otopcua-abcip-cli — AB CIP test client
Ad-hoc probe / read / write / subscribe tool for ControlLogix / CompactLogix /
Micro800 / GuardLogix PLCs, talking to the same AbCipDriver the OtOpcUa
server uses (libplctag under the hood).
Second of four driver test-client CLIs (Modbus → AB CIP → AB Legacy → S7 →
TwinCAT). Shares Driver.Cli.Common with the others.
Build + run
dotnet run --project src/ZB.MOM.WW.OtOpcUa.Driver.AbCip.Cli -- --help
Common flags
| Flag | Default | Purpose |
|---|---|---|
-g / --gateway |
required | Canonical ab://host[:port]/cip-path |
-f / --family |
ControlLogix |
ControlLogix / CompactLogix / Micro800 / GuardLogix |
--timeout-ms |
5000 |
Per-operation timeout |
--addressing-mode |
Auto |
Auto / Symbolic / Logical — see AbCip-Performance §Addressing mode. Logical against Micro800 silently falls back to Symbolic with a warning. |
--partner |
(unset) | PR abcip-5.1 — partner gateway URI for a ControlLogix HSBY pair (e.g. ab://10.0.0.6/1,0). When set, the driver runs a second role-probe loop against the partner and the hsby-status command can surface which chassis is currently Active. See AbCip-HSBY.md for the full guide. |
--verbose |
off | Serilog debug output |
Family ↔ CIP-path cheat sheet:
- ControlLogix / CompactLogix / GuardLogix —
1,0(slot 0 of chassis) - Micro800 — empty path, just
ab://host/ - Sub-slot Logix (rare) —
1,3for slot 3
Commands
probe — is the PLC up?
# ControlLogix — read the canonical libplctag system tag
otopcua-abcip-cli probe -g ab://10.0.0.5/1,0 -t @raw_cpu_type --type DInt
# Micro800 — point at a user-supplied global
otopcua-abcip-cli probe -g ab://10.0.0.6/ -f Micro800 -t _SYSVA_CLOCK_HOUR --type DInt
read — single Logix tag
# Controller scope
otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real
# Program scope
otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Program:Main.Counter" --type DInt
# Array element
otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Recipe[3]" --type Real
# UDT member (dotted path)
otopcua-abcip-cli read -g ab://10.0.0.5/1,0 -t "Motor01.Speed" --type Real
Diagnostic / system tags
PR abcip-4.3 exposes five read-only diagnostic variables per device under
AbCip/<device>/_System/ in the OPC UA address space (see
AbCip-Operability §System tags
for the full table). These are not reachable through the AB CIP CLI — they
live on the OPC UA server side, not the libplctag wire — so to read one,
point the OPC UA client CLI at the running OtOpcUa server:
# Read _ConnectionStatus for one device through the OPC UA server
otopcua-client-cli read -u opc.tcp://localhost:4840 \
-n "ns=2;s=AbCip/ab://10.0.0.5/1,0/_System/_ConnectionStatus"
write — single Logix tag
Same shape as read plus -v. Values parse per --type using invariant
culture. Booleans accept true/false/1/0/yes/no/on/off.
Structure (UDT) writes need the member layout declared in a real driver config
and are refused by the CLI.
otopcua-abcip-cli write -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real -v 3.14
otopcua-abcip-cli write -g ab://10.0.0.5/1,0 -t StartCommand --type Bool -v true
subscribe — watch a tag until Ctrl+C
otopcua-abcip-cli subscribe -g ab://10.0.0.5/1,0 -t Motor01_Speed --type Real -i 500
hsby-status — which chassis is Active now?
PR abcip-5.1 — read the role tag (WallClockTime.SyncStatus by default,
S:34 for legacy SLC500 / PLC-5 fronts) on a ControlLogix HSBY pair and
print which chassis is currently Active. Requires --partner.
otopcua-abcip-cli hsby-status -g ab://10.0.0.5/1,0 --partner ab://10.0.0.6/1,0
# Custom role tag (legacy fronts) and more samples
otopcua-abcip-cli hsby-status -g ab://10.0.0.5/1,0 --partner ab://10.0.0.6/1,0 \
--role-tag S:34 --samples 5
| Flag | Default | Purpose |
|---|---|---|
--role-tag |
WallClockTime.SyncStatus |
Address of the role tag. Use S:34 for SLC500 / PLC-5. |
--samples |
3 |
Number of role-probe ticks to wait for before printing. |
The output prints the resolved roles + the address of whichever chassis the driver currently considers Active. PR abcip-5.1 only reports the role — PR abcip-5.2 will land the routing change so reads / writes flow to the Active chassis automatically.
