Joseph Doherty 5ea57d2d70 Task #138 — Modbus addressing grammar docs + e2e
Closes the docs/e2e end of the Modbus addressing line shipped across
#136-#145.

Docs:

- docs/v2/modbus-addressing.md (new) — full grammar reference.
  Region+offset (Modicon 5-digit / 6-digit / mnemonic), bit suffix,
  type codes (BOOL / I / UI / DI / UDI / LI / ULI / F / D / BCD / LBCD /
  STR<n>), all four byte-order mnemonics (ABCD / CDAB / BADC / DCBA),
  array-count semantics, family-native syntax (DL205 V/Y/C/X/SP and
  MELSEC D/M/X/Y with hex-vs-octal sub-family selection), driver-instance
  options (KeepAlive / Reconnect / IdleDisconnect, MaxCoilsPerRead and
  FC15/16 forcing, Deadband + WriteOnChangeOnly, MaxReadGap +
  CoalesceProhibited, multi-unit IPerCallHostResolver). Includes a worked
  JSON DTO example mixing AddressString + structured tag forms.

- docs/Driver.Modbus.Cli.md — appended a "v2 addressing grammar" section
  pointing users at the full reference, with quick-reference examples.

- Vendor-compatibility caveat documented: type codes and byte-order
  mnemonics were synthesised from training-era vendor docs (Wonderware
  DASMBTCP, Kepware KEPServerEX, Ignition, Matrikon, OAS) and should be
  verified against current vendor manuals before locking for production.

E2E tests (4 new AddressingGrammarTests in IntegrationTests):
- Modicon 5-digit and 6-digit forms map to identical wire offsets.
- Float32 + WordSwap (CDAB) round-trips end-to-end through the
  pymodbus simulator.
- Int16[5] array round-trips as a typed short[] surface.
- Block-read coalescing produces a wire-acceptable PDU when MaxReadGap=5
  bridges three nearby tags.

All tests skip gracefully when the pymodbus simulator at localhost:5020
is unreachable (matches the existing ModbusSimulatorFixture pattern).

Final test count across the Modbus addressing surface:
- 107 ModbusAddressing.Tests (parser + family + Modicon)
- 231 Driver.Modbus.Tests (driver, byte order, array, multi-unit, coalescing,
  protocol, subscribe, connection options)
- 110 Admin.Tests (incl. ModbusOptionsViewModel defaults pinning)
- 4 new AddressingGrammar integration tests (skip when sim down)
2026-04-25 00:32:27 -04:00

