Authoring FOCAS tags through /raw -> Browse device... produced tags the driver
could never read. Every committed tag read BadNodeIdUnknown forever, and the
failure was silent end to end: the AdminUI accepted it, the deploy gate sealed
green, and the driver reported Healthy with 0 errors while ignoring the tags.
Net effect: the whole fixed-tree surface could not be published through any v3
authoring path. Found cutting wonder-app-vd03 over to v3 against a real Makino
Pro 5 / Fanuc 30i, where 0 of 20 committed tags read while two hand-authored
MACRO: tags on the same device read Good.
A captured browse leaf's id IS its DriverAttributeInfo.FullName, and the fixed
tree emitted "{deviceHost}/{path}" there -- an internal cache key, not an
address. Both authoring paths wrote it verbatim into TagConfig.address, and
FocasAddress.TryParse accepts no such form, so the driver skipped the tags at
init.
Fixed at the emitter rather than by stripping the host at commit, which fixes
the browse-commit flow and the manual picker's tree-select together and leaves
one canonical address form:
- FocasAddress gains a fourth kind, FIXED:<path>, and moves to Contracts so the
AdminUI and ControlPlane can parse without referencing the runtime driver
(#526). A FIXED: read is served from the fixed-tree snapshot the poll loop
already maintains -- no area read, no connection. Writes refuse: nothing in
that tree is a writable location on the CNC.
- The address carries no device. A tag's device comes from its Device row, and
a second routing channel for one fact is what created this defect.
- An authored FIXED: tag arms the fixed-tree poll loop by itself. Enabled
defaults false and the browser force-enables it only for a browse, so the
operator would otherwise browse, commit, deploy, and land on a driver whose
loop never starts -- every tag Bad with a correct address.
- Fixed-tree values are now dated from the last answered poll and go
BadCommunicationError once it is stale (8 cadences, floored at 30s). The poll
loop swallows a failed tick by design, so a dead CNC would otherwise serve its
last snapshot as Good indefinitely -- harmless while nothing could bind to the
tree, not harmless now.
Guardrails, so this class cannot recur silently:
- FocasTagConfigModel.Validate() runs the real parser instead of a non-empty
check, and FocasTagDefinitionFactory.Inspect() warns at the deploy gate, which
covers CSV/API config that never touches the modal.
- The manual picker offered axis/spindle/program/status "parameter groups" --
none of which is a FOCAS addressing space -- and its own default value,
axis:5, was unusable. It now composes PMC / PARAM: / MACRO: through
FocasAddress, so what it emits is parseable by construction.
Tests assert addresses ROUND-TRIP through the parser rather than matching an
expected string: the previous FocasAddressBuilderTests pinned "axis:5" exactly,
which is how a green suite coexisted with a picker nobody could use. Verified
red-first against the old emitter. FOCAS 308, AdminUI 1095, ControlPlane 169,
Core 581 -- all pass, 0 warnings.
The remaining half of #540 -- a driver reporting Healthy/0 errors while
skipping tags at init -- is fleet-wide (eight drivers do this) and is filed
separately rather than patched per-driver.
OtOpcUa documentation
Two tiers of documentation live here:
- Current reference at the top level (
docs/*.md) — describes what's shipped today. Start here for operator + integrator reference. - Implementation history + design notes at
docs/v2/*.md— the authoritative plan + decision log the current reference is built from. Start here when you need the why behind an architectural choice, or when a top-level doc says "see plan.md § X".
The project was originally called LmxOpcUa (a single-driver Galaxy/MXAccess OPC UA server) and has since become OtOpcUa, a multi-driver OPC UA server platform. Any lingering LmxOpcUa-string in a path you see in docs is a deliberate residual (executable name lmxopcua-cli, client PKI folder {LocalAppData}/LmxOpcUaClient/) — fixing those requires migration shims + is tracked as follow-ups.
Platform overview
v2 (2026-05-26): the separate
OtOpcUa.Server+OtOpcUa.Adminservices fused into a single role-gatedOtOpcUa.Hostbinary, joined by an Akka.NET cluster. See v2 design for the architectural decision.
- Core owns shared abstractions (driver capability contracts, scripting, virtual tags, alarm historian).
