# AB Legacy Driver
In-process native-protocol driver that exposes legacy Allen-Bradley PLCs —
**SLC 500**, **MicroLogix**, **PLC-5**, and Logix-via-PCCC — as OPC UA nodes. It
runs inside the OtOpcUa server's .NET 10 AnyCPU process and speaks PCCC over
EtherNet/IP through the same libplctag.NET wrapper as the AB CIP driver, but
addresses data by **file** (data-table) rather than by symbolic tag. One driver
instance can serve many devices; per-device routing is keyed on the canonical
`ab://gateway[:port]/cip-path` host-address string. PCCC has no native push
model, so subscriptions are a polling overlay on top of `IReadable`.
For the driver spec (capability surface, config shape, payload limits), see
[docs/v2/driver-specs.md §4](../v2/driver-specs.md). For the manual test client,
see [Driver.AbLegacy.Cli.md](../Driver.AbLegacy.Cli.md). For the integration
fixture coverage map, see [AbLegacy-Test-Fixture.md](AbLegacy-Test-Fixture.md).
## Project Layout
| Project | Role |
|---------|------|
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy/` | The driver — `AbLegacyDriver`, the libplctag runtime wrapper, the PCCC file-address parser (`AbLegacyAddress`), the host-address parser, and the status mapper. |
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Contracts/` | `AbLegacyDriverOptions`, `AbLegacyDeviceOptions`, `AbLegacyTagDefinition`, and the `AbLegacyDataType` / `AbLegacyPlcFamily` / `AbLegacyPlcFamilyProfile` records bound from the driver's `DriverConfig` JSON. |
Per family the `AbLegacyPlcFamilyProfile` supplies the libplctag `plc` attribute,
default CIP path, max-payload bytes, and the `SupportsStringFile` /
`SupportsLongFile` capability flags. MicroLogix uses direct EIP (empty default
path); MicroLogix and PLC-5 don't ship L-files; PLC-5 predates them entirely.
Tag types are validated against the device's profile at init time — declaring a
`Long` or `String` tag on a family that can't support it fails fast with a clear
message.
## Capability Surface
`AbLegacyDriver : IDriver, IReadable, IWritable, ITagDiscovery, ISubscribable, IHostConnectivityProbe, IPerCallHostResolver, IDisposable, IAsyncDisposable`
(`Driver.AbLegacy/AbLegacyDriver.cs`). There is **no `IAlarmSource`** — unlike the
AB CIP driver, PCCC has no ALMD instruction to project, so alarms are out of
scope.
| Capability | Implementation entry point | Notes |
|------------|---------------------------|-------|
| `ITagDiscovery` | `DiscoverAsync` | Emits pre-declared tags under per-device folders. Tags are single-element today (`IsArray` hard-wired false); multi-element file ranges are a tracked follow-up. |
| `IReadable` | `ReadAsync` | Per-tag reads serialized per cached runtime under a lock (a libplctag `Tag` handle is not concurrency-safe across the server read path + poll loop). |
| `IWritable` | `WriteAsync` | Bit-within-word writes (N/L-file `N7:0/3`, B-file `B3:0/0`, and I/O image files `I:0/0`/`O:1/2`) do a per-parent-word read-modify-write under a lock. An Input-image (`I`) write is forwarded to the PLC and may be rejected by the device (the device drives the input image from physical inputs); the driver surfaces the device's real PCCC status in that case. Non-writable tags return `BadNotWritable`. |
| `ISubscribable` | `SubscribeAsync` driven by the shared `PollGroupEngine` | No push model — subscriptions become polling groups. |
| `IHostConnectivityProbe` | `ProbeLoopAsync` + `GetHostStatuses` | One probe loop per device reading `Probe.ProbeAddress`; transitions log Warning (down) / Information (recover). |
| `IPerCallHostResolver` | `ResolveHost` | Routes each call to the tag's `DeviceHostAddress`; unknown references fall back to the first device, never throwing (per the interface contract). |
## Addressing Model
Per-device host addresses are the canonical `ab://gateway[:port]/cip-path` form
parsed by `AbLegacyHostAddress.TryParse`. When the parsed CIP path is empty the
family profile's default path is used (e.g. SLC 500 gets `1,0`; MicroLogix stays
empty for direct EIP).
