365 lines
19 KiB
C#
365 lines
19 KiB
C#
using Shouldly;
|
|
using Xunit;
|
|
using ZB.MOM.WW.OtOpcUa.Core.Abstractions;
|
|
using S7DataItem = global::S7.Net.Types.DataItem;
|
|
using S7NetDataType = global::S7.Net.DataType;
|
|
|
|
namespace ZB.MOM.WW.OtOpcUa.Driver.S7.IntegrationTests.S7_1500;
|
|
|
|
/// <summary>
|
|
/// Live gate for the read-batching layer: the <see cref="S7ReadSpanPlanner"/> block-read pass
|
|
/// (16-byte gap / 220-byte span defaults) and the multi-var leftover pass, both exercised against
|
|
/// the real python-snap7 S7-1500 fixture rather than a fake. The span defaults were chosen
|
|
/// analytically and the multi-var batching shipped with unit coverage only; this suite is what
|
|
/// proves they behave on real S7comm wire.
|
|
/// </summary>
|
|
/// <remarks>
|
|
/// <para>
|
|
/// <b>Live-gate record.</b> Run 2026-08-17 against <c>10.100.0.35:1102</c>
|
|
/// (<c>otopcua-python-snap7-s7_1500</c>, profile <c>Docker/profiles/s7_1500.json</c>):
|
|
/// <b>PASSED</b> — 3 tests, 0 failed, 0 skipped. Grouped batch collapsed 10 tags to 3 wire
|
|
/// requests (2 block reads + 1 three-item multi-var) and matched the ungrouped 10-request
|
|
/// batch value-for-value and type-for-type. No behavioural difference between the planner's
|
|
/// analytic model and real wire was found.
|
|
/// </para>
|
|
/// <para>
|
|
/// <b>What the layout buys.</b> The ten tags are positioned so the planner's rules produce a
|
|
/// known, non-trivial partition rather than one that would pass by accident:
|
|
/// </para>
|
|
/// <list type="bullet">
|
|
/// <item>
|
|
/// <b>Cluster A</b> (<c>DB1.DBW300 … DB1.DBD316</c>) — five tags whose largest hole is 5
|
|
/// bytes, so all five merge into ONE 20-byte span under the 16-byte gap budget. The
|
|
/// holes are seeded with poison (<c>0xDEAD</c>, <c>0xDEADBEEF</c>) so a mis-computed
|
|
/// slice offset yields garbage rather than a zero that could coincidentally match.
|
|
/// </item>
|
|
/// <item>
|
|
/// <b>Cluster B</b> (<c>DB1.DBW400</c> + <c>DB1.DBW402</c>) — 80 bytes past cluster A, so
|
|
/// the gap budget is what forces a SECOND span instead of one merged read. Two members
|
|
/// keep it clear of the <c>PrefersPerTagRead</c> demotion, so it is a real block read.
|
|
/// </item>
|
|
/// <item>
|
|
/// <b>Leftovers</b> (<c>DB1.DBW500</c>, <c>DB1.DBW600</c>, <c>MW10</c>) — each isolated
|
|
/// enough to form its own single-member span, each therefore demoted by
|
|
/// <c>PrefersPerTagRead</c>, and three of them is past <c>MultiVarReadMinItems</c> — so
|
|
/// they ride ONE multi-var request. <c>MW10</c> is deliberately in a different area:
|
|
/// a block read can never merge across <c>(area, DB)</c>, and the multi-var pass can,
|
|
/// so its presence in the single request is what pins that property live.
|
|
/// </item>
|
|
/// </list>
|
|
/// <para>
|
|
/// <b>Timer / Counter are NOT covered here.</b> The fixture profile declares only DB1 and
|
|
/// MK; python-snap7's server can register TM/CT areas but S7.Net's timer/counter read is a
|
|
/// distinct wire shape that the fixture has never served, so pinning the planner's per-tag
|
|
/// exclusion live would mean standing up and validating a new fixture area. That exclusion
|
|
/// stays unit-covered. Nothing else in this suite depends on it — Timer/Counter tags are
|
|
/// rejected by the planner on AREA and by the multi-var pass on <c>IsBufferType</c>, two
|
|
/// independent guards.
|
|
/// </para>
|
|
/// <para>
|
|
/// <b>Why a counting factory rather than logs.</b> The driver emits no log on a successful
|
|
/// grouped read, so the only honest way to assert the wire shape is to observe the calls.
