Audit of docs/ against src/ surfaced shipped features without current-reference coverage (FOCAS CLI, Core.Scripting+VirtualTags, Core.ScriptedAlarms, Core.AlarmHistorian), an out-of-date driver count + capability matrix, ADR-002's virtual-tag dispatch not reflected in data-path docs, broken cross-references, and OpcUaServerReqs declaring OPC-020..022 that were never scoped. This commit closes all of those so operators + integrators can stay inside docs/ without falling back to v2/implementation/. Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
4.8 KiB
Driver test-client CLIs
Six shell-level ad-hoc validation tools, one per native-protocol driver family.
Each mirrors the v1 otopcua-cli shape (probe / read / write / subscribe) against
the same driver the OtOpcUa server uses — so "does the CLI see it?" and
"does the server see it?" are the same question.
| CLI | Protocol | Docs |
|---|---|---|
otopcua-modbus-cli |
Modbus-TCP | Driver.Modbus.Cli.md |
otopcua-abcip-cli |
CIP / EtherNet-IP (Logix symbolic) | Driver.AbCip.Cli.md |
otopcua-ablegacy-cli |
PCCC (SLC / MicroLogix / PLC-5) | Driver.AbLegacy.Cli.md |
otopcua-s7-cli |
S7comm / ISO-on-TCP | Driver.S7.Cli.md |
otopcua-twincat-cli |
Beckhoff ADS | Driver.TwinCAT.Cli.md |
otopcua-focas-cli |
Fanuc FOCAS/2 (CNC) | Driver.FOCAS.Cli.md |
The OPC UA client CLI lives separately and predates this suite —
see Client.CLI.md for otopcua-cli.
Shared commands
Every driver CLI exposes the same four verbs:
probe— open a session, read one sentinel tag, print driver health. Fastest "is the device talking?" check.read— synthesise a one-tag driver config from--type/--address(or--tag/--symbol) flags, read once, print the snapshot. No extra config file needed.write— same shape plus--value. Values parse per--typeusing invariant culture. Booleans accepttrue/false/1/0/yes/no/on/off. Writes are non-idempotent by default — a timeout after the device already applied the write will not auto-retry (plan decisions #44, #45).subscribe— long-running data-change stream until Ctrl+C. Uses native push where available (TwinCAT ADS notifications) and falls back to polling (PollGroupEngine) where the protocol has no push (Modbus, AB, S7, FOCAS).
Shared infrastructure
All six CLIs depend on src/ZB.MOM.WW.OtOpcUa.Driver.Cli.Common/:
DriverCommandBase—--verbose+ Serilog configuration + the abstractTimeoutsurface every protocol-specific base overrides with its own default.SnapshotFormatter— consistent output across every CLI: tag / value / status / source-time / server-time for single reads, a 4-column table for batches,Write <tag>: 0x... (Name)for writes, and one line per change event for subscriptions. OPC UA status codes render as0xXXXXXXXX (Name)with a shortlist forGood/Bad*/Uncertain; unknown codes fall back to hex.
Writing a seventh CLI (hypothetical Galaxy / OPC UA Client) costs roughly
150 lines: a {Family}CommandBase + four thin command classes that hand
their flag values to the already-shipped driver.
Typical cross-CLI workflows
- Commissioning a new device —
probefirst, thenreada known-good tag. If the device is up + talking the protocol, both pass; if the tag is wrong you'll see the read fail with a protocol-specific error. - Reproducing a production bug —
subscribeto the tag the bug report names, then have the operator run the scenario. You get an HH:mm:ss.fff timeline of exactly when each value changed. - Validating a recipe write —
write+readback. If the server's write path would have done anything different, the CLI would have too. - Byte-order / word-swap debugging —
readwith one--byte-order, then the other. The plausible result identifies the correct setting for that device family. (Modbus, S7.)
Known gaps
- AB Legacy cip-path quirk — libplctag's ab_server requires a
non-empty CIP routing path before forwarding to the PCCC dispatcher.
Pass
--gateway "ab://127.0.0.1:44818/1,0"against the Docker fixture; real SLC / MicroLogix / PLC-5 hardware accepts an empty path (ab://host:44818/). Bit-file writes (B3:0/5) still surface0x803D0000against ab_server — route operator-critical bit writes to real hardware until upstream fixes this. - S7 PUT/GET communication must be enabled in TIA Portal for any S7-1200/1500. See Driver.S7.Cli.md.
- TwinCAT AMS router must be reachable (local XAR, standalone Router NuGet, or authorised remote route). See Driver.TwinCAT.Cli.md.
- Structure / UDT writes are refused by the AB CIP + TwinCAT CLIs — whole-UDT writes need a declared member layout that belongs in a real driver config, not a one-shot flag.
Tracking
Tasks #249 / #250 / #251 shipped the original five. The FOCAS CLI followed
alongside the Tier-C isolation work on task #220 — no CLI-level test
project (hardware-gated). 122 unit tests cumulative across the first five
(16 shared-lib + 106 CLI-specific) — run
dotnet test tests/ZB.MOM.WW.OtOpcUa.Driver.Cli.Common.Tests +
tests/ZB.MOM.WW.OtOpcUa.Driver.*.Cli.Tests to re-verify.