`IHostConnectivityProbe` was a dead surface: eleven drivers implement it, `GetHostStatuses()` had ZERO production call sites, and `OnHostStatusChanged` had no subscriber outside the Galaxy driver's own aggregator. Per-host connectivity was computed by every driver and read by nobody. The issue offered "build the publisher or delete it". The publisher as its entity doc described it — driver nodes upserting `DriverHostStatus` rows — is not buildable: per-cluster mesh Phase 4 gates `AddOtOpcUaConfigDb` on the `admin` role, so a driver-only node has no ConfigDb connection to write rows with. So the capability is kept and the transport changed. `DriverHealthChanged.HostStatuses` now carries the probe result to `/hosts` as a Hosts column. That channel already reached the page, already survives the mesh split via the Phase 5 gRPC telemetry stream, and already replays a last-value snapshot on re-subscribe — so per-host state re-primes after a reconnect without a durable store. Both halves of the interface finally do what they are for: the event triggers a prompt publish, the pull is the source of truth. The point of the column is the case the driver-level state chip structurally cannot express: a multi-device driver stays aggregate-Healthy while ONE of its devices is unreachable. Two traps, both pinned by tests that were falsified against the prod code: - The host digest MUST be in the publish fingerprint. On a single-host-down transition every other fingerprint component is unchanged, so the dedup would swallow exactly the publish carrying the news — the trap that already bit the rediscovery signal. Removing it turns the guard test red, verified. - null (no probe) must stay distinct from empty (probe with no hosts). proto3 cannot tell an absent repeated field from an empty one, hence the explicit `has_host_statuses` flag; collapsing them would render every probe-less driver as one whose devices are all fine. Dropped: the DriverHostStatus entity, enum, DbSet, model config and table (migration DropDriverHostStatusTable — empty on every deployment, so the scaffolder's data-loss warning is moot, and Down() recreates it exactly). Found en route, NOT fixed here: `DriverInstanceResilienceStatus` is the identical defect — no writer, no reader, only a DbSet declaration, while the live data rides the `driver-resilience-status` telemetry channel. Its doc-comment now states that rather than describing the sampler and AdminUI join that were never built. Filed as #524 rather than widening this schema change beyond what was asked. Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
OtOpcUa
OPC UA server (.NET 10 AnyCPU) that exposes a fleet of industrial drivers as a single OPC UA address space. Drivers ship in-process for AVEVA System Platform Galaxy (via the sibling mxaccessgw repo), Modbus TCP, Siemens S7, Allen-Bradley CIP (ControlLogix / CompactLogix), Allen-Bradley Legacy (SLC 500 / MicroLogix), Beckhoff TwinCAT (ADS), FANUC FOCAS, OPC UA Client (gateway), and MQTT (broker subscribe; Sparkplug B in progress).
A cross-platform client stack (.NET 10) — shared library, CLI, and Avalonia desktop app — connects to any OPC UA server.
Architecture
OPC UA Clients (CLI, Desktop UI, 3rd-party)
|
v
+-------------------------------------+
| OtOpcUa.Server (.NET 10 AnyCPU) |
| address space + capability fan-out|
+-------------------------------------+
| | | | | | | |
Galaxy Modbus S7 AbCip AbLeg TwinCAT FOCAS OpcUaClient MQTT
|
v
mxaccessgw (sibling repo, gRPC)
|
v
MXAccess COM (x86 worker, on AVEVA box)
Galaxy is the only driver with an external runtime: it speaks gRPC to a separately installed mxaccessgw server (sibling repo at c:\Users\dohertj2\Desktop\mxaccessgw\) which owns the MXAccess COM apartment and the x86/STA bitness constraint server-side. Everything in this repo is platform-agnostic .NET 10.