|
|
/// <see cref="CountingPlcFactory"/> decorates the REAL <see cref="S7PlcFactory"/>, so the
|
|
/// shipped <c>S7PlcAdapter</c> (and its <c>S7OperationDeadline</c> ceiling) stays on the
|
|
/// wire — the gate measures production's path, not a re-implementation of it.
|
|
/// </para>
|
|
/// </remarks>
|
|
[Collection(Snap7ServerCollection.Name)]
|
|
[Trait("Category", "Integration")]
|
|
[Trait("Device", "S7_1500")]
|
|
public sealed class S7_1500SpanReadTests(Snap7ServerFixture sim)
|
|
{
|
|
/// <summary>
|
|
/// Verifies the grouped batch returns exactly what reading every tag individually returns —
|
|
/// same values, same boxed CLR types, all Good.
|
|
/// </summary>
|
|
/// <remarks>
|
|
/// Boxed equality is the assertion on purpose: the three paths decode through different code
|
|
/// (block slicing, <c>S7.Net.ParseBytes</c> via multi-var, and the per-address read), and a
|
|
/// path that returned the right number as the wrong CLR type would be a real defect that a
|
|
/// numeric-tolerance comparison would hide.
|
|
/// </remarks>
|
|
[Fact]
|
|
public async Task Grouped_batch_matches_ungrouped_reads_value_for_value()
|
|
{
|
|
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
|
|
|
var grouped = await ReadBatchAsync(SpanLayout.DefaultGapBytes, "s7-span-on");
|
|
var ungrouped = await ReadBatchAsync(SpanLayout.GroupingDisabled, "s7-span-off");
|
|
|
|
grouped.Snapshots.Count.ShouldBe(SpanLayout.TagNames.Count);
|
|
ungrouped.Snapshots.Count.ShouldBe(SpanLayout.TagNames.Count);
|
|
|
|
for (var i = 0; i < SpanLayout.TagNames.Count; i++)
|
|
{
|
|
var name = SpanLayout.TagNames[i];
|
|
grouped.Snapshots[i].StatusCode.ShouldBe(0u, $"grouped read of '{name}' must be Good");
|
|
ungrouped.Snapshots[i].StatusCode.ShouldBe(0u, $"ungrouped read of '{name}' must be Good");
|
|
grouped.Snapshots[i].Value.ShouldBe(
|
|
ungrouped.Snapshots[i].Value,
|
|
$"'{name}' must decode identically whichever path served it");
|
|
}
|
|
}
|
|
|
|
/// <summary>
|
|
/// Verifies the grouped batch decodes the fixture's seeded values — so both paths agreeing
|
|
/// cannot mean "both wrong the same way".
|
|
/// </summary>
|
|
/// <remarks>
|
|
/// Every seed is distinct and non-zero (the #536 trap: a zero-valued source proves nothing,
|
|
/// because a read that returned nothing at all would also read as zero). Distinctness matters
|
|
/// independently: two tags sharing a value would let a swapped slice offset pass.
|
|
/// </remarks>
|
|
[Fact]
|
|
public async Task Grouped_batch_decodes_the_seeded_values()
|
|
{
|
|
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
|
|
|
var grouped = await ReadBatchAsync(SpanLayout.DefaultGapBytes, "s7-span-seeds");
|
|
var byName = SpanLayout.TagNames
|
|
.Select((n, i) => (n, grouped.Snapshots[i]))
|
|
.ToDictionary(x => x.n, x => x.Item2);
|
|
|
|
foreach (var (name, snapshot) in byName)
|
|
snapshot.StatusCode.ShouldBe(0u, $"'{name}' must be Good");
|
|
|
|
// Cluster A — the five members of the single merged span.
|
|
byName["SpanA_U16"].Value.ShouldBe((ushort)51001);
|
|
byName["SpanA_I16"].Value.ShouldBe((short)-21001);
|
|
byName["SpanA_I32"].Value.ShouldBe(305419896);
|
|
byName["SpanA_Bool"].Value.ShouldBe(true);
|
|
Convert.ToSingle(byName["SpanA_F32"].Value).ShouldBe(2.7182817f, tolerance: 0.000001f);
|
|
|
|
// Cluster B — the second span.