- Drivers plug in via capability interfaces in
ZB.MOM.WW.OtOpcUa.Core.Abstractions:IDriver,IReadable,IWritable,ITagDiscovery,ISubscribable,IHostConnectivityProbe,IAlarmSource,IHistoryProvider,IPerCallHostResolver. Each driver opts into whichever it supports. - Host (
src/Server/ZB.MOM.WW.OtOpcUa.Host) is the single fused binary (.NET 10, AnyCPU).OTOPCUA_ROLESenv decides what to mount:admin(Blazor + control-plane singletons),driver(OPC UA endpoint + per-node actors), or both. See ServiceHosting.md. - Cluster + ControlPlane + Runtime + AdminUI + Security sit between Core and Host. The cluster glues per-node actors into one logical fleet; the control-plane singletons (deploy coordinator, audit writer, redundancy state) live on the admin role-leader. See Redundancy.md.
- The Galaxy driver still reaches MXAccess via gRPC to a separately-installed mxaccessgw sidecar (sibling repo).
Where to find what
Architecture + data-path reference
| Doc | Covers |
|---|---|
| OpcUaServer.md | Top-level server architecture — Core, driver dispatch, Config DB, generations |
| AddressSpace.md | GenericDriverNodeManager + ITagDiscovery + IAddressSpaceBuilder |
| ReadWriteOperations.md | OPC UA Read/Write → CapabilityInvoker → IReadable/IWritable |
| DriverLifecycle.md | Server-side driver lifecycle + infrastructure contracts (IDriverFactory, IDriverProbe, IDriverHealthPublisher, IDriverConfigEditor, IHistorianDataSource) + the Commons library |
| Subscriptions.md | Monitored items → ISubscribable + per-driver subscription refcount (v1 archive) |
| AlarmTracking.md | IAlarmSource + AlarmSurfaceInvoker + OPC UA alarm conditions — native Galaxy alarms end-to-end (live) |
| AlarmTracking.md | Original alarm-tracking write-up (v1 archive) |
| AlarmHistorian.md | Core.AlarmHistorian store-and-forward sink — LocalDbStoreAndForwardSink, the replicated alarm_sf_events buffer + Primary-only drain, IAlarmHistorianWriter, dead-letter/retry/eviction |
| DataTypeMapping.md | Per-driver DriverAttributeInfo → OPC UA variable types (v1 archive — live mapping is in src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.Galaxy/Browse/DataTypeMap.cs) |
| IncrementalSync.md | Address-space rebuild on redeploy + sp_ComputeGenerationDiff |
| HistoricalDataAccess.md | IHistoryProvider as a per-driver optional capability (v1 archive) |
| VirtualTags.md | Core.Scripting + Core.VirtualTags — Roslyn script sandbox, engine, dispatch alongside driver tags |
| ScriptEditor.md | Monaco script editor — Roslyn-backed IntelliSense (completions, diagnostics, hover, tag-path) for C# virtual-tag scripts; AdminUI/ScriptAnalysis/ backend |
| ScriptedAlarms.md | Core.ScriptedAlarms — script-predicate IAlarmSource + Part 9 state machine |
One Core subsystem is shipped without a dedicated top-level doc; see the section in the linked doc:
| Project | See |
|---|---|
Analyzers (Roslyn OTOPCUA0001) |
security.md § OTOPCUA0001 Analyzer |
Drivers
| Doc | Covers |
|---|---|
| drivers/README.md | Index of the eight shipped drivers + capability matrix |
| drivers/Galaxy.md | Galaxy driver — in-process gRPC client to the mxaccessgw sidecar |
| v1/drivers/Galaxy-Repository.md | Galaxy-specific discovery via the ZB SQL database (v1 archive — the gateway owns this path now) |
For Modbus / S7 / AB CIP / AB Legacy / TwinCAT / FOCAS / OPC UA Client specifics, see v2/driver-specs.md.