Prerequisites
- .NET 10 SDK (server, drivers, clients all target .NET 10)
- SQL Server reachable for the central config DB
- For Galaxy specifically: a running
mxaccessgwdeployment — see docs/v2/Galaxy.ParityRig.md - For historian read-back / alarm history / continuous historization: a running
ZB.MOM.WW.HistorianGatewaydeployment (the sole historian backend; consumed as theZB.MOM.WW.HistorianGateway.ClientgRPC package). It must runRuntimeDb:Enabled=true+RuntimeDb:EventReadsEnabled=true, and the API key must carryhistorian:read+historian:write+historian:tags:writescopes.
Quick Start
dotnet restore ZB.MOM.WW.OtOpcUa.slnx
dotnet build ZB.MOM.WW.OtOpcUa.slnx
dotnet test ZB.MOM.WW.OtOpcUa.slnx
# Run the server in dev (foreground)
dotnet run --project src/Server/ZB.MOM.WW.OtOpcUa.Host
The server starts on opc.tcp://localhost:4840 with the None security profile. Configure Security.Profiles in src/Server/ZB.MOM.WW.OtOpcUa.Host/appsettings.json to enable Basic256Sha256-Sign or Basic256Sha256-SignAndEncrypt. See docs/security.md.
Install as Windows Services
Production deployment is driven by scripts/install/Install-Services.ps1, which registers the OtOpcUa server service under a chosen service account. Historian support requires a separately deployed ZB.MOM.WW.HistorianGateway and Galaxy support a separately installed mxaccessgw — neither this repo nor the install script provisions them.
.\scripts\install\Install-Services.ps1 `
-InstallRoot 'C:\Program Files\OtOpcUa' `
-ServiceAccount 'DOMAIN\svc-otopcua'
The historian backend is the external ZB.MOM.WW.HistorianGateway (not installed by this script). See the script header and docs/ServiceHosting.md for full options.
Client CLI
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- connect -u opc.tcp://localhost:4840
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- browse -u opc.tcp://localhost:4840 -r -d 3
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- read -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode"
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- write -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -v 42
dotnet run --project src/Client/ZB.MOM.WW.OtOpcUa.Client.CLI -- subscribe -u opc.tcp://localhost:4840 -n "ns=2;s=SomeNode" -i 500
See docs/Client.CLI.md and docs/Client.UI.md.
Documentation
Architecture deep-dives
| Topic | Doc |
|---|---|
| OPC UA server composition, namespace fan-out, Polly invoker | docs/OpcUaServer.md |
| Address space layout | docs/AddressSpace.md |
| Read / Write dispatch (driver vs virtual vs scripted-alarm) | docs/ReadWriteOperations.md |
| Incremental sync (driver-backend rediscovery + config publishes) | docs/IncrementalSync.md |
| Service hosting (Server + Admin; external HistorianGateway backend) | docs/ServiceHosting.md |
| Security (transport, LDAP, certificates) | docs/security.md |
| Redundancy | docs/Redundancy.md |
| Status dashboard | docs/StatusDashboard.md |
Drivers
| Topic | Doc |
|---|---|
| Driver specs (per-driver capability surface, config, addressing) | docs/v2/driver-specs.md |
| Galaxy driver | docs/drivers/Galaxy.md |
| Modbus / S7 / AbCip / AbLegacy / TwinCAT / FOCAS / OpcUaClient / MQTT | docs/drivers/ |
| Galaxy parity rig (mxaccessgw setup) | docs/v2/Galaxy.ParityRig.md |
| Galaxy performance + tracing | docs/v2/Galaxy.Performance.md |
Clients
| Topic | Doc |
|---|---|
| Client CLI | docs/Client.CLI.md |
| Client UI (Avalonia desktop) | docs/Client.UI.md |
v1 archive
The original v1 in-process MXAccess docs (Galaxy.Host topology, Configuration env vars, AlarmTracking, DataTypeMapping, HistoricalDataAccess, Subscriptions, etc.) are preserved under docs/v1/ — historical reference only. PR 7.2 retired the v1 architecture on 2026-04-30; current state is documented in the sections above.
License
Internal use only.