Joseph Doherty 9f62310b49
v2-ci / build (pull_request) Successful in 3m24s
v2-ci / unit-tests (pull_request) Failing after 8m19s
fix(historian): map Boolean historization to Int2, not degenerate Int1 (#441)
The historian's Int1 analog-tag creation path is server-degenerate:
EnsureTags(Int1) stores an unusable stub (live-probed on the deployed
2023 R2 historian; root-caused + documented gateway-side in
HistorianGateway #11 / PR #16). HistorianTypeMapper mapped
DriverDataType.Boolean -> HistorianDataType.Int1, so Boolean historized
tags failed auto-provisioning.

Map Boolean -> Int2 instead (store 0/1). Int2 is a proven-creatable
analog type, and the value-write path already sends every value as a
double on WriteLiveValues regardless of tag type, so Boolean 0.0/1.0
round-trips cleanly. Both Float and Int2 are supported, so a
pre-existing Float Boolean tag retypes cleanly on its next deploy.

- HistorianTypeMapper: Boolean => Int2 (+ remarks)
- Unit pins: HistorianTypeMapperTests, GatewayTagProvisionerTests
  (Boolean_definition_carries_explicit_Int2_presence)
- Live gate: EnsureTags_boolean_sandbox_provisions_as_Int2 (was _Int1);
  retype probe reframed Float->Int2 (drops the dead Int1 leg)
- Docs: docs/Historian.md 'Boolean historization maps to Int2', CLAUDE.md,
  archreview STATUS.md (R2-06 live gate -> 6/6)

Resolves #441.
2026-07-14 11:57:27 -04:00

28 KiB
Raw Permalink Blame History

Historian — server-side OPC UA HistoryRead (Phase C)

Phase C wires server-side OPC UA HistoryRead for authored equipment tags flagged historized. The feature is driver-agnostic: any equipment tag (Galaxy, Modbus, OpcUaClient, or any other driver) can be marked historized; the server dispatches all history reads to the registered IHistorianDataSource — the HistorianGateway read client (GatewayHistorianDataSource, talking gRPC to the external ZB.MOM.WW.HistorianGateway via the ZB.MOM.WW.HistorianGateway.Client package). No EF migration is required; the historian flag rides in the existing schemaless TagConfig JSON blob alongside the Phase B alarm object. (The bespoke Wonderware TCP sidecar backend this replaced was retired — see drivers/Historian.Wonderware.md.)

Design reference: docs/plans/2026-06-14-galaxy-phase-c-historian-design.md.


Historized TagConfig schema

A tag is historized by setting the Historize this tag checkbox and optional Historian tagname (override) textbox in the Tag modal on the /uns equipment page Tags tab. These controls work for all drivers — typed editors (Modbus, S7, OpcUaClient, etc.) and the raw-JSON textarea (Galaxy) alike. The controls merge isHistorized / historianTagname into the existing TagConfig JSON blob via the TagHistorizeConfig helper, preserving all other keys byte-stable. Drivers that still use the raw-JSON editor (Galaxy) can also add the fields directly in the textarea.

Fields

Field Type Required Description
isHistorized bool yes Marks the tag historized. Materialises the OPC UA node with Historizing=true and the HistoryRead AccessLevel bit.
historianTagname string no Explicit historian tagname to query. When absent or empty, defaults to the tag's driver FullName (the TagConfig.FullName).

Examples

Default historian tagname (uses FullName = TestMachine_002.TestFloat):

{"FullName":"TestMachine_002.TestFloat","isHistorized":true}

Explicit historian tagname override:

{"FullName":"TestMachine_002.TestFloat","isHistorized":true,"historianTagname":"Plant.Line1.Flow"}

A tag that is both historized and a native alarm:

{"FullName":"TestMachine_002.HiAlarm","isHistorized":true,"alarm":{"alarmType":"OffNormalAlarm","severity":700}}

ServerHistorian configuration

The ServerHistorian section in appsettings.json controls the historian read path. Enabled defaults to false; when disabled, the server registers NullHistorianDataSource and all HistoryRead calls on historized nodes return GoodNoData (empty, not an error).