See AbCip-HSBY.md for the role-tag detection matrix
- active-resolution rules + the feature-flag gate.
rebrowse — force a controller-side @tags re-walk
PR abcip-2.5 (issue #233) added RebrowseAsync to drop the cached UDT
template shapes and re-run the symbol-table enumerator without restarting
the driver. The CLI variant builds a transient driver against the supplied
gateway, runs the rebrowse, and prints the freshly discovered tag names —
useful after a controller program-download to confirm the new tags are
visible on the wire before wiring them through the OtOpcUa server.
otopcua-abcip-cli rebrowse -g ab://10.0.0.5/1,0
Refreshing the tag DB
Two operator-facing surfaces drive the same RebrowseAsync plumbing — pick
the one that matches your context:
| Surface | When to use | Command |
|---|---|---|
CLI rebrowse |
Off-server validation. Spins up a transient driver against the gateway, prints the discovered tag list, no shared state with the live OtOpcUa server. | otopcua-abcip-cli rebrowse -g ab://10.0.0.5/1,0 |
OPC UA write to _RefreshTagDb |
Production / Admin-UI button (PR abcip-4.4). Forces the live driver to re-walk + clear its template cache. The AbCip.RefreshTriggers driver-diagnostics counter increments per truthy write. |
otopcua-client-cli write -u opc.tcp://localhost:4840 -n "ns=2;s=AbCip/ab://10.0.0.5/1,0/_System/_RefreshTagDb" -v true --type Boolean |
Read-back semantics: _RefreshTagDb always reads back as false (Kepware-
style "latches to idle the moment the dispatch returns") so a subscribed
client sees a stable shape regardless of how many refreshes have fired.
Falsy / unparseable writes are no-ops that still report Good so a UI
template that resets the trigger flag after firing it doesn't see a phantom
error. See
AbCip-Operability §System tags
for the full semantics + the diagnostics counter wiring.
Typical workflows
- "Is the PLC reachable?" →
probe. - "Did my recipe write land?" →
write+readback. - "Why is tag X flipping?" →
subscribe. - "Is this GuardLogix safety tag writable from non-safety?" →
writeand read the status code — safety tags surfaceBadNotWritable/ CIP errors, non-safety tags surfaceGood. - "Did my program download show up in the address space?" →
rebrowse(off-server) or writetrueto the live server's_RefreshTagDbsystem tag (in-server, PR abcip-4.4) — both drop the template cache + force a fresh@tagswalk.
Connection Size
PR abcip-3.1 introduced a per-device ConnectionSize override on the driver
side (AbCipDeviceOptions.ConnectionSize, range 500..4002). The CLI does
not expose a flag for it — every CLI invocation uses the family-default
Connection Size (4002 / 504 / 488 depending on --family). When a Forward
Open is rejected with a CIP error like 0x01/0x113 ("connection request
size invalid"), the symptom is almost always a mismatch between the chosen
family default and the controller firmware:
- v19-and-earlier ControlLogix caps at 504 — pick
--family CompactLogixon the CLI to fall back to that narrower default. - 5069-L1/L2/L3 CompactLogix narrow-buffer parts also cap at 504, which is the family default already.
- FW20+ ControlLogix accepts the full 4002.
For the warning "AbCip device 'X' family 'Y' uses a narrow-buffer profile
(default ConnectionSize Z); the configured ConnectionSize N exceeds the
511-byte legacy-firmware cap..." see
docs/drivers/AbCip-Performance.md — that
warning is fired by the driver host, not the CLI.
Related operability knobs
docs/drivers/AbCip-Operability.md— Phase 4 per-tag knobs (per-tag scan rate, deadband, etc). The CLI does not expose these knobs directly; they're set in driver config JSON and consumed by the driver at subscribe time.