Operational
| Doc | Covers |
|---|---|
| Configuration.md | Live appsettings + environment-variable reference (current state) |
| Configuration.md | appsettings bootstrap + Config DB + Admin UI draft/publish (v1 archive — OTOPCUA_GALAXY_* env vars now live in mxaccessgw config) |
| Uns.md | The global /uns master tree — manage Area/Line/Equipment/Tag/VirtualTag fleet-wide; replaces the per-cluster UNS/Equipment/Tags tabs |
| security.md | Transport security profiles, LDAP auth, ACL trie, role grants, OTOPCUA0001 analyzer |
| Redundancy.md | RedundancyStateActor (cluster-scoped singleton), ServiceLevelCalculator, IRedundancyRoleView, per-cluster meshes, Prometheus metrics |
| Reservations.md | Fleet-wide ZTag / SAPID external-ID reservations — publish-time claim, release flow |
| ServiceHosting.md | Single fused OtOpcUa.Host binary install/uninstall with OTOPCUA_ROLES gating; the historian backend is the external HistorianGateway |
| StatusDashboard.md | Pointer — superseded by v2/admin-ui.md |
Client tooling
| Doc | Covers |
|---|---|
| Client.CLI.md | otopcua-cli — OPC UA command-line client |
| Client.UI.md | Avalonia desktop client |
| DriverClis.md | Driver test-client CLIs — index + shared commands |
| Driver.Modbus.Cli.md | otopcua-modbus-cli — Modbus-TCP |
| Driver.AbCip.Cli.md | otopcua-abcip-cli — ControlLogix / CompactLogix / Micro800 / GuardLogix |
| Driver.AbLegacy.Cli.md | otopcua-ablegacy-cli — SLC / MicroLogix / PLC-5 (PCCC) |
| Driver.S7.Cli.md | otopcua-s7-cli — Siemens S7-300 / S7-400 / S7-1200 / S7-1500 |
| Driver.TwinCAT.Cli.md | otopcua-twincat-cli — Beckhoff TwinCAT 2/3 ADS |
| Driver.FOCAS.Cli.md | otopcua-focas-cli — Fanuc FOCAS/2 CNC |
Requirements
| Doc | Covers |
|---|---|
| reqs/HighLevelReqs.md | HLRs — numbered system-level requirements |
| reqs/OpcUaServerReqs.md | OPC UA server-layer reqs |
| v1/reqs/ServiceHostReqs.md | Per-process hosting reqs (v1 archive — only OtOpcUa server hosting remains in scope post-PR-7.2) |
| reqs/ClientRequirements.md | Client CLI + UI reqs |
| v1/reqs/GalaxyRepositoryReqs.md | Galaxy-scoped repository reqs (v1 archive — owned by mxaccessgw today) |
| v1/reqs/MxAccessClientReqs.md | Galaxy-scoped MXAccess reqs (v1 archive — owned by mxaccessgw today) |
| reqs/StatusDashboardReqs.md | Pointer — superseded by Admin UI |
Implementation history (docs/v2/)
Design decisions + phase plans + execution notes. Load-bearing cross-references from the top-level docs:
- v2/plan.md — authoritative v2 vision doc + numbered decision log (referenced as "decision #N" elsewhere)
- v2/admin-ui.md — Admin UI spec
- v2/acl-design.md — data-plane ACL + permission-trie design (Phase 6.2)
- v2/config-db-schema.md — Config DB schema reference
- v2/driver-specs.md — per-driver addressing + quirks for every shipped protocol
- v2/dev-environment.md — dev-box bootstrap
- v2/test-data-sources.md — integration-test simulator matrix (includes the pinned libplctag
ab_serverversion for AB CIP tests) - v2/multi-host-dispatch.md — per-PLC circuit breakers (Phase 6.1 decision #144)
- v2/v2-release-readiness.md — release-readiness tracker
- v2/phase-7-status.md — Phase 7 reconciliation: what shipped vs. the plan, and the five remaining gaps
- v2/implementation/phase--.md — per-phase execution plans with exit-gate evidence
v1 archive
The v1 in-process MXAccess architecture (Galaxy.Host + Galaxy.Proxy + Galaxy.Shared, .NET 4.8 x86 COM, the OtOpcUaGalaxyHost Windows service) was retired in PR 7.2 (2026-04-30, commit ae7106d). Docs that described that shape are kept under v1/ as historical record — see v1/README.md for the index.