Tags carry a PCCC **file address** parsed by `AbLegacyAddress` (`AbLegacyAddress.cs`)
— file letter + file number + word number, with an optional bit index (`/N`) or
structured sub-element (`.ACC`, `.PRE`, …). The string is passed straight through
to libplctag's `name=` attribute; the parser validates shape and surfaces the
pieces for driver-side routing (e.g. deciding a bit needs read-modify-write):
| Form | Meaning |
|------|---------|
| `N7:0` | Integer file 7, word 0 (signed 16-bit) |
| `F8:0` | Float file 8, word 0 (32-bit IEEE-754) |
| `B3:0/0` | Bit file 3, word 0, bit 0 |
| `L9:0` | Long-integer file (SLC 5/05+, 32-bit) |
| `ST9:0` | String file (82-byte fixed-length) |
| `T4:0.ACC` / `C5:0.PRE` | Timer / counter sub-element |
| `I:0/0` / `O:1/2` / `S:1` | Input / output / status system files (no file number) |
| `I:017/07` | **PLC-5 only:** `I:`/`O:` word and bit indices are **octal** (#244); a digit 8/9 is a parse error |
| `RTC:0.HR` / `HSC:0.ACC` | **MicroLogix only:** function files RTC, HSC, DLS, MMI, PTO, PWM, STI, EII, IOS, BHI (#245) |
| `N7:[N7:0]` / `N[N7:0]:5` | Indirect (index word read from the PLC) — resolved at read/write time (#646) |
`AbLegacyDataType` covers the corresponding PCCC types: `Bit`, `Int` (N), `Long`
(L), `Float` (F), `AnalogInt` (A), `String` (ST), and the `TimerElement` /
`CounterElement` / `ControlElement` sub-element families. The parser enforces
PCCC structural rules — bit-addressing only on 16/32-bit element files,
sub-elements only on T/C/R files, no file number on I/O/S — rejecting malformed
addresses before they reach libplctag.
**Bit-within-word writes** — B-file (`B3:0/0`), I/O image (`I:0/0`, `O:1/2`),
N-file (`N7:0/3`), and L-file bit addresses all use the same parent-word
read-modify-write (RMW) path: the driver reads the parent word, flips the target
bit, and writes the word back, under a per-parent lock. The lock serialises the
driver's own concurrent bit-writers against the same word, but cannot guard
against the PLC program writing that word between the driver's read and write —
this is an inherent limitation of any software-level RMW. Input-image (`I`) bit
writes are forwarded to the PLC as-is; the device drives the input image from
physical inputs and may reject the write.
### Family-specific address forms (#244 / #245 / #247)
`AbLegacyAddress.TryParse(text, family)` is family-aware; the driver passes the device's `PlcFamily`
(the one-argument overload is the family-neutral grammar: decimal, no function files).
- **PLC-5 octal I/O (#244).** RSLogix 5 shows `I:`/`O:` word and bit indices in octal, so `I:017/07` is word 15,
bit 7 and `I:017/17` is bit 15. Only `I`/`O` on PLC-5 (`OctalIoAddressing` on the family profile) — SLC,
MicroLogix and Logix-PCCC stay decimal, and PLC-5 `N`/`B`/... files stay decimal. The record stores decimal and
`ToLibplctagName()` **emits decimal**, so the libplctag `name=` string and the string the native transport
re-parses carry identical numbers. This is not a double conversion: libplctag's `pccc.c`
(`parse_pccc_elem_num` / `parse_pccc_bit_num`) parses decimal numerals only (a FIXME there says octal is
unsupported), so the driver must convert. Pinned by `Plc5_io_indices_are_octal` (`I:017/17` -> `I:15/15`).
The connectivity-probe address is normalised the same way.
- ⚠️ **Behaviour change / migration.** Before this change a PLC-5 `I:`/`O:` address was passed to libplctag as
written, i.e. read as **decimal**. An address copied from RSLogix in octal (e.g. `I:017`) therefore read the
wrong word, and an authored decimal such as `I:1/12` now means bit 10 (octal 12). A previously "working"
address containing the digits 8 or 9 (`I:018`, `O:1/9`) is no longer valid on PLC-5. Re-author any PLC-5
I/O tags in RSLogix octal. Such a tag is refused (see below), never silently misread.
- **A malformed / family-invalid address** (also: a function-file letter off MicroLogix) reads and writes
`BadNodeIdUnknown` for that tag only, creates no runtime, leaves driver health alone, and logs **one**
Warning per tag. The same check (`AbLegacyAddress.Validate`) runs in the AdminUI tag editor (family-independent:
rejects only what *no* family accepts) and the deploy gate (`EquipmentTagConfigInspector`, using the device's
`DeviceConfig.PlcFamily`, absent = SLC 500, unrecognised = unknown) — so `I:018` on a PLC-5 device warns at
deploy (an error under `TagConfigValidationMode.Error`), and the editor is never stricter than the gate.
