# `otopcua-ablegacy-cli` — AB Legacy (PCCC) test client
|
|
|
|
Ad-hoc probe / read / write / subscribe tool for SLC 500 / MicroLogix 1100 /
|
|
MicroLogix 1400 / PLC-5 devices, talking to the **same** `AbLegacyDriver` the
|
|
OtOpcUa server uses (libplctag PCCC back-end).
|
|
|
|
Third of four driver test-client CLIs. Shares `Driver.Cli.Common` with the
|
|
others.
|
|
|
|
## Build + run
|
|
|
|
```powershell
|
|
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Cli -- --help
|
|
```
|
|
|
|
## Common flags
|
|
|
|
| Flag | Default | Purpose |
|
|
|---|---|---|
|
|
| `-g` / `--gateway` | **required** | Canonical `ab://host[:port]/cip-path` |
|
|
| `-P` / `--plc-type` | `Slc500` | Slc500 / MicroLogix / Plc5 / LogixPccc |
|
|
| `--timeout-ms` | `5000` | Per-operation timeout — see precedence note below |
|
|
| `--retries` | `0` | Retry count on transient `BadCommunicationError` (PR 9 / #252) |
|
|
| `--demote-failure-threshold` | `3` | **PR ablegacy-12 / #255** — consecutive comm failures before the device is auto-demoted |
|
|
| `--demote-for-ms` | `30000` | **PR ablegacy-12 / #255** — auto-demote cool-down window in ms |
|
|
| `--no-demote` | off | **PR ablegacy-12 / #255** — disable auto-demote entirely (counters still tick) |
|
|
| `--verbose` | off | Serilog debug output |
|
|
|
|
Family ↔ CIP-path cheat sheet:
|
|
- **SLC 5/05 / PLC-5** — `1,0`
|
|
- **MicroLogix 1100 / 1400** — empty path (`ab://host/`) — they use direct EIP
|
|
with no backplane
|
|
- **LogixPccc** — `1,0` (Logix controller accessed via the PCCC compatibility
|
|
layer; rare)
|
|
|
|
### Per-device timeout / retry tuning (#252, PR 9)
|
|
|
|
The CLI's `--timeout-ms` is the **driver-wide default** when launched as a
|
|
one-shot test client. In production (server-side, multi-device deployment)
|
|
each `AbLegacyDeviceOptions` row carries its own optional `Timeout` /
|
|
`Retries` that override the driver-wide value.
|
|
|
|
Precedence (highest → lowest): per-device override → driver-wide default →
|
|
hard-coded fallback (2000 ms / 0 retries).
|
|
|
|
Tuning cheat sheet — start here, measure, then trim:
|
|
|
|
| Family | Recommended `Timeout` | Notes |
|
|
|---|---|---|
|
|
| SLC 5/01 (RS-232 / DH+ bridge) | **5000 ms** | Slowest of the bunch; serial round-trip plus DH+ hop |
|
|
| SLC 5/02 / 5/03 (DH+) | 3000 ms | Bridged Ethernet → DH+ adds ~1 s |
|
|
| **SLC 5/04 / 5/05** (Ethernet) | **2000 ms** | Fastest of the SLC family — direct EIP/PCCC |
|
|
| MicroLogix 1100 / 1400 | **3000 ms** | Single-CPU, slow scan; no backplane |
|
|
| PLC-5 (Ethernet I/F) | 2500 ms | Comparable to SLC 5/05 over EIP |
|
|
| LogixPccc compat layer | 2000 ms | Logix CPU is fast; PCCC layer is the floor |
|
|
|
|
A small `--retries 1` (or `2` for slow chassis) is generally safe — the retry
|
|
loop only fires on transient `BadCommunicationError`; terminal errors
|
|
(`BadNodeIdUnknown`, `BadTypeMismatch`, …) surface on the first attempt.
|
|
|
|
## PCCC address primer
|
|
|
|
File letters imply data type; type flag still required so the CLI knows how to
|
|
parse your `--value`.
