
### Subscription tuning (#273)
The per-subscription parameters that used to be hardcoded are driver options; the defaults are the old values.
| Key | Default | Notes |
|---|---|---|
| `subscriptionPublishingInterval` | `null` | A .NET `TimeSpan` string (`"00:00:02"`), not a number. `null` = the interval the runtime requests per subscribe (floored at 50 ms). When set it overrides that value (floor still applies); monitored-item sampling follows it. |
| `subscriptionKeepAliveCount` | `10` | `>= 1`. |
| `subscriptionLifetimeCount` | `1000` | Must be `>= 3 x` keep-alive count (Part 4 §5.13.2). |
| `subscriptionMaxNotificationsPerPublish` | `0` | `0` = server decides. |
| `subscriptionPriority` | `0` | `0`-`255`. |
Out-of-range values (and a non-absolute `discoveryUrl`) are rejected when the options are loaded — driver creation / `InitializeAsync` fails once with a clear message rather than the driver faulting and retrying forever. The alarm subscription uses the same counts.
*Per-tag* tuning (deadband / sampling interval / queue size, #274) is not implemented — it needs an
`ISubscribable` signature change on Core.
### Server OperationLimits (#275)
Nothing driver-side: the SDK session already honours the remote server's
`ServerCapabilities/OperationLimits`. `Opc.Ua.Client.Session` derives from `Opc.Ua.SessionClientBatched`,
fetches the limits on open (`FetchOperationLimitsAsync`) and splits Read / Write / CreateMonitoredItems / Browse /
HistoryRead requests that exceed them (a limit of `0` = unlimited). The driver issues one logical call per
operation and a unit test pins the `Session : SessionClientBatched` relationship so an SDK change that dropped
it is caught. (A driver-side splitter was tried and removed: it duplicated the SDK and, on a stalled link, held
the driver gate for chunks x timeout.)
### Discovery URL (#278)
`discoveryUrl` (default `null`, e.g. `opc.tcp://lds:4840`): at `InitializeAsync` the driver runs `FindServers` on it
and `GetEndpoints` on every returned server, keeping the endpoints matching `securityPolicy` + `securityMode`.
Discovered URLs are tried **after** `endpointUrls`/`endpointUrl` (case-insensitive de-dup) — discovery can add
fallbacks but never outranks or replaces the configured server. Because an LDS commonly registers several servers
(identical line PLCs, a gateway plus a historian) and the first to accept a connection would be bound silently:
- `discoveryServerUri` set: only endpoints of the server with that ApplicationUri are used.
- unset and exactly one distinct server discovered: that server is used.
- unset and more than one: the connect attempt **fails** with an error naming the discovered ApplicationUris and
telling the operator to set `discoveryServerUri`.
A discovery *network* failure (LDS down) is logged and non-fatal — the static list is used (note it is retried on
every `InitializeAsync`, including comms-loss reconnects). The discovery channel itself is always unsecured (spec).
### Diagnostics counters (#276)
Session/publish events are published on the shared OTel meter as the counter
`otopcua.driver.opcuaclient.events`, tagged `driver_instance` (the driver instance id) and `event` =
`publish_response`, `notification` (items), `data_change`, `bad_status_value`, `publish_error`,
`keepalive_miss`, `keepalive_recovered` (a bad keep-alive followed by a good one on the same session),
`stale_notification_dropped` (a late replay dropped inside the post-recovery window, see above). A climbing
`keepalive_miss` / `keepalive_recovered` rate is the signature of a flapping upstream (`reconnect_*` were removed with
the reconnect handler, #670). They are not part of `DriverHealth` or the
`/hosts` panel.
## Testing
- **Unit tests** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.OpcUaClient.Tests/`
cover the session lifecycle, namespace remapping, alarm/history passthrough,
and config binding against a faked SDK session.
- **Integration fixture** — exercises the driver against a reference OPC UA
server (opc-plc) on the shared docker host; see
[OpcUaClient-Test-Fixture.md](OpcUaClient-Test-Fixture.md) for the coverage map.
- **Wire tests against the in-process server** — `tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests/`
`OpcUaClientDriver*WireTests` (no Docker). `OpcUaClientDriverStallWireTests` (#676) covers the in-place blip that
used to be live-gate-only: the driver connects through `TcpStallProxy`, an in-test TCP forwarder whose pause holds
every byte without closing anything (which only works because of the endpoint rewrite above); it asserts one Bad,
a frozen read stamp, recovery on the SAME session, the identical value republished Good, a change published right
after recovery still arriving, and no source-time regression once the SDK's late backlog flush has arrived. Its
second test uses `HardClose` (reset every connection, refuse new ones) — the shape of a real process stop — and
asserts the live-gate status sequence, that the SDK never reconnects on its own once the proxy accepts again,
`ConnectionLost` exactly once, and the re-initialise bringing the identical value back Good.
`OpcUaClientDriverReconnectWireTests` covers the server restart (incl. the `BadServerHalted` → `ConnectionLost` signal)
and the subscription-lost case.
## Further reading
- [`docs/v2/driver-specs.md §8`](../v2/driver-specs.md) — full per-field spec,
namespace-assignment rules, and cascading-quality detail
- [OpcUaClient-Test-Fixture.md](OpcUaClient-Test-Fixture.md) — test-harness map
- [Client.CLI.md](../Client.CLI.md) — general-purpose OPC UA client CLI for
ad-hoc browsing of any endpoint