- **MicroLogix function files (#245).** `RTC`, `HSC`, `DLS`, `MMI`, `PTO`, `PWM`, `STI`, `EII`, `IOS`, `BHI`
(single fixed instance — no file number — with a `.SUBELEMENT`; no bit index) parse on MicroLogix devices only.
`AbLegacyFunctionFile.SubElementType` carries the sub-element catalogue (flags → Boolean, words → Int32; unknown
members default to Int32). ⚠️ **Wire-unverified on both transports:** there is no capture and no simulator
coverage; the libplctag path passes the name through and the native transport has no file-type code for them, so
it refuses the tag as `Unsupported` (`BadNotSupported` to the client; see Wire evidence).
- **Indirect addressing (#247 parse, #646 runtime).** `N7:[N7:0]` (word from another address) and `N[N7:0]:5` (file
from another address) parse, one level deep (the inner address must be direct, and carries the family's octal rule).
At runtime the driver reads the inner address first (same runtime factory, so libplctag and Native alike), requires
an integer in range (word/element `0..255`, or `0..999` on PLC-5/LogixPccc; file `0..999`), composes the concrete address and runs the normal
read/write path against it. **The index is re-read on every read/write - never cached** - and the previous
resolution's handle is released when the index moves. A bad index (negative, too large, float/string source) is
`BadOutOfRange` for that tag only (no health impact); an inner-read failure propagates its own status (a wire
failure also degrades health like any read). **Writes** resolve then write and are **not atomic**: the index can
change between the two PLC accesses. Bit RMW writes (`B3:[N7:0]/4`) resolve first, then RMW the concrete word.
The Native transport never sees the bracket form (it receives the composed name), so N-file indirect stays inside
the wire-proven envelope; other file types are as (un)verified as their direct forms. Live-gated on `ab_server`
by `AbLegacyIndirectAddressingTests` (`N7:0=5`, `N7:5=42`, `N7:[N7:0]` reads 42).
## Configuration
`AbLegacyDriverOptions` (`Driver.AbLegacy.Contracts/AbLegacyDriverOptions.cs`)
binds from the driver's `DriverConfig` JSON:
- **`Devices`** — one `AbLegacyDeviceOptions` per PLC (`HostAddress`, `PlcFamily`, optional `DeviceName`).
- **`Tags`** — pre-declared `AbLegacyTagDefinition` list (`Name`, `DeviceHostAddress`, `Address`, `DataType`, `Writable`, `WriteIdempotent`).
- **`Probe`** — connectivity-probe `Enabled` / `Interval` / `Timeout` / `ProbeAddress`.
- **`Transport`** — absent (default ⇒ `Libplctag`), `Native` (opt-in), or `Libplctag`; see [Transport](#transport-transport-option).
Full per-field descriptions live in the contracts assembly. The JSON skeleton is
reproduced in [docs/v2/driver-specs.md §4](../v2/driver-specs.md).
## Transport (`transport` option)
Same switch as AB CIP: `transport` = absent \| `Native` \| `Libplctag`, a string (case-insensitive on read,
written as `"Libplctag"` / `"Native"`; "use the default" is encoded by omitting the key). `Native` is a managed
PCCC-over-EtherNet/IP client (`Driver.Ab.Transport`).
**Default resolution** (one place, `AbLegacyTransportResolver`, used by the driver, the Test Connect probe and
the CLI): an absent key resolves to **`Libplctag` for every PLC family** — unchanged from before the native
transport existed. **`Native` is opt-in** (final review I3: on a wire it is proven only for N-file reads and
writes and one F8 read — see [Wire evidence](#wire-evidence-native-pccc)). An explicit value always wins:
explicit `Native` with a PLC-5 / `LogixPccc` device is allowed (an operator choice) and logs one Warning per
driver instance naming the limitation. (AbCip's node-level `Drivers:AbCip:DefaultTransport` has no AbLegacy
counterpart — the AbLegacy default is libplctag and is not node-configurable.)
A change takes effect when the driver instance is constructed: on a deploy that changes `DriverConfig`
(which recreates it) **and on every process start**, including the restart that installs this build (see the
release note). The
AdminUI form's **Transport** dropdown offers "Default (libplctag)" (omits the key on save), "Native (managed,
opt-in)" and "libplctag". The driver logs `transport=<effective> (default|configured)` on every init, e.g.
`transport=Libplctag (default)`. CLI: `--transport default|native|libplctag` (default `default` = libplctag for
every `--plc-type`). See
[AbCip.md §Transport](AbCip.md#transport-transport-option) for the shared behaviour (one pooled connection
per device, Forward Open throttle, routing).
