lmxopcua/docs/drivers/Modbus-Test-Fixture.md
Joseph Doherty 96940aeb24 Modbus exception-injection profile — closes the end-to-end test gap for exception codes 0x01/0x03/0x04/0x05/0x06/0x0A/0x0B. pymodbus simulator naturally emits only 0x02 (Illegal Data Address on reads outside configured ranges) + 0x03 (Illegal Data Value on over-length); the driver's MapModbusExceptionToStatus table translates eight codes, but only 0x02 had integration-level coverage (via DL205's unmapped-register test). Unit tests lock the translation function in isolation but an integration test was missing for everything else. This PR lands wire-level coverage for the remaining seven codes without depending on device-specific quirks to naturally produce them.
New exception_injector.py — standalone pure-Python-stdlib Modbus/TCP server shipped alongside the pymodbus image. Speaks the wire protocol directly (MBAP header parse + FC 01/02/03/04/05/06/15/16 dispatch + store-backed happy-path reads/writes + spec-enforced length caps) and looks up each (fc, starting-address) against a rules list loaded from JSON; a matching rule makes the server respond [fc|0x80, exception_code] instead of the normal response. Zero runtime dependencies outside the stdlib — the Dockerfile just COPY's the script into /fixtures/ alongside the pymodbus profile JSONs, no new pip install needed. ~200 lines. New exception_injection.json profile carries rules for every exception code on FC03 (addresses 1000-1007, one per code), FC06 (2000-2001 for CPU-PROGRAM-mode and busy), and FC16 (3000 for server failure). New exception_injection compose profile binds :5020 like every other service + runs python /fixtures/exception_injector.py --config /fixtures/exception_injection.json.

New ExceptionInjectionTests.cs in Modbus.IntegrationTests — 11 tests. Eight FC03-read theories exercise every exception code 0x01/0x02/0x03/0x04/0x05/0x06/0x0A/0x0B asserting the driver's expected OPC UA StatusCode mapping (BadNotSupported/BadOutOfRange/BadOutOfRange/BadDeviceFailure/BadDeviceFailure/BadDeviceFailure/BadCommunicationError/BadCommunicationError). Two FC06-write theories cover the write path for 0x04 (Server Failure, CPU in PROGRAM mode) + 0x06 (Server Busy). One sanity-check read at address 5 confirms the injector isn't globally broken + non-injected reads round-trip cleanly with Value=5/StatusCode=Good. All tests follow the MODBUS_SIM_PROFILE=exception_injection skip guard so they no-op on a fresh clone without Docker running.

Docker/README.md gains an §Exception injection section explaining what pymodbus can and cannot emit, what the injector does, where the rules live, and how to append new ones. docs/drivers/Modbus-Test-Fixture.md follow-up item #2 (extend pymodbus profiles to inject exceptions) gets a shipped strikethrough with the new coverage inventory; the unit-level section adds ExceptionInjectionTests next to DL205ExceptionCodeTests so the split-of-responsibilities is explicit (DL205 test = natural out-of-range via dl205 profile, ExceptionInjectionTests = every other code via the injector).

Test baselines: Modbus unit 182/182 green (unchanged); Modbus integration with exception_injection profile live 11/11 new tests green. Existing DL205/S7/Mitsubishi integration tests unaffected since they skip on MODBUS_SIM_PROFILE mismatch.

Found + fixed during validation: a stale native pymodbus simulator from April 18 was still listening on port 5020 on IPv6 localhost (Windows was load-balancing between it + the Docker IPv4 forward, making injected exceptions intermittently come back as pymodbus's default 0x02). Killed the leftover. Documented the debugging path in the commit as a note for anyone who hits the same "my tests see exception 0x02 but the injector log has no request" symptom.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
2026-04-20 15:11:32 -04:00

