# AbCip — ControlLogix HSBY paired-IP support
|
|
|
|
PR abcip-5.1 adds **non-transparent** HSBY (Hot-Standby) awareness to the AB
|
|
CIP driver. Each device may declare a partner gateway; when both gateways are
|
|
up the driver concurrently probes a role tag on each chassis and reports
|
|
which one is currently Active.
|
|
|
|
PR abcip-5.1 only **gathers + reports** the role. PR abcip-5.2 is the
|
|
follow-up that wires the resolved active address into
|
|
`AbCipDriver.ResolveHost` so reads and writes route to whichever chassis is
|
|
Active without operator intervention.
|
|
|
|
## When to use HSBY paired IPs
|
|
|
|
You have a redundant **ControlLogix** chassis pair (1756-RM redundancy
|
|
module, two CPUs, one acting + one standby) and the SCADA / OPC UA layer
|
|
needs to keep talking to *whichever chassis is currently Active* without an
|
|
operator manually re-pointing the connection.
|
|
|
|
Pre-5.1 the driver only knew about a single `HostAddress`. After a
|
|
hot-standby switch-over, the standby (now Active) carried a **different IP**
|
|
and the driver kept probing the dead-but-was-Active address until someone
|
|
edited the config.
|
|
|
|
PR abcip-5.1 closes the visibility half of that gap by reading the role tag
|
|
on both chassis. PR abcip-5.2 closes the routing half by re-pointing
|
|
`ResolveHost` at the Active address each tick.
|
|
|
|
## Configuration
|
|
|
|
```jsonc
|
|
{
|
|
"Devices": [
|
|
{
|
|
"HostAddress": "ab://10.0.0.5/1,0",
|
|
"PartnerHostAddress": "ab://10.0.0.6/1,0",
|
|
"Hsby": {
|
|
"Enabled": true,
|
|
"RoleTagAddress": "WallClockTime.SyncStatus",
|
|
"ProbeIntervalMs": 2000
|
|
}
|
|
}
|
|
]
|
|
}
|
|
```
|
|
|
|
| Field | Default | Notes |
|
|
|---|---|---|
|
|
| `PartnerHostAddress` | `null` | Canonical `ab://gateway[:port]/cip-path` of the partner chassis. `null` = no HSBY pair; the driver behaves exactly like every pre-5.1 build. |
|
|
| `Hsby.Enabled` | `false` | Master switch. When `false` (or `Hsby` omitted) no role probing happens, even if `PartnerHostAddress` is set. |
|
|
| `Hsby.RoleTagAddress` | `WallClockTime.SyncStatus` | Address of the role tag on each chassis. See [role-tag detection matrix](#role-tag-detection-matrix). |
|
|
| `Hsby.ProbeIntervalMs` | `2000` | How often each chassis is sampled. 2 s is a good default — tight enough to detect a switch-over within one Admin-UI refresh, loose enough to leave headroom for the regular probe loop. |
|
|
|
|
## Feature-flag gate (`Redundancy.Hsby.Enabled`)
|
|
|
|
`Hsby.Enabled = false` (the default) is the off-switch for the entire
|
|
feature. The role-probe loop never starts, the diagnostics keys are not
|
|
emitted, and the driver behaves identically to a pre-5.1 build. This is the
|
|
gate to flip when an operator wants to roll the feature out cautiously
|
|
across a fleet — set `Hsby.Enabled = true` per-device in driver config (no
|
|
build flag, no env var).
|
|
|
|
When the gate is on but the partner gateway is unreachable, the role-probe
|
|
loop reports `HsbyRole.Unknown` for the partner each tick. The primary's
|
|
role still drives the active-chassis resolution; the operator sees the
|
|
partner's role as Unknown in the Admin UI / driver diagnostics, which is the
|
|
correct surface for "we can't reach the standby chassis right now."
|
|
|
|
## Role-tag detection matrix
|
|
|
|
| Firmware / fronts | Address | Decode |
|
|
|---|---|---|
|
|
| **v20 / v24 / v32+ ControlLogix HSBY** | `WallClockTime.SyncStatus` (DINT) | `0` = Standby, `1` = Synchronized / Active, `2` = Disqualified, anything else = Unknown |
|
|
| **PLC-5 / SLC500 status-byte fallback** | `S:34` Module Status word | bit 0 = "this chassis is Active". Bit set → `Active`; clear → `Standby` |
|
|
| **Custom user role tag** | any DINT-typed CIP path | Same matrix as `WallClockTime.SyncStatus` (0 / 1 / 2). Out-of-range values → Unknown. |
|
|
|
|
`AbCipHsbyRoleProber.MapValueToRole` is the value-to-role mapper; unit tests
|
|
in `tests/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests/AbCipHsbyTests.cs` pin every
|
|
row of the matrix.
|
|
|
|
## What gets reported
|
|
|
|
The driver surfaces three diagnostics counters per HSBY-enabled device
|
|
(visible via `driver-diagnostics` RPC + the Admin UI):
|
|
|
|
| Counter | Value |
|
|
|---|---|
|
|
| `AbCip.HsbyActive` | `1` if primary is Active, `2` if partner is Active, `0` if neither (or HSBY off) |
|
|
| `AbCip.HsbyPrimaryRole` | `(int)HsbyRole` — `0` = Unknown, `1` = Active, `2` = Standby, `3` = Disqualified |
|
|
| `AbCip.HsbyPartnerRole` | Same encoding as `HsbyPrimaryRole`, observed on the partner chassis |
|
|
|
|
When more than one HSBY pair is configured on the same driver instance the
|
|
flat keys are scoped per primary host: `AbCip.HsbyActive[ab://10.0.0.5/1,0]`,
|
|
etc.