|
|
byName["SpanB_U16a"].Value.ShouldBe((ushort)40201);
|
|
byName["SpanB_U16b"].Value.ShouldBe((ushort)40202);
|
|
|
|
// The multi-var leftovers, including the one in a different area.
|
|
byName["Lone_U16"].Value.ShouldBe((ushort)60001);
|
|
byName["Lone_I16"].Value.ShouldBe((short)-32001);
|
|
byName["Lone_MkU16"].Value.ShouldBe((ushort)4097);
|
|
}
|
|
|
|
/// <summary>
|
|
/// Verifies the wire shape the batching actually produces against a live PLC: ten tags served
|
|
/// by three requests with grouping on, ten with it off.
|
|
/// </summary>
|
|
/// <remarks>
|
|
/// This is the half of the gate that a value-parity test cannot cover — a driver that quietly
|
|
/// fell back to per-tag reads for every tag would pass parity perfectly while delivering none
|
|
/// of the round-trip saving the feature exists for. The off-case is asserted too, because
|
|
/// <c>SpanReadMaxGapBytes < 0</c> is documented to restore the pre-grouping wire shape
|
|
/// EXACTLY, and "exactly" is a claim about requests, not values.
|
|
/// </remarks>
|
|
[Fact]
|
|
public async Task Grouping_collapses_ten_tags_to_three_wire_requests()
|
|
{
|
|
if (sim.SkipReason is not null) Assert.Skip(sim.SkipReason);
|
|
|
|
var grouped = await ReadBatchAsync(SpanLayout.DefaultGapBytes, "s7-span-shape-on");
|
|
|
|
grouped.Counters.BlockReads.ShouldBe(2,
|
|
"cluster A merges into one span and cluster B into a second; the gap budget separates them");
|
|
grouped.Counters.MultiVarReads.ShouldBe(1,
|
|
"the three demoted single-member spans are past MultiVarReadMinItems, so they share one request");
|
|
grouped.Counters.MultiVarItems.ShouldBe(3,
|
|
"all three leftovers ride that request — including MW10, which no block read could have joined");
|
|
grouped.Counters.AddressReads.ShouldBe(0,
|
|
"nothing in this batch should reach the per-tag path once both grouping passes have run");
|
|
grouped.Counters.TotalReadRequests.ShouldBe(3);
|
|
|
|
var ungrouped = await ReadBatchAsync(SpanLayout.GroupingDisabled, "s7-span-shape-off");
|
|
|
|
ungrouped.Counters.AddressReads.ShouldBe(SpanLayout.TagNames.Count,
|
|
"grouping off must restore one per-address read per tag");
|
|
ungrouped.Counters.BlockReads.ShouldBe(0);
|
|
ungrouped.Counters.MultiVarReads.ShouldBe(0,
|
|
"the multi-var pass rides the SAME switch as the span pass — disabling grouping must disable both");
|
|
ungrouped.Counters.TotalReadRequests.ShouldBe(SpanLayout.TagNames.Count);
|
|
}
|
|
|
|
/// <summary>Reads the whole layout once through a freshly-built driver and reports the wire shape.</summary>
|
|
/// <param name="maxGapBytes">The span budget: the shipped default, or a negative value to disable grouping.</param>
|
|
/// <param name="driverInstanceId">Instance id, distinct per call so log lines stay attributable.</param>
|
|
/// <returns>The batch's snapshots plus the wire-call counts observed for the read itself.</returns>
|
|
private async Task<(IReadOnlyList<DataValueSnapshot> Snapshots, CountingPlcFactory Counters)>
|
|
ReadBatchAsync(int maxGapBytes, string driverInstanceId)
|
|
{
|
|
var counters = new CountingPlcFactory(new S7PlcFactory());
|
|
await using var drv = new S7Driver(
|
|
SpanLayout.BuildOptions(sim.Host, sim.Port, maxGapBytes), driverInstanceId, counters);
|
|
|
|
await drv.InitializeAsync("{}", TestContext.Current.CancellationToken);
|
|
|
|
// Initialization may open the connection and probe; only the batch's own wire calls are the
|
|
// subject here, so the counters start from zero at the read.
