# Siemens S7 Driver
Getting-started guide for the Siemens S7 driver. This is the short path — for
the full per-field spec read [`docs/v2/driver-specs.md §5`](../v2/driver-specs.md),
for hands-on CLI testing read [Driver.S7.Cli.md](../Driver.S7.Cli.md), and for
the test-harness map read [S7-Test-Fixture.md](S7-Test-Fixture.md).
## What it talks to
Siemens S7 PLCs — S7-300, S7-400, S7-1200, S7-1500, plus S7-200 / S7-200 Smart
/ LOGO! 0BA8 — over the native **S7comm** protocol on **ISO-on-TCP, TCP port
102**. The wire is spoken by the pure-managed [S7netplus](https://github.com/S7NetPlus/s7netplus)
(`S7.Net`) library: no native DLL, no P/Invoke, no out-of-process isolation. The
driver runs in-process in the OtOpcUa server's .NET 10 AnyCPU host on every OS
the server runs on.
This is the **leanest** OtOpcUa driver — read/write/subscribe/discover plus a
connectivity probe, and nothing else. It implements no alarm source and no
per-call host resolver (a single S7 instance targets a single CPU).
## Project split
| Project | Target | Role |
|---------|--------|------|
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7/` | net10.0 | In-process driver — hosts the `S7.Net.Plc` connection and the address parser |
| `src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7.Contracts/` | net10.0 | Dependency-free config records + enums (`S7DriverOptions`, `S7CpuType`, `S7DataType`) bound from `DriverConfig` JSON |
## Minimum deployment
Register the driver instance in the central config DB (or `appsettings.json`).
No separate service, no DLL deployment:
```jsonc
"Drivers": {
"s7-line-1": {
"Type": "S7",
"Config": {
"Host": "10.20.30.40",
"CpuType": "S71500",
"Rack": 0,
"Slot": 0,
"Tags": [
{ "Name": "Running", "Address": "DB1.DBX0.0", "DataType": "Bool", "Writable": false },
{ "Name": "Speed", "Address": "DB1.DBD4", "DataType": "Float32", "Writable": true }
]
}
}
}
```
S7 exposes a symbol table, but `S7.Net` does not surface it — so the driver
operates off a **static, per-site tag list**, not live symbol discovery.
### Rack / slot / CPU family
`CpuType` selects the ISO-TSAP slot byte used during the connection handshake;
pick the family that matches the PLC exactly. `Rack` is almost always `0`
(relevant only for distributed S7-400 racks). `Slot` conventions per family:
S7-300 = slot 2, S7-400 = slot 2 or 3, S7-1200 / S7-1500 = slot 0 (onboard PN).
A wrong slot causes a connection refusal during the handshake. See
`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7.Contracts/S7DriverOptions.cs` for the
per-field defaults.
## Address forms
Addresses use Siemens TIA-Portal / STEP 7 Classic syntax, parsed by
`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7/S7AddressParser.cs`:
| Area | Example | Meaning |
|------|---------|---------|
| Data block | `DB1.DBX0.0` / `DB1.DBW0` / `DB1.DBD4` | DB number + size suffix `X`(bit) / `B`(byte) / `W`(word) / `D`(dword), optional `.bit` for `DBX` |
| Merker (M) | `MB0` / `MW0` / `MD4` / `M0.0` | Marker byte; size prefix `B`/`W`/`D`, or bare offset `.bit` for bit access |
| Input (I) | `IB0` / `IW0` / `I0.0` | Process-image input |
| Output (Q) | `QB0` / `QW0` / `Q0.0` | Process-image output |
Parsing is strict and runs once at `InitializeAsync` so a config typo fails fast
at load instead of surfacing as `BadInternalError` on every read. Bit offsets
must be 0-7, byte offsets non-negative, DB numbers >= 1.
> **Timer (`T{n}`) and Counter (`C{n}`)** addresses parse cleanly but the read
> path has no decode case for them yet — the driver rejects them at init with an
> explicit error rather than letting them surface a misleading type-mismatch.
## Data types
`S7DataType` declares the **semantic** type; `S7.Net` returns an unsigned boxed
value (bool / byte / ushort / uint) that the driver reinterprets without an
extra PLC round-trip. Wired through today: `Bool`, `Byte`, `Int16`, `UInt16`,
`Int32`, `UInt32`, `Float32`. `Int64`, `UInt64`, `Float64`, `String`, and
`DateTime` are declared in the enum but **rejected at init** — half-implemented
types must not create OPC UA nodes that then return `BadNotSupported` on every
access.