|
|
|
|
| File | Type | CLI `--type` |
|
|
|---|---|---|
|
|
| `N` | signed int16 | `Int` |
|
|
| `F` | float32 | `Float` |
|
|
| `B` | bit-packed (`B3:0/3` addresses bit 3 of word 0) | `Bit` |
|
|
| `L` | long int32 (SLC 5/05+ only) | `Long` |
|
|
| `A` | analog int (semantically like N) | `AnalogInt` |
|
|
| `ST` | ASCII string (82-byte + length header) | `String` |
|
|
| `T` | timer sub-element (`T4:0.ACC` / `.PRE` / `.EN` / `.DN`) | `TimerElement` |
|
|
| `C` | counter sub-element (`C5:0.ACC` / `.PRE` / `.CU` / `.CD` / `.DN`) | `CounterElement` |
|
|
| `R` | control sub-element (`R6:0.LEN` / `.POS` / `.EN` / `.DN` / `.ER`) | `ControlElement` |
|
|
|
|
## Commands
|
|
|
|
### `probe`
|
|
|
|
```powershell
|
|
# SLC 5/05 — default probe address N7:0
|
|
otopcua-ablegacy-cli probe -g ab://192.168.1.20/1,0
|
|
|
|
# MicroLogix 1100 — status file first word
|
|
otopcua-ablegacy-cli probe -g ab://192.168.1.30/ -P MicroLogix -a S:0
|
|
```
|
|
|
|
`probe` output (PR ablegacy-12 / #255) reports both `Health` (driver health
|
|
state) and `Host state`. The latter is sourced from `IHostConnectivityProbe`
|
|
and surfaces `Demoted` when the auto-demote threshold has tripped — a fast
|
|
visual signal that the CLI is short-circuiting future reads against this
|
|
device until the cool-down expires:
|
|
|
|
```text
|
|
Gateway: ab://192.168.1.20/1,0
|
|
PLC type: Slc500
|
|
Health: Degraded
|
|
Host state: Demoted
|
|
Last error: libplctag status -33 reading N7:0
|
|
```
|
|
|
|
### Auto-demote knobs
|
|
|
|
```powershell
|
|
# Trip after just one comm failure, hold for 60s.
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a N7:0 -t Int `
|
|
--demote-failure-threshold 1 --demote-for-ms 60000
|
|
|
|
# Opt out of auto-demote — stresses the link without short-circuiting.
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a N7:0 -t Int --no-demote
|
|
```
|
|
|
|
The CLI is a one-shot test client — auto-demote primarily matters in the
|
|
server-side multi-device deployment, where a single demoted PLC can no
|
|
longer block reads against its healthy peers. Use the CLI flags to
|
|
reproduce a flapping-link scenario locally before tuning the server-side
|
|
`appsettings.json` `Demote` block.
|
|
|
|
### `read`
|
|
|
|
```powershell
|
|
# Integer
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a N7:10 -t Int
|
|
|
|
# Float
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a F8:0 -t Float
|
|
|
|
# Bit-within-word
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a B3:0/3 -t Bit
|
|
|
|
# Long (SLC 5/05+)
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a L19:0 -t Long
|
|
|
|
# Timer ACC
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a T4:0.ACC -t TimerElement
|
|
|
|
# Diagnostic counter (PR ablegacy-10 / #253). The seven _Diagnostics/<name>
|
|
# addresses live alongside user tags — short-circuit serves them straight from
|
|
# the in-process counter store, so no PCCC frame is sent to the PLC.
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 --address _Diagnostics/RequestCount
|
|
```
|
|
|
|
The diagnostic surface auto-emits per device — no config required. See
|
|
`docs/drivers/AbLegacy-Diagnostics.md` for the full counter table + reset
|
|
semantics + collision-rejection rules.
|
|
|
|
### `write`
|
|
|
|
```powershell
|
|
otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a N7:10 -t Int -v 42
|
|
otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a F8:0 -t Float -v 3.14
|
|
otopcua-ablegacy-cli write -g ab://192.168.1.20/1,0 -a B3:0/3 -t Bit -v on
|
|
```
|
|
|
|
Writes to timer / counter / control sub-elements land at the wire level but
|
|
the PLC's runtime semantics (EN/DN edge-triggering, preset reload) are
|
|
PLC-managed — use with caution.
|
|
|
|
### `subscribe`
|
|
|
|
```powershell
|
|
otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a N7:10 -t Int -i 500
|
|
```
|
|
|
|
#### Deadband
|
|
|
|
PR 8 — per-tag absolute / percent change filter on top of the polled subscription. The driver
|
|
caches the last *published* value per tag and suppresses `OnDataChange` notifications until the
|
|
new sample crosses the configured threshold.
|
|
|
|
| Flag | Effect |
|
|
|---|---|
|
|
| `--deadband-absolute <value>` | Suppress until `|new - prev| >= value`. |
|
|
| `--deadband-percent <value>` | Suppress until `|new - prev| >= |prev * value / 100|`. `prev == 0` always publishes (avoids div-by-zero). |
|
|
|
|
Booleans bypass the filter entirely (every transition publishes); strings + status changes
|
|
always publish; first-seen always publishes; both flags set → either passing triggers a
|
|
publish (Kepware-style logical OR).
|
|
|
|
```powershell
|
|
# Float — drop sub-0.5 jitter from the noisy load-cell address.
|
|
otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a F8:0 -t Float -i 500 `
|
|
--deadband-absolute 0.5
|
|
|
|
# Integer — only fire on >= 5% deviation from the last reported value.
|
|
otopcua-ablegacy-cli subscribe -g ab://192.168.1.20/1,0 -a N7:10 -t Int -i 500 `
|
|
--deadband-percent 5
|
|
```
|
|
|
|
## Array reads
|
|
|
|
PR 7 — one PCCC frame can carry up to ~120 words. Address an array tag with either the
|
|
Rockwell-native `,N` suffix or the libplctag-native `[N]` suffix on the word number; both
|
|
forms canonicalise to `[N]` when the driver hands the tag to libplctag, and the parser
|
|
caps `N` at 120.
