test(validation): ScadaBridge consumer matrix uses a production-length API key; SDK 2 consumer run (ScadaBridge#125)
The consumer matrix minted a 55-character otua_matrix_ key, which stays
under SDK 2's 64-byte RsaEncryptedSecret threshold and so could not show
lmxopcua#880 from the consumer side. It now uses the ApiKeySecret.Generate
shape (65 characters), as opcua-sdk-compatibility already does.

README records the 2026-11-12 run with ScadaBridge on SDK 2.0.1
(a2e9d718): matrix 11/11 x3 modes on 83ed880e and 412da27c, ACL off and
on; 8/8 trust controls fail closed; failover 8/8; a mutation with the SDK
default UserName handler fails every baseline leg with
BadIdentityTokenInvalid.

Claude-Session: https://claude.ai/code/session_01GT67ACmpMR7b9LGRPLijMi
2026-11-12 22:22:45 -05:00

117 lines
7.3 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Actual ScadaBridge consumer compatibility
This isolated process references the real ScadaBridge `OpcUaDataConnection` and
`RealOpcUaClient`, with their own dependency graph. It never loads the candidate
SDK into that process. The verified consumer source is
`0e89966da670e289bd875166295bb0e85d8cf8b2`, pinned to SDK 1.5.378.106.
Build with an explicit clean consumer checkout:
```sh
dotnet build scripts/validation/scadabridge-sdk-compatibility/Probe.csproj \
-c Release -p:ScadaBridgeSourceRoot=/absolute/ScadaBridge
```
First build the separate application hosts with the parent
`scripts/e2e/test-opcua-sdk-compatibility.ps1` harness. Then choose a new output
directory and pass its original and candidate `ProcessHost.dll` paths:
```sh
python3 scripts/validation/scadabridge-sdk-compatibility/run.py \
--baseline-host /absolute/matrix/build-baseline/bin/Release/net10.0/ProcessHost.dll \
--candidate-host /absolute/matrix/build-candidate/bin/Release/net10.0/ProcessHost.dll \
--probe scripts/validation/scadabridge-sdk-compatibility/bin/Release/net10.0/Probe.dll \
--results /absolute/fresh-consumer-evidence
```
The helper runs each application version with None, Sign and SignAndEncrypt,
plus two trust negative controls per secure profile (server does not trust the
client, client does not trust the server) that must fail closed. None and Sign
are enabled only in their own test fixtures (`OPCUA_MATRIX_SERVER_SECURITY=none|sign`);
the ordinary compatibility host remains strict SignAndEncrypt. Before each secure
leg the probe's `prepare` step provisions the consumer identity through
ScadaBridge's own certificate code and exports only its public certificate, which
the runner places in the server's trusted store before the server starts.
`OPCUA_MATRIX_ACL=off` disables the server's node-ACL check. The fixture's `Eq` equipment folder is placed in the
authority snapshot (`unsFolderScopes`, as a deployed generation does since lmxopcua#808, fixed in lmxopcua#888), so
the UNS cases pass with the ACL on and off; an unplaced `Unplaced` UNS folder is kept as a negative control that the
Shared client leg requires to stay denied with the ACL on. The task key is
generated per process pair, issuer/trusted/rejected stores are task-local, and
server public certificates are explicitly copied. Autoaccept remains false.
Never commit an entire output directory: it contains the fixture's private PKI.
The consumed subset covers API-key activation, raw/UNS scalar and Int32[]
roundtrips, durable hierarchical browse including the native alarm, data quality
and timestamps on raw and UNS subscriptions, alarm filter/ConditionRefresh,
disconnect/reconnect, and (ScadaBridge#125) a Server-object alarm subscription on
the reconnected session whose ConditionRefresh must replay the active native
condition (11 cases per trusted leg). The API key has the production
`ApiKeySecret.Generate` shape and length, 65 characters (lmxopcua#880): the
55-character `otua_matrix_` key used before stayed under SDK 2's 64-byte
`RsaEncryptedSecret` threshold, so it could not show whether an SDK 2 consumer
still sends the password in a format an SDK 1.5 server decrypts. History
and Part 9 acknowledgment are not exposed by the inspected consumer interfaces;