|
|
counters.Reset();
|
|
|
|
var snapshots = await drv.ReadAsync(SpanLayout.TagNames, TestContext.Current.CancellationToken);
|
|
return (snapshots, counters);
|
|
}
|
|
|
|
/// <summary>
|
|
/// The tag layout under test, positioned against the shipped 16-byte gap / 220-byte span
|
|
/// defaults so the planner produces a known partition. Addresses map 1:1 to the seed offsets
|
|
/// in <c>Docker/profiles/s7_1500.json</c>, so a seed drift there surfaces here as a value
|
|
/// mismatch rather than a mystery failure.
|
|
/// </summary>
|
|
private static class SpanLayout
|
|
{
|
|
/// <summary>The shipped gap budget — the value this gate exists to validate.</summary>
|
|
public const int DefaultGapBytes = S7DriverOptions.DefaultSpanReadMaxGapBytes;
|
|
|
|
/// <summary>Any negative gap disables BOTH grouping passes; the documented off switch.</summary>
|
|
public const int GroupingDisabled = -1;
|
|
|
|
private static readonly S7TagDefinition[] Definitions =
|
|
[
|
|
// Cluster A: holes of 0, 0, 2 and 5 bytes — all inside the 16-byte budget, so these five
|
|
// merge into one 300..320 span (20 bytes, far under the 220-byte ceiling).
|
|
new("SpanA_U16", "DB1.DBW300", S7DataType.UInt16),
|
|
new("SpanA_I16", "DB1.DBW302", S7DataType.Int16),
|
|
new("SpanA_I32", "DB1.DBD304", S7DataType.Int32),
|
|
new("SpanA_Bool", "DB1.DBX310.5", S7DataType.Bool),
|
|
new("SpanA_F32", "DB1.DBD316", S7DataType.Float32),
|
|
|
|
// Cluster B: 80 bytes past cluster A's end, so the budget forces a second span. Two
|
|
// members, so PrefersPerTagRead cannot demote it to the per-tag path.
|
|
new("SpanB_U16a", "DB1.DBW400", S7DataType.UInt16),
|
|
new("SpanB_U16b", "DB1.DBW402", S7DataType.UInt16),
|
|
|
|
// Leftovers: each far enough from every neighbour to form a single-member span, hence
|
|
// demoted, hence batched by the multi-var pass. MW10 is in another area entirely.
|
|
new("Lone_U16", "DB1.DBW500", S7DataType.UInt16),
|
|
new("Lone_I16", "DB1.DBW600", S7DataType.Int16),
|
|
new("Lone_MkU16", "MW10", S7DataType.UInt16),
|
|
];
|
|
|
|
/// <summary>The batch's references, in the order the driver is asked for them.</summary>
|
|
public static readonly IReadOnlyList<string> TagNames = [.. Definitions.Select(d => d.Name)];
|
|
|
|
/// <summary>Builds driver options for the layout at the requested span budget.</summary>
|
|
/// <param name="host">The fixture hostname or IP address.</param>
|
|
/// <param name="port">The fixture port.</param>
|
|
/// <param name="maxGapBytes">Span gap budget; negative disables grouping.</param>
|
|
/// <returns>The driver options.</returns>
|
|
public static S7DriverOptions BuildOptions(string host, int port, int maxGapBytes) => new()
|
|
{
|
|
Host = host,
|
|
Port = port,
|
|
CpuType = S7CpuType.S71500,
|
|
Rack = 0,
|
|
Slot = 0,
|
|
Timeout = TimeSpan.FromSeconds(5),
|
|
// Same reasoning as the smoke profile: a background probe would race these reads for the
|
|
// connection gate and would also pollute the wire-shape counts this suite asserts on.
|
|
Probe = new S7ProbeOptions { Enabled = false },
|
|
SpanReadMaxGapBytes = maxGapBytes,
|
|
SpanReadMaxSpanBytes = S7DriverOptions.DefaultSpanReadMaxSpanBytes,
|
|
RawTags = S7RawTags.Entries(Definitions),
|
|
};
|
|
}
|
|
|
|
/// <summary>
|
|
/// <see cref="IS7PlcFactory"/> decorator that counts the read calls the driver makes, so a
|
|
/// test can assert the wire shape rather than infer it. Delegates to the real factory, so
|
|
/// every counted call is the one production would have issued.