|
|
|
|
```powershell
|
|
# Rockwell `,N` form — "10 consecutive words starting at N7:0"
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0,10" -t Int
|
|
|
|
# libplctag `[N]` form — same wire result
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0[10]" -t Int
|
|
|
|
# Float / Long arrays — same suffix syntax, narrower frame ceiling on Float (~60 elements)
|
|
# and Long (~60 elements) because each element is 4 bytes vs Int's 2.
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "F8:0,4" -t Float
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "L19:0,4" -t Long
|
|
|
|
# --array-length override — pin the element count from config rather than the address
|
|
# suffix. Wins over the parsed `,N` / `[N]` value when both are set; useful for keeping the
|
|
# address string compact while bumping the element count from a tags config file.
|
|
otopcua-ablegacy-cli read -g ab://192.168.1.20/1,0 -a "N7:0" --array-length 10 -t Int
|
|
```
|
|
|
|
Array tags reject sub-element references (`T4:0,5.ACC`) and bit suffixes (`N7:0,10/3`) at
|
|
parse time — both combinations are semantically meaningless against a contiguous block.
|
|
|
|
For `B`-files the Rockwell convention is "one BOOL per word, not per bit": `B3:0,10`
|
|
returns `bool[10]` (one per word's non-zero state), not `bool[160]`.
|
|
|
|
### `import-rslogix`
|
|
|
|
ablegacy-11 / [#254](https://github.com/dohertj2/lmxopcua/issues/254) — bulk-import RSLogix
|
|
500 / 5 CSV symbol exports into an `appsettings.json` tag fragment. Avoids hand-typing every
|
|
`N7:0` / `F8:12` / `B3:0/5` row of a several-hundred-tag PLC. Binary `.RSS` / `.RSP` project
|
|
files are out of scope; export to CSV first.
|
|
|
|
```powershell
|
|
# Default: emit JSON fragment to stdout
|
|
otopcua-ablegacy-cli import-rslogix `
|
|
--file C:\plc\plc-export.csv `
|
|
--device ab://192.168.1.20/1,0
|
|
|
|
# Write the fragment to a file + print a summary line to stdout
|
|
otopcua-ablegacy-cli import-rslogix `
|
|
--file C:\plc\plc-export.csv `
|
|
--device ab://192.168.1.20/1,0 `
|
|
--output tags.json
|
|
|
|
# Filter by Scope column — only import Local:1 program-scoped tags
|
|
otopcua-ablegacy-cli import-rslogix `
|
|
--file C:\plc\plc-export.csv `
|
|
--device ab://192.168.1.20/1,0 `
|
|
--scope Local:1
|
|
|
|
# Summary mode — one-line counter for CI / health checks
|
|
otopcua-ablegacy-cli import-rslogix `
|
|
--file C:\plc\plc-export.csv `
|
|
--device ab://192.168.1.20/1,0 `
|
|
--emit summary
|
|
```
|
|
|
|
| Flag | Default | Purpose |
|
|
|---|---|---|
|
|
| `-f` / `--file` | **required** | RSLogix CSV path |
|
|
| `-d` / `--device` | **required** | `ab://host[:port]/cip-path` every imported tag binds to |
|
|
| `--emit` | `appsettings-fragment` | `appsettings-fragment` (JSON) or `summary` (one-line counter) |
|
|
| `-o` / `--output` | stdout | Optional output file path |
|
|
| `--scope` | none | Scope filter — `Global` / `Local:N` (case-insensitive); empty Scope counts as Global |
|
|
| `--max-rows` | unlimited | Defensive cap on rows imported |
|
|
| `--strict` | off | Fail-fast on first malformed row (default permissive: skip + log) |
|
|
|
|
See [drivers/AbLegacy-RSLogix-Import.md](drivers/AbLegacy-RSLogix-Import.md) for the full
|
|
column reference, file-letter → `AbLegacyDataType` mapping, and the API surface
|
|
(`IRsLogixImporter`, `AbLegacyDriverOptions.AddRsLogixImport`).
|
|
|
|
## Known caveat — ab_server upstream gap
|
|
|
|
The integration-fixture `ab_server` Docker container accepts TCP but its PCCC
|
|
dispatcher doesn't actually respond — see
|
|
[`tests/...AbLegacy.IntegrationTests/Docker/README.md`](../tests/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.IntegrationTests/Docker/README.md).
|
|
Point `--gateway` at real hardware or an RSEmulate 500 box for end-to-end
|
|
wire-level validation. The CLI itself is correct regardless of which endpoint
|
|
you target.
|