{
  "ServerHistorian": {
    "Enabled": false,
    "Endpoint": "",
    "ApiKey": "",
    "UseTls": true,
    "AllowUntrustedServerCertificate": false,
    "CaCertificatePath": null,
    "CallTimeout": "00:00:30",
    "MaxTieClusterOverfetch": 65536,
    "HistoryReadBatchParallelism": 4,
    "MaxConcurrentHistoryReadBatches": 16,
    "HistoryReadDeadline": "00:01:00"
  }
}
Key Type Default Description
Enabled bool false Enable the live GatewayHistorianDataSource. falseNullHistorianDataSource (empty reads).
Endpoint string "" Absolute gateway URI, e.g. https://host:5222. Scheme selects transport (https:// = TLS, http:// = h2c plaintext). Required when Enabled.
ApiKey string "" The gateway peppered-HMAC key (histgw_<id>_<secret>) sent as Authorization: Bearer. Required when Enabled. Supply via env ServerHistorian__ApiKey.
UseTls bool true Connect over TLS; must match the Endpoint scheme.
AllowUntrustedServerCertificate bool false Accept a self-signed / untrusted server certificate (dev / on-prem only).
CaCertificatePath string|null null PEM CA file pinning the gateway's TLS chain. Null/empty uses the OS trust store.
CallTimeout TimeSpan 00:00:30 Per-call deadline applied to each unary gateway read. A read for a tag the historian does not yet know about — e.g. a freshly-historized tag that has not been provisioned (see Tag auto-provisioning) — can run to this full deadline before the gateway errors, so an unprovisioned-tag HistoryRead can block for ~30 s. Lower this to fail faster, at the cost of truncating legitimately long reads.
MaxTieClusterOverfetch int 65536 Maximum samples the server will fetch in one shot to page through a tie cluster (multiple samples sharing one SourceTimestamp). A cluster larger than this ceiling fails BadHistoryOperationUnsupported. Raise to handle abnormally large tie clusters; the default covers all normal-data cases.
HistoryReadBatchParallelism int 4 Max historized nodes served concurrently within one HistoryRead batch (arch-review 03/S3). The SDK's HistoryRead* override surface is synchronous, so each arm bridges once at its boundary; this turns per-node serving from sequential (N × CallTimeout worst case) into ⌈N / P⌉ × CallTimeout. Also caps the gateway-load multiplication a single client can command. ≤ 1 serves sequentially.
MaxConcurrentHistoryReadBatches int 16 Process-wide limit on HistoryRead batches served concurrently (arch-review 03/S3). A flood of history clients degrades to BadTooManyOperations rather than exhausting the SDK request-thread pool. With HistoryReadBatchParallelism this caps total in-flight gateway reads at MaxConcurrentHistoryReadBatches × HistoryReadBatchParallelism (default 16 × 4 = 64). A batch that cannot get a slot within min(HistoryReadDeadline, 5 s) fails every handle BadTooManyOperations.
HistoryReadDeadline TimeSpan 00:01:00 Per-request wall-clock deadline for a HistoryRead batch (arch-review 03/S3). A node still in flight at the deadline surfaces BadTimeout, so one request can never hold an SDK request thread longer than this regardless of node count. Non-positive = unbounded (a Validate() warning).

Do not commit ApiKey to appsettings.json. Set it via the environment variable ServerHistorian__ApiKey, a secrets store, or a deployment-time overlay. The checked-in default is always empty.

Gateway-side prerequisites. The target gateway must run RuntimeDb:Enabled=true (continuous WriteLiveValues) + RuntimeDb:EventReadsEnabled=true (alarm-history ReadEvents), and the API key must carry the scopes historian:read, historian:write, historian:tags:write.

Migration from the Wonderware backend. Rename the old keys: Host/PortEndpoint (https://host:5222); SharedSecretApiKey (env ServerHistorian__ApiKey); ServerCertThumbprintCaCertificatePath (+ UseTls / AllowUntrustedServerCertificate).