|
|
|
|
The `DeviceState.ActiveAddress` field (internal; surfaced via
|
|
`HsbyActive` diagnostics) is the address PR 5.2 will route through
|
|
`ResolveHost`.
|
|
|
|
### Active-resolution rules
|
|
|
|
| Primary role | Partner role | `ActiveAddress` resolution |
|
|
|---|---|---|
|
|
| Active | Standby / Disqualified / Unknown | primary |
|
|
| Standby / Disqualified / Unknown | Active | partner |
|
|
| Active | Active (split-brain) | **primary wins**, warning logged |
|
|
| Standby + Standby | Standby + Standby | `null` (PR 5.2 will surface as `BadCommunicationError`) |
|
|
| Unknown + Unknown | Unknown + Unknown | `null` |
|
|
|
|
Split-brain (both chassis claim Active simultaneously) is a real
|
|
production failure mode — typically a redundancy-module misconfiguration or
|
|
a partial network split. The driver picks primary deterministically + emits
|
|
a warning through `AbCipDriverOptions.OnWarning` so operators see it in the
|
|
log.
|
|
|
|
## CLI flags
|
|
|
|
The `otopcua-abcip-cli` tool exposes the HSBY plumbing through two surfaces
|
|
(see [Driver.AbCip.Cli.md](../Driver.AbCip.Cli.md) for the full CLI guide):
|
|
|
|
- `--partner <gateway>` — global flag on every command. Sets
|
|
`PartnerHostAddress` + auto-enables `Hsby.Enabled = true` so the role
|
|
probe runs alongside any read / write / subscribe.
|
|
- `hsby-status` — dedicated command that prints which chassis is
|
|
currently Active. Reads the role tag on both gateways for a few ticks +
|
|
prints the `(primary, partner, active)` tuple.
|
|
|
|
```powershell
|
|
# Print which chassis is Active right now
|
|
otopcua-abcip-cli hsby-status -g ab://10.0.0.5/1,0 --partner ab://10.0.0.6/1,0
|
|
|
|
# Subscribe through the active chassis (PR 5.2 follow-up — today the
|
|
# subscribe stays pointed at the primary; the role probe runs alongside).
|
|
otopcua-abcip-cli subscribe -g ab://10.0.0.5/1,0 --partner ab://10.0.0.6/1,0 \
|
|
-t Motor01_Speed --type Real -i 500
|
|
```
|
|
|
|
## Test coverage
|
|
|
|
- **Unit** (`tests/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Tests/AbCipHsbyTests.cs`):
|
|
- Pure `MapValueToRole` matrix (WallClockTime.SyncStatus + S:34 bit
|
|
mask + Unknown values).
|
|
- End-to-end driver loop: primary Active / partner Standby resolves to
|
|
primary; both Active resolves to primary with a warning; both
|
|
Standby clears `ActiveAddress`; primary read failure routes to
|
|
partner.
|
|
- Diagnostics surface (`AbCip.HsbyActive` / `HsbyPrimaryRole` /
|
|
`HsbyPartnerRole`).
|
|
- DTO JSON round-trip (`PartnerHostAddress` + `Hsby.{Enabled,
|
|
RoleTagAddress, ProbeIntervalMs}` survive deserialise → driver →
|
|
`DeviceState`).
|
|
- `Hsby.Enabled = false` → no role probing.
|
|
- **Integration** (`tests/ZB.MOM.WW.OtOpcUa.Driver.AbCip.IntegrationTests/AbCipHsbyRoleProberTests.cs`):
|
|
- **Skipped by default** (`Assert.Skip`) — `ab_server` cannot emulate
|
|
a ControlLogix HSBY pair (no `WallClockTime.SyncStatus`, no second
|
|
chassis concept). The Docker `paired` profile (PR 5.1) brings up two
|
|
`ab_server` instances + a stub `hsby-mux` sidecar so the topology is
|
|
documented, but PR 5.2 follow-up needs a patched `ab_server` image
|
|
that actually serves the role tag before the integration test can
|
|
assert anything against the wire.
|
|
- Trait `Category=Hsby` so `dotnet test --filter Category=Hsby` finds
|
|
this test once it's promoted.
|
|
|
|
## Follow-ups (PR 5.2 + beyond)
|
|
|
|
- **PR 5.2** — wire `ActiveAddress` into `ResolveHost` so reads/writes
|
|
route to the live chassis automatically. Today's PR only **gathers** the
|
|
role.
|
|
- **Patched `ab_server` image** — add a writable `WallClockTime.SyncStatus`
|
|
tag (or a separate Python shim) so the Docker `paired` profile can
|
|
exercise the wire-level role probe.
|
|
- **`hsby-mux` REST endpoint** — `POST /flip {"active": "primary"}` writes
|
|
`1` to the chosen chassis + `0` to the other so integration tests can
|
|
drive switch-overs deterministically.
|
|
- **GuardLogix HSBY** — same role-tag plumbing applies; verify against a
|
|
real 1756-L8xS pair when one is on-site.
|
|
|
|
## See also
|
|
|
|
- [`docs/Driver.AbCip.Cli.md`](../Driver.AbCip.Cli.md) — `--partner` flag +
|
|
`hsby-status` command reference
|
|
- [`docs/drivers/AbServer-Test-Fixture.md`](AbServer-Test-Fixture.md) §"What
|
|
it does NOT cover" — HSBY entry
|
|
- [`docs/Redundancy.md`](../Redundancy.md) — server-level (OPC UA-stack)
|
|
redundancy; HSBY is the **driver-level** companion
|