the parent Shared/CLI matrix covers those application services instead.
ScadaBridge#121 (consumer never configured an application certificate) is
fixed in ScadaBridge `ff835447`/`36c64a6b`. Re-run 2026-11-12 with ScadaBridge
`424db155`: None, Sign and SignAndEncrypt 9/9 against the SDK 1.5.378 baseline
(`83ed880e`), the SDK 2.0.1 candidate (`ebdc5892`) and master `182fb353` with
ACL off; all trust negative controls failed closed. The runner retains the
nonzero result and each actual failure; it does not loosen trust or change
expected results to return success. No ScadaBridge production source or user PKI is modified.
## Redundancy failover (ScadaBridge#125)
`run.py` also runs a `failover` suite (`--suites matrix,failover`, both by
default; `--versions candidate` runs one application version only). Each leg
starts two independent servers and runs `Probe failover <primary> <backup>
<mode> <dir>`, which drives ScadaBridge's own `DataConnectionActor` (the
production primary/backup state machine, the real `DataConnectionFactory`,
production `DataConnectionOptions` defaults, `FailoverRetryCount = 3`). Once the
probe has a steady primary (Good values on a raw and a UNS tag, a write, the
Server-object alarm subscription with its ConditionRefresh) it writes
`primary-ready`; the runner then loses the primary and writes `primary-killed`.
The probe must then see Bad quality pushed, "Connected to backup", Good values
whose first value is the backup's own (proving the source), a fresh
ConditionRefresh replaying the native condition, and a write through the backup.
Two loss shapes run per security mode (`--failover-modes None,SignAndEncrypt`,
`--failover-loss kill,freeze`):
- `kill` — SIGKILL; the OS closes the primary's sockets, so the client sees the loss at once.
- `freeze` — SIGSTOP; the sockets stay open and silent (hung host / dead link), so only the
consumer's session keep-alive can detect it.
ScadaBridge does not read `ServiceLevel`/`ServerRedundancy`: its failover is
endpoint-level (primary/backup connection details), so two independent fixture
servers exercise exactly what it consumes. `rig-failover.sh <Probe.dll> <dir>`
runs the same probe against the real local docker-dev pair (central-1 `:4840`,
central-2 `:4841`), `docker kill`s central-1 once the primary is steady and
starts it again afterwards. The rig admits anonymous sessions read-only and has
no active native alarm, so that variant checks values and ConditionRefresh
completion only. Local docker-dev only; never point it at a wonder box.
Run 2026-11-12 (ScadaBridge#125) with ScadaBridge `94ae1860` (SDK client
1.5.378.106), ACL off, against the SDK 1.5.378.182 baseline (`83ed880e`) and
master `a28adba2` (SDK 2.0.1): matrix 11/11 in None, Sign and SignAndEncrypt on
both, all 8 trust controls failed closed (0x80130000 / 0x801A0000); failover 8/8
legs (11/11 cases each). Loss-to-backup timings are the same on both versions:
`kill` about 20 s (three 5 s reconnect attempts, then the backup), `freeze` about
20 s to detect and 86–130 s to reach the backup, because each reconnect attempt
waits out a connect timeout against the silent primary. `rig-failover.sh` passed
9/9 against the docker-dev pair (image SDK 2.0.1), central-1 killed, about 20 s
to central-2.
Run 2026-11-12 (ScadaBridge#125) with the consumer itself on SDK **2.0.1**
(ScadaBridge `731d1ed7`, on main as `a2e9d718`; the DCL sends UserName passwords in the
legacy RSA format), 65-character key, against the SDK 1.5.378 baseline
(`83ed880e`) and master `412da27c` (SDK 2.0.1): matrix 11/11 in None, Sign and
SignAndEncrypt on both with the ACL off and on, all 8 trust controls failed
closed (0x80130000 / 0x801A0000), failover 8/8 legs. `kill` reaches the backup
in about 20 s as before; `freeze` is now detected in about 15 s (SDK 2
keep-alive; about 20 s on the SDK 1.5 client) and reaches the backup in 81–125 s.
A mutation run with the consumer's UserName identity reverted to the SDK 2
default handler fails every trusted leg against the baseline with
`BadIdentityTokenInvalid` (0x80200000) and passes against master, which is
lmxopcua#880 reproduced from the consumer side.