The ServerHistorian section is independent of the AlarmHistorian section (the alarm write path) and the ContinuousHistorization section (driver-value capture). All three target the same gateway — but only ServerHistorian carries the connection (endpoint/key/TLS); the other two source it from there.

Continuous-historization value quality is server-stamped. The gateway's WriteLiveValues SQL path discards the quality the recorder sends (a server-managed column; 0.2.0 Contracts C-002), so persisted quality is stamped gateway-side regardless of what the ContinuousHistorizationRecorder provides (it hardcodes OPC-DA Good, 192). Capturing real per-node quality will not persist until the gateway honors the field — see GatewayHistorianValueWriter's remarks (archreview 06/C-7).


Tag auto-provisioning (EnsureTags)

When a deploy adds a historized tag, the server auto-ensures it exists in the historian via the gateway's EnsureTags before the first value or HistoryRead lands. AddressSpaceApplier.Apply() fires a non-blocking, fire-and-forget IHistorianProvisioning.EnsureTagsAsync for each added historized value tag (with the resolved historian name — the historianTagname override when set, else the driver FullName); the hook is wrapped so a faulted, slow, or throwing provisioner can never block or fail a deploy. Non-numeric (String/DateTime/Reference) types are skipped, not provisioned.

Wiring + gating. The concrete provisioner is the gateway-backed GatewayTagProvisioner, registered by the Host's AddHistorianProvisioning (GatewayHistorian.CreateProvisioner) and gated on the same ServerHistorian:Enabled flag as the read path — both target the same single gateway. When the section is disabled (or absent) the applier resolves the no-op NullHistorianProvisioning and provisioning does not run (so on a read-only-historian deployment, ensure tags exist by some other means). The Host requires the API key to carry the historian:tags:write scope for EnsureTags to succeed.

Observability. Every dispatch logs an Information tally — historian provisioning completed (dispatched=N, requested=…, ensured=…, skipped=…, failed=…). A line showing dispatched=N but requested=0 indicates the no-op provisioner ran (provisioning is not wired for this node), which is the signal to check that ServerHistorian:Enabled=true.

Why this matters for HistoryRead latency. Until a tag is provisioned, the historian does not know it, so a HistoryRead on it runs to the full CallTimeout (~30 s) before erroring. Auto-provisioning on deploy keeps freshly-historized tags from hitting that slow path. See the CallTimeout row above.

Boolean historization maps to Int2 (issue #441)

EnsureTags is contract-documented (HistorianGateway 0.2.0+) as an upsert"creates or updates historian tags according to the given definitions" — that maps per-tag onto AVEVA's HistorianClient.EnsureTagAsync(definition) -> bool. It is not idempotent (not routed through the idempotent retry pipeline) and not skip-if-exists.

HistorianTypeMapper maps DriverDataType.Boolean → HistorianDataType.Int2 and Boolean values historize as a small 0/1 integer. Int2 is used rather than the semantically-exact Int1 because the historian's Int1 analog-tag creation path is server-degenerateEnsureTags(Int1) stores an unusable stub, so a Boolean tag mapped to Int1 never becomes historizable. This is an evidence-based decision from a live probe against the deployed 2023 R2 historian; the root cause and gateway-side resolution are tracked in issue #441 and HistorianGateway #11 / PR #16 (which documents Int1 as an explicit, evidence-based exclusion). The value-write path is unaffected: the recorder sends every value as a double on WriteLiveValues regardless of tag type, so a Boolean 0.0/1.0 round-trips cleanly into the Int2 tag.

Observed live (2026-07-13, real 0.2.0 gateway → real AVEVA historian on wonder-sql-vd03, probed via grpcurl — archreview R2-06 T12):

  • EnsureTags is a real create-or-update upsert — re-EnsureTags of an existing tag at the same type returns Success=true.
  • An in-place retype between SUPPORTED types is ACCEPTEDFloat→Double on an existing tag returns Success=true.
  • A type sweep confirmed Int2/UInt2/Int4/UInt4/Float/Double all provision Success=true; only Int1 fails (Success=false, Error="ProtocolEvidenceMissingException" — the vendored client's "no capture evidence for this type" guard → gRPC Unimplemented), both for a fresh tag and as a retype target. Mapping Boolean to Int2 sidesteps that gap entirely.