Native routing: SLC500/MicroLogix/PLC-5 are direct; `logixpccc` uses UnconnectedSend and its SLC framing is
**unverified**.
### Release note — native PCCC transport, opt-in (final review I3)
- **The default is unchanged: libplctag.** A driver config with no `transport` key runs `Libplctag`, for
every PLC family, exactly as before this release. The upgrade restart moves nothing. (An interim build on
this branch defaulted SLC 500 / MicroLogix to Native; that was reverted before merge.)
- **`"transport": "Native"` opts a driver into the managed PCCC-over-EtherNet/IP client** (`Driver.Ab.Transport`).
It takes effect when the driver is constructed — a deploy that changes `DriverConfig`, or a process start —
not on `ReinitializeAsync`. The AdminUI **Transport** dropdown authors it; remove the key (or pick
"Default (libplctag)") to go back.
- **Known limits of Native** (why it is opt-in):
- ⚠️ **Wire evidence is narrow and simulator-only** — see [Wire evidence](#wire-evidence-native-pccc). Only
N-file reads and writes and one F8 read have touched a wire (`ab_server`). The **default probe address
`S:0`** and the **B, T, C, R, S, L, ST, A, O and I file types** — and the T/C/R sub-element offsets
(`.PRE`/`.ACC`/`.LEN`/`.POS`) — are encoded from the PCCC file-type table and are **unverified natively**.
No real SLC, MicroLogix or PLC-5 has been exercised. Opt in per driver after checking it against the real
controller.
- ⚠️ **Status-bit writes are refused** — `T4:0.DN`, `T4:0.TT`, `T4:0.EN`, `C5:0.CU`, `C5:0.DN`, `R6:0.EN`
and the rest return **`BadNotSupported`** whatever the tag's authored data type (the refusal keys on the
address); nothing is written to the PLC; health is unchanged. The driver answers the refusal **before it
creates the tag's runtime**, so a first-touch write sends nothing at all — not even the init read, which
against a controller without that file used to surface as `BadCommunicationError` + Degraded health (#593
follow-up). PLC-5 writes are refused the same way. libplctag performs a masked bit write here; a native
read-modify-write of the control word would race the PLC updating TT/DN. Reads of status bits are unaffected.
- ⚠️ **On libplctag (the default) a status-bit write is NOT refused** — it goes to the controller as a write to the
timer/counter/control element (libplctag's bit-tag write; not exercised on a wire — `ab_server` has no T/C/R
files). Nothing in authoring prevents it: the address is free text,
any `dataType` may be chosen (a status bit is naturally authored `Bit`), and `writable` defaults to `true`.
Author status-bit tags with `"writable": false` unless writing them is genuinely intended.
- **PLC-5 native is N-file reads only**; every other PLC-5 operation is refused with `BadNotSupported`.
`LogixPccc` framing is unverified. Explicit Native on either logs a Warning at init.
- **ST (string) byte order is unverified** (no capture); string values may be byte-swapped.
- Unlike AbCip, the native AbLegacy runtime has **no element-type check**, so a mis-authored same-width
type reads as reinterpreted data (as on libplctag), not `BadTypeMismatch`.
- Releasing a native tag (evict, reinitialize, shutdown) never blocks on the connection close: the lease
is released in the background (`ConnectionLease.ReleaseInBackground`), the same shape as native AbCip
(#579). A re-create cannot overlap the close, because the pool holds the successor connection behind it.
### Wire evidence (native PCCC)
Everything below is against the `ab_server` simulator; no real PCCC controller has been exercised.
| What | Evidence |
|---|---|
| N-file read (`N7:0`) | libplctag captures `slc500-read-n7`, `micrologix-read-n7`, `plc5-read-n7` (codec byte parity) + native `AbLegacyReadSmokeTests` read on all three profiles |
| N-file write (`N7:5`) | capture `slc500-write-n7` + native `AbLegacyReadSmokeTests` write/read round trip (SLC 500) |
| F-file read (`F8`) | one capture, `slc500-read-f8` (codec parity only; no native F write on a wire) |
| S (incl. the default probe `S:0`), B, T, C, R, L, ST, A, O, I | **none** — encoded from the PCCC file-type table |
| MicroLogix function files (RTC/HSC/...), PLC-5 octal I/O | **none** — parsed only; native refuses function files as Unsupported |
| Bit-within-word write (`B3:0/5`) | `ab_server` SLC500 + MicroLogix, both transports (`AbLegacyBitWriteTests`): the driver RMWs the parent word, only the addressed bit changes. PLC-5 native refuses it (`BadNotSupported`, #571) |
| Indirect addressing (`N7:[N7:0]`) | `ab_server` N-file, both transports (#646) - resolved by the driver, the transport sees the composed address |
| T/C/R sub-elements (`.PRE`/`.ACC`/`.LEN`/`.POS`), 6-byte T/C/R element layout | **none** |
### Native known gaps
- ⚠️ **Simulator-only, and narrow.** Only N-file reads/writes and one F8 read are on a wire (`ab_server`); see
[Wire evidence](#wire-evidence-native-pccc). No real SLC/MicroLogix/PLC-5 has been exercised; the real-press
gate (Task 21) was read-only and AbCip-only.