## Capability surface
`S7Driver : IDriver, ITagDiscovery, IReadable, IWritable, ISubscribable, IHostConnectivityProbe`
(`src/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7/S7Driver.cs`).
| Capability | Path | Notes |
|------------|------|-------|
| `IReadable` | `ReadAsync``S7.Net.Plc.ReadAsync` | One request/response per tag, serialized on a per-PLC semaphore |
| `IWritable` | `WriteAsync``S7.Net.Plc.WriteAsync` | Read-only tags (`Writable=false`) return `BadNotWritable` |
| `ITagDiscovery` | `DiscoverAsync` | Emits a flat `S7/` folder of the configured tags — no live browse |
| `ISubscribable` | per-tag poll loop with capped exponential backoff | S7 has no push model; floor is 100 ms (the CPU services the comms mailbox once per scan) |
| `IHostConnectivityProbe` | periodic `S7.Net.Plc.ReadStatusAsync` (CPU-status PDU) | `host:port` host key; `Running`/`Stopped` transitions raise `OnHostStatusChanged` |
### Single-connection policy
One `S7.Net.Plc` instance per PLC, serialized with a `SemaphoreSlim`.
Parallelising reads against a single CPU doesn't help — the CPU scans its
comms mailbox at most once per cycle and queues concurrent requests wire-side
anyway, while wasting the CPU's 8-64 connection-resource budget.
## PUT/GET communication
S7-1200 / S7-1500 ship with **PUT/GET access disabled** by default. A driver
pointed at a freshly-flashed CPU sees a hard access-denied fault. The driver
maps it specifically to `BadNotSupported`, flags the instance `Faulted` (a
configuration alert, not a transient fault), and does **not** blind-retry —
because the CPU will keep refusing. Fix: enable PUT/GET communication in TIA
Portal under *Protection & Security* for the CPU.
## Error mapping
| Condition | StatusCode | Health |
|-----------|------------|--------|
| Tag not in config | `BadNodeIdUnknown` | unchanged |
| Read-only tag written | `BadNotWritable` | unchanged |
| Unimplemented data type | `BadNotSupported` | unchanged |
| PUT/GET denied | `BadNotSupported` | `Faulted` (config alert) |
| CPU / hardware fault | `BadDeviceFailure` | `Degraded` |
| Socket / timeout | `BadCommunicationError` | `Degraded` |
## Testing
- **Unit tests** — `tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7.Tests/` cover the
address parser, the reinterpret/box conversions, and the driver lifecycle.
- **Integration fixture** — a Docker S7 simulator on the shared docker host; see
[S7-Test-Fixture.md](S7-Test-Fixture.md) for the coverage map and endpoint.
- **CLI** — [Driver.S7.Cli.md](../Driver.S7.Cli.md) documents the standalone
read/write/probe CLI for manual checks against a real or simulated CPU.
## 1-D array support
An S7 tag becomes a **1-D OPC UA array node** when its `TagConfig` JSON carries
`"isArray": true` and `"arrayLength": N` (N ≥ 1). The canonical rule:
`isArray: true` + `arrayLength >= 1` → array; `isArray: false` (any length) → scalar.
**Read mechanism** — the driver issues a single `ReadBytesAsync` call over the contiguous
memory span starting at the declared address for `N × (bytes per element)` bytes, then
loops over the response buffer decoding each element individually using the same
reinterpret/box logic as scalar reads. This keeps wire round-trips at 1 per array tag
regardless of N.
**Supported element types** — any `S7DataType` that has a scalar decode path today
(`Bool`, `Byte`, `Int16`, `UInt16`, `Int32`, `UInt32`, `Float32`). The `ReadBytesAsync`
network half is a thin `S7.Net` call; the decode half is fully unit-tested.
**Unit test coverage**`tests/Drivers/ZB.MOM.WW.OtOpcUa.Driver.S7.Tests/` covers
the contiguous-block read and per-element decode loop. Integration fixture is down during
normal dev (the S7 sim is on the shared Docker host but currently offline).
**Live-verify** — integration-fixture-gated (not Mac-verifiable without the S7 sim up).
**Deferrals** — array *writes*, multi-dimensional arrays, per-element historization. The
`Timer` / `Counter` address types that are rejected at init for scalars are also excluded
for arrays.
See [Uns.md §Array tags](../Uns.md#array-tags-1-d) for the cross-driver coverage matrix
and the UI authoring flow.
## Further reading
- [`docs/v2/driver-specs.md §5`](../v2/driver-specs.md) — full per-field spec,
DriverConfig JSON shape, and operational stability notes
- [Driver.S7.Cli.md](../Driver.S7.Cli.md) — standalone S7 driver CLI
- [S7-Test-Fixture.md](S7-Test-Fixture.md) — simulator + test-harness map