|
|
/// </summary>
|
|
/// <param name="inner">The factory producing the real connection.</param>
|
|
private sealed class CountingPlcFactory(IS7PlcFactory inner) : IS7PlcFactory
|
|
{
|
|
/// <summary>Block reads issued — one per planned span.</summary>
|
|
public int BlockReads { get; private set; }
|
|
|
|
/// <summary>Multi-var requests issued — one per leftover chunk.</summary>
|
|
public int MultiVarReads { get; private set; }
|
|
|
|
/// <summary>Items carried across all multi-var requests.</summary>
|
|
public int MultiVarItems { get; private set; }
|
|
|
|
/// <summary>Per-address reads issued — the unchanged per-tag path.</summary>
|
|
public int AddressReads { get; private set; }
|
|
|
|
/// <summary>Total read round-trips, whichever shape they took.</summary>
|
|
public int TotalReadRequests => BlockReads + MultiVarReads + AddressReads;
|
|
|
|
/// <summary>Zeroes the counters, so a batch can be measured without initialization's calls.</summary>
|
|
public void Reset()
|
|
{
|
|
BlockReads = 0;
|
|
MultiVarReads = 0;
|
|
MultiVarItems = 0;
|
|
AddressReads = 0;
|
|
}
|
|
|
|
/// <inheritdoc />
|
|
public IS7Plc Create(S7CpuType cpuType, string host, int port, short rack, short slot, TimeSpan timeout)
|
|
=> new CountingPlc(inner.Create(cpuType, host, port, rack, slot, timeout), this);
|
|
|
|
private void CountBlockRead() => BlockReads++;
|
|
|
|
private void CountMultiVarRead(int items)
|
|
{
|
|
MultiVarReads++;
|
|
MultiVarItems += items;
|
|
}
|
|
|
|
private void CountAddressRead() => AddressReads++;
|
|
|
|
/// <summary>Counting pass-through over one real connection.</summary>
|
|
/// <param name="inner">The real connection.</param>
|
|
/// <param name="owner">The factory holding the counters.</param>
|
|
private sealed class CountingPlc(IS7Plc inner, CountingPlcFactory owner) : IS7Plc
|
|
{
|
|
/// <inheritdoc />
|
|
public bool IsConnected => inner.IsConnected;
|
|
|
|
/// <inheritdoc />
|
|
public Task OpenAsync(CancellationToken cancellationToken) => inner.OpenAsync(cancellationToken);
|
|
|
|
/// <inheritdoc />
|
|
public void Close() => inner.Close();
|
|
|
|
/// <inheritdoc />
|
|
public Task<object?> ReadAsync(string address, CancellationToken cancellationToken)
|
|
{
|
|
owner.CountAddressRead();
|
|
return inner.ReadAsync(address, cancellationToken);
|
|
}
|
|
|
|
/// <inheritdoc />
|
|
public Task<byte[]> ReadBytesAsync(
|
|
S7NetDataType area, int db, int startByteAdr, int count, CancellationToken cancellationToken)
|
|
{
|
|
owner.CountBlockRead();
|
|
return inner.ReadBytesAsync(area, db, startByteAdr, count, cancellationToken);
|
|
}
|
|
|
|
/// <inheritdoc />
|
|
public Task<IReadOnlyList<S7DataItem>> ReadMultipleVarsAsync(
|
|
List<S7DataItem> items, CancellationToken cancellationToken)
|
|
{
|
|
// Counted before the call: the item count is the request's shape, and S7.Net hands
|
|
// the same list back, so reading it afterwards would measure the same thing later.
|
|
owner.CountMultiVarRead(items?.Count ?? 0);
|
|
return inner.ReadMultipleVarsAsync(items!, cancellationToken);
|
|
}
|
|
|
|
/// <inheritdoc />
|
|
public Task WriteAsync(string address, object value, CancellationToken cancellationToken)
|
|
=> inner.WriteAsync(address, value, cancellationToken);
|
|
|
|
/// <inheritdoc />
|
|
public Task WriteBytesAsync(
|
|
S7NetDataType area, int db, int startByteAdr, byte[] value, CancellationToken cancellationToken)
|
|
=> inner.WriteBytesAsync(area, db, startByteAdr, value, cancellationToken);
|
|
|
|
/// <inheritdoc />
|
|
public Task ReadStatusAsync(CancellationToken cancellationToken) => inner.ReadStatusAsync(cancellationToken);
|
|
|
|
/// <inheritdoc />
|
|
public void Dispose() => inner.Dispose();
|
|
}
|
|
}
|
|
}
|