124 lines
5.6 KiB
Markdown
Raw Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Modbus test fixture
Coverage map + gap inventory for the Modbus TCP driver's integration-test
harness backed by `pymodbus` simulator profiles per PLC family.
**TL;DR:** Modbus is the best-covered driver — a real `pymodbus` server on
localhost with per-family seed-register profiles, plus a skip-gate when the
simulator port isn't reachable. Covers DL205 / Mitsubishi MELSEC / Siemens
S7-1500 family quirks end-to-end. Gaps are mostly error-path + alarm/history
shaped (neither is a Modbus-side concept).
## What the fixture is
- **Simulator**: `pymodbus` (Python, BSD) launched as a pinned Docker
container at
`tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Docker/`.
Docker is the only supported launch path.
- **Lifecycle**: `ModbusSimulatorFixture` (collection-scoped) TCP-probes
`localhost:5020` on first use. `MODBUS_SIM_ENDPOINT` env var overrides the
endpoint so the same suite can target a real PLC.
- **Profiles**: `DL205Profile`, `MitsubishiProfile`, `S7_1500Profile`
each composes device-specific register-format + quirk-seed JSON for pymodbus.
Profile JSONs live under `Docker/profiles/` and are baked into the image.
- **Compose services**: one per profile (`standard` / `dl205` /
`mitsubishi` / `s7_1500`); only one binds `:5020` at a time.
- **Tests skip** via `Assert.Skip(sim.SkipReason)` when the probe fails; no
custom FactAttribute needed because `ModbusSimulatorCollection` carries the
skip reason.
## What it actually covers
### DL205 (Automation Direct)
- `DL205SmokeTests` — FC16 write → FC03 read round-trip on holding register
- `DL205CoilMappingTests` — Y-output / C-relay / X-input address mapping
(octal → Modbus offset)
- `DL205ExceptionCodeTests` — Modbus exception 0x02 → OPC UA `BadOutOfRange` against the dl205 profile (natural out-of-range path)
- `ExceptionInjectionTests` — every other exception code in the mapping table (0x01 / 0x03 / 0x04 / 0x05 / 0x06 / 0x0A / 0x0B) against the `exception_injection` profile on both read + write paths
- `DL205FloatCdabQuirkTests` — CDAB word-swap float encoding
- `DL205StringQuirkTests` — packed-string V-memory layout
- `DL205VMemoryQuirkTests` — V-memory octal addressing
- `DL205XInputTests` — X-register read-only enforcement
### Mitsubishi MELSEC
- `MitsubishiSmokeTests` — read + write round-trip
- `MitsubishiQuirkTests` — word-order, device-code mapping (D/M/X/Y ranges)
### Siemens S7-1500 (Modbus gateway flavor)
- `S7_1500SmokeTests` — read + write round-trip
- `S7_ByteOrderTests` — ABCD/DCBA/BADC/CDAB byte-order matrix
### Capability surfaces hit
- `IReadable` + `IWritable` — full round-trip
- `ISubscribable` — via the shared `PollGroupEngine` (polled subscription)
- `IHostConnectivityProbe` — TCP-reach transitions
## What it does NOT cover
### 1. No `ITagDiscovery`
Modbus has no symbol table — the driver requires a static tag map from
`DriverConfig`. There is no discovery path to test + none in the fixture.
### 2. Error-path fuzzing
`pymodbus` serves the seeded values happily; the fixture can't easily inject
exception responses (code 0x010x0B) or malformed PDUs. The
`AbCipStatusMapper`-equivalent for exception codes is unit-tested via
`DL205ExceptionCodeTests` but the simulator itself never refuses a read.
### 3. Variant-specific quirks beyond the three profiles
- FX5U / QJ71MT91 Mitsubishi variants — profile scaffolds exist, no tests yet
- Non-S7-1500 Siemens (S7-1200 / ET200SP) — byte-order covered but
connection-pool + fragmentation quirks untested
- DL205-family cousins (DL06, DL260) — no dedicated profile
### 4. Subscription stress
`PollGroupEngine` is unit-tested standalone but the simulator doesn't exercise
it under multi-register packing stress (FC03 with 125-register batches,
boundary splits, etc.).
### 5. Alarms / history
Not a Modbus concept. Driver doesn't implement `IAlarmSource` or
`IHistoryProvider`; no test coverage is the correct shape.
## When to trust the Modbus fixture, when to reach for a rig
| Question | Fixture | Unit tests | Real PLC |
| --- | --- | --- | --- |
| "Does FC03/FC06/FC16 work end-to-end?" | yes | - | yes |
| "Does DL205 octal addressing map correctly?" | yes | yes | yes |
| "Does float CDAB word-swap round-trip?" | yes | yes | yes |
| "Does the driver handle exception responses?" | no | yes | yes (required) |
| "Does packing 125 regs into one FC03 work?" | no | no | yes (required) |
| "Does FX5U behave like Q-series?" | no | no | yes (required) |
## Follow-up candidates
1. Add `MODBUS_SIM_ENDPOINT` override documentation to
`docs/v2/test-data-sources.md` so operators can point the suite at a lab rig.
2. ~~Extend `pymodbus` profiles to inject exception responses~~**shipped**
via the `exception_injection` compose profile + standalone
`exception_injector.py` server. Rules in
`Docker/profiles/exception_injection.json` map `(fc, address)` to an
exception code; `ExceptionInjectionTests` exercises every code in
`MapModbusExceptionToStatus` (0x01 / 0x02 / 0x03 / 0x04 / 0x05 / 0x06 /
0x0A / 0x0B) end-to-end on both read (FC03) and write (FC06) paths.
3. Add an FX5U profile once a lab rig is available; the scaffolding is in place.
## Key fixture / config files
- `tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/ModbusSimulatorFixture.cs`
- `tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/DL205/DL205Profile.cs`
- `tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Mitsubishi/MitsubishiProfile.cs`
- `tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/S7/S7_1500Profile.cs`
- `tests/ZB.MOM.WW.OtOpcUa.Driver.Modbus.IntegrationTests/Docker/`
Dockerfile + compose + per-family JSON profiles