196 lines
7.0 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Modbus tag-addressing reference
Foundational doc for the Modbus addressing grammar shipped across #136#144.
Covers the address-string parser (`ModbusAddressParser`) that the wire driver
and the Admin UI both consume, the per-tag suffix modifiers, and the family-
native branch.
## Grammar
```
<region><offset>[.<bit>][:<type>[<len>]][:<order>][:<count>]
```
Each field is optional from left to right; the parser fills defaults.
### Region + offset
Three accepted forms — pick whichever matches your tag spreadsheet's
convention. All three resolve to the same `(Region, ushort PduOffset)`
on the wire.
| Form | Example | Means |
|---|---|---|
| Modicon 5-digit | `40001` | Holding register 1 (PDU 0) |
| Modicon 6-digit | `400001` | Holding register 1 (PDU 0); supports up to `465536` (PDU 65535) |
| Mnemonic | `HR1`, `IR1`, `C100`, `DI1` | Same regions; `1`-based register number |
Modicon leading-digit → region:
| Digit | Region | OPC UA wire FC |
|---|---|---|
| `0` | Coils | FC01 / FC05 / FC15 |
| `1` | DiscreteInputs | FC02 (read-only) |
| `3` | InputRegisters | FC04 (read-only) |
| `4` | HoldingRegisters | FC03 / FC06 / FC16 |
### Bit suffix `.N`
`40001.5` = bit 5 (LSB-first) of HR[0]. Implies `DataType=BitInRegister`;
mixing with an explicit type or array-count is rejected.
### Type code `:T`
| Code | Type | Registers |
|---|---|---|
| `BOOL` | Boolean | 1 (region must be Coils / DiscreteInputs) |
| `I` | Int16 | 1 |
| `UI` | UInt16 | 1 |
| `DI`, `L` | Int32 | 2 |
| `UDI`, `UL` | UInt32 | 2 |
| `LI` | Int64 | 4 |
| `ULI` | UInt64 | 4 |
| `F` | Float32 | 2 |
| `D` | Float64 | 4 |
| `BCD` | 16-bit BCD | 1 |
| `LBCD` | 32-bit BCD | 2 |
| `STR<len>` | ASCII string, `len` chars (2 chars / register) | `ceil(len/2)` |
Default when omitted:
- Coils / DiscreteInputs → `BOOL`
- HoldingRegisters / InputRegisters → `I` (Int16)
### Byte order `:O`
| Mnemonic | Meaning | Wire |
|---|---|---|
| `ABCD` | Big-endian (Modbus spec default) | `[A,B,C,D]` |
| `CDAB` | Word swap (Siemens, several AB) | `[C,D,A,B]` |
| `BADC` | Byte swap (legacy little-endian-internal devices) | `[B,A,D,C]` |
| `DCBA` | Full reverse (some EtherNet/IP gateways) | `[D,C,B,A]` |
For 8-byte values (Int64 / Float64) the same labels apply pairwise.
### Array count `:N`
`40001:F:5` = `Float32[5]` (consumes HR[0..9]). Array + bit suffix is
rejected. Strings are not arrays.
### Composition
The 3-field shorthand `40001:F:5` is parsed as `(type=F, count=5)` because
`5` isn't a valid byte-order mnemonic. Use the explicit 4-field form
`40001:F:CDAB:5` when you need a non-default order.
## Family-native syntax (#144)
When the driver instance has `Family != Generic`, the parser tries the
family's native syntax FIRST, then falls back to Modicon / mnemonic.
### DL205 (AutomationDirect DirectLOGIC)
| Form | Example | Mapping |
|---|---|---|
| `Vnnnn` (octal) | `V2000` | HoldingRegisters[1024] (octal 2000 = decimal 1024) |
| `Ynn` (octal) | `Y17` | Coils[2048 + 15] (Y-output base + offset) |
| `Cnn` (octal) | `C100` | Coils[3072 + 64] (C-relay base + offset) |
| `Xnn` (octal) | `X17` | DiscreteInputs[15] |
| `SPnn` (octal) | `SP10` | DiscreteInputs[1024 + 8] |
**Cross-family ambiguity**: `C100` means Coils[99] under `Generic`
(mnemonic) but Coils[3136] under `DL205`. Per-driver Family choice
disambiguates.
### MELSEC (Mitsubishi)
| Form | Example | Mapping (sub-family Q_L_iQR / F_iQF) |
|---|---|---|
| `Dnnn` (decimal) | `D100` | HoldingRegisters[100] |
| `Mnnn` (decimal) | `M50` | Coils[50] |
| `Xnn` | `X20` | DiscreteInputs[32 hex / 16 octal] |
| `Ynn` | `Y20` | Coils[32 hex / 16 octal] |
X / Y digit interpretation depends on `MelsecSubFamily`:
- `Q_L_iQR` → hex (default)
- `F_iQF` → octal
Bank-base offsets default to 0 in the grammar string. Sites with non-zero
"Modbus Device Assignment" bases use the structured tag form.
## Driver-instance options
Beyond per-tag addressing, `ModbusDriverOptions` exposes (#139#143):
### Connection (#139)
- `KeepAlive { Enabled, Time, Interval, RetryCount }` — TCP-level probes.
Defaults match the historical PR 53 wire output (Enabled=true, Time=30s,
Interval=10s, RetryCount=3).
- `IdleDisconnectTimeout` — proactively close + reconnect after this much
socket idle time. Default null = disabled.
- `Reconnect { InitialDelay, MaxDelay, BackoffMultiplier }` — geometric
backoff for the post-drop reconnect loop. Default
`(0, 30s, 2.0)` = immediate first retry, geometric thereafter.
### Protocol (#140)
- `MaxCoilsPerRead` (default 2000) — separate cap for FC01/FC02 coil reads.
- `UseFC15ForSingleCoilWrites` — force FC15 (write multiple coils
qty=1) for single-coil writes. Safety/audit PLCs may require this.
- `UseFC16ForSingleRegisterWrites` — same for FC16 vs FC06.
- `DisableFC23` — kill switch for FC23 (currently unused; reserved).
### Subscribe (#141)
- Per-tag `Deadband` — suppress sub-threshold publishes on numeric tags.
- `WriteOnChangeOnly` (driver-level) — short-circuit identical-value
writes. Cache invalidates on read-divergence.
### Multi-unit (#142)
- Per-tag `UnitId` — overrides the driver-level UnitId in the MBAP
header. Required for one-Ethernet-gateway / N-RTU-slave deployments.
- `IPerCallHostResolver.ResolveHost` returns `host:port/unitN` per tag so
per-PLC circuit breakers fire per slave.
- Per-tag `CoalesceProhibited` — escape hatch for #143's planner (read
this tag in isolation regardless of `MaxReadGap`).
### Block-read coalescing (#143)
- `MaxReadGap` (default 0 = off) — gap budget the planner is willing to
bridge between adjacent register tags. With `MaxReadGap=10`, three tags
at HR 100/102/110 collapse into one FC03 of quantity 11.
## JSON DTO shape
The factory accepts both the structured form (legacy) and the new
`AddressString` form per-tag. Mix freely — newer pasted rows use the
grammar string; legacy rows keep the structured fields.
```json
{
"host": "10.1.2.3",
"port": 502,
"unitId": 1,
"family": "DL205",
"keepAlive": { "enabled": true, "timeMs": 30000, "intervalMs": 10000, "retryCount": 3 },
"idleDisconnectMs": 120000,
"reconnect": { "initialDelayMs": 0, "maxDelayMs": 30000, "backoffMultiplier": 2.0 },
"maxCoilsPerRead": 2000,
"writeOnChangeOnly": false,
"maxReadGap": 8,
"tags": [
{ "name": "Temp", "addressString": "V2000:F:CDAB" },
{ "name": "Setpoint", "addressString": "40001:I" },
{ "name": "Outputs", "addressString": "Y0:5" },
{ "name": "AlarmCount", "region": "HoldingRegisters", "address": 200, "dataType": "Int16", "deadband": 5.0 }
]
}
```
## Vendor compatibility caveat
The exact spelling of type codes (e.g. `I` vs `INT`, `BCD` vs `L_BCD`) and
the byte-order mnemonics were synthesised from training-era vendor docs
(Wonderware DASMBTCP, Kepware KEPServerEX, Ignition, Matrikon, OAS).
Before locking the grammar for a production deployment, verify against
the current Kepware "Modbus Ethernet Driver Help" PDF and Ignition's
"Modbus Addressing" user-manual page — if a critical tool's mnemonics
have shifted, add aliases in `ModbusAddressParser.TryParseType` rather
than asking users to rewrite spreadsheets.