- **PLC-5 native is N-file reads only.** Every other file type and all PLC-5 writes are refused before the
wire and reach the client as `BadNotSupported` (handle kept, health unchanged; #571 closed). Native is opt-in
for every family; an explicit Native on PLC-5 / `logixpccc` logs a Warning at init.
- Status-bit sub-element writes (e.g. `T4:0.DN`, `C5:0.DN`) are Unsupported natively (they would clobber the
control word); nothing goes on the wire — the driver refuses before creating the tag's runtime, so not even an
init read is sent (`NativeAbLegacyTagRuntime.WriteRefusal` is the single predicate, asked through
`IAbLegacyTagFactory.WriteRefusal`). Pinned offline by `NativeAbLegacyRefusedWriteTests` and on `ab_server` by
`AbLegacyUnsupportedPathTests` (whose SLC500 fixture has no T/C/R files, which is what makes it discriminating). Sub-element arrays are Unsupported natively. L-file bit indexes
above 15 are allowed.
- **ST (string) file layout is uncaptured**, so the string byte order is unverified natively.
- Capture recipe for golden frames: `scripts/ab-capture/capture.sh` (see
[AbLegacy-Test-Fixture.md](AbLegacy-Test-Fixture.md)). Follow-up issues: #564 to #577.
## Testing
- **Unit tests** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Tests/` cover the driver, the PCCC address parser, and the host-address parser via fake tag runtimes.
- **Integration tests** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.IntegrationTests/` run against the AB Legacy Docker fixture. See [AbLegacy-Test-Fixture.md](AbLegacy-Test-Fixture.md) for the coverage map.
- **Manual client** — [Driver.AbLegacy.Cli.md](../Driver.AbLegacy.Cli.md).
## 1-D array support
An AB Legacy tag becomes a **1-D OPC UA array node** when its `TagConfig` JSON carries
`"isArray": true` and `"arrayLength": N` (N ≥ 1, capped at 256). The canonical rule:
`isArray: true` + `arrayLength >= 1` → array; `isArray: false` (any length) → scalar.
**Read mechanism** — the driver issues a **PCCC multi-element file read** (libplctag by default; the opt-in
native transport issues the same typed read, chunked under the PCCC payload limit).
The tag's file address (e.g. `N7:0`) is extended by `N` element count so the transport fetches
`N` consecutive PCCC file elements in one EIP/PCCC request. The response is decoded into
N values of the declared `AbLegacyDataType`. Maximum element count is 256 (PCCC payload
limit).
This closes the previously-noted limitation ("single-element addressing today") for the
array read path. The opt-in native transport also writes multi-element arrays (chunked); on libplctag
array *writes* remain a follow-up.
**Unit test coverage** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.AbLegacy.Tests/` covers
the multi-element read path via the fake tag runtime. The AB Legacy integration fixture is
down during normal dev.
**Live-verify** — integration-fixture-gated (requires the AB Legacy Docker fixture).
**Deferrals** — array *writes* on libplctag (the opt-in native transport writes them), multi-dimensional arrays, per-element historization.
`arrayLength > 256` is rejected at init with an explicit error (PCCC payload cap).
See [Uns.md §Array tags](../Uns.md#array-tags-1-d) for the cross-driver coverage matrix
and the UI authoring flow.
## Operational Notes
- **Native heap is invisible to the GC.** As with AB CIP, libplctag's native heap does not show up in CLR allocation figures; watch whole-process RSS and use `ReinitializeAsync` to recycle libplctag handles. (`IDriver.GetMemoryFootprint()` was deleted as unconsumed in Gitea #525.)
- **PCCC reconnect is more expensive than CIP** — legacy PLCs have no connection multiplexing, so the resilience pipeline should use longer backoff than for AB CIP (see [docs/v2/driver-specs.md §4](../v2/driver-specs.md)).
- **Single-element addressing today** — a PCCC file is inherently an array (an N7 file is up to 256 words), but the current tag surface addresses one element per tag; range-spanning tags must be enumerated element-by-element until multi-element addressing lands.