Prerequisite for provisioning to land at all: the provisioner must stamp a positive StorageRateMs — a 0 made EnsureTags throw ArgumentOutOfRangeException and fail every provision (fixed in GatewayTagProvisioner, PR #439).

Migration note for pre-existing Boolean tags. A Boolean tag historian-side as Float (e.g. from the 0.1.0-era default) is asked, on its next deploy, to upsert to Int2. Both are supported analog types, so the retype is accepted. Provisioning is fire-and-forget and never blocks/fails a deploy; a per-tag rejection (if any) surfaces only as the tally's failed count, and values written to a still-Float tag remain readable (Float supersets the 0/1 range) pending reconcile. A bulk retype sweep is not done in code.


HistoryRead behavior

Read variants

The server supports all four OPC UA HistoryRead variants:

Variant Node type CLI --aggregate
Raw Historized variable (omit --aggregate)
Processed Historized variable Average, Minimum, Maximum, Total, Count
AtTime Historized variable n/a (client supplies exact timestamps)
Events Equipment folder (event notifier) n/a

Variable nodes (historized tags) serve Raw, Processed, and AtTime history. Historizing=true and AccessLevels.HistoryRead are set at materialization so any compliant OPC UA client can discover historized capability from the node's attributes.

Equipment-folder event-notifier nodes serve Event history. Every equipment folder that owns at least one alarm condition is already an event notifier; the server registers a sourceName (the equipment id) for each such folder and maps event history reads to the HistorianGateway using that source. (Alarm-history ReadEvents requires the gateway running RuntimeDb:EventReadsEnabled=true.) Event-field projection supports the standard BaseEventType select clauses — EventId, SourceName, Time, ReceiveTime, Message, and Severity; an unsupported select operand returns a null field (spec-conformant).

OpcUaClient driver — upstream passthrough for all four variants

The OpcUaClient driver's IHistoryProvider implementation forwards all four history-read variants (Raw, Processed, AtTime, and Events) to its upstream OPC UA server. For the Events variant it sends a fixed canonical BaseEventType EventFilter selecting the standard six fields (EventId, SourceName, Time, ReceiveTime, Message, Severity) and maps the upstream HistoryEvent onto HistoricalEvent — the same six-field projection the OtOpcUa node-manager itself projects when serving event history. This is a driver-level capability: the OpcUaClient driver acts as a passthrough to whatever historian the upstream server exposes, and is independent of the single server-side IHistorianDataSource backend (GatewayHistorianDataSource / NullHistorianDataSource) that the OtOpcUa node-manager dispatches HistoryRead to for tags on other drivers (Galaxy, Modbus, S7, etc.).

Graceful degradation

Situation HistoryRead status
Historized node, historian configured and reachable, results found Good
Historized node, historian configured, time range empty GoodNoData
Historized node, historian NOT configured (Enabled=false / Null source) GoodNoData (empty)
Non-historized node BadHistoryOperationUnsupported
Backend timeout or exception BadHistoryOperationUnsupported per node; other nodes in the same batch are unaffected

A historized node with no historian configured never returns an error status — it returns empty. This means a deployment can author and publish historized tags before the historian gateway is provisioned, without producing error spikes in connected clients.

Continuation-point paging (Raw)

HistoryRead-Raw is paged server-side. The historian backend is single-shot (it returns up to NumValuesPerNode samples with no continuation point of its own), so the server synthesises paging time-based:

  • A page that returns exactly NumValuesPerNode samples (with NumValuesPerNode > 0) MAY have more behind it, so the server stores a resume cursor and returns an opaque continuation point (16 bytes). The client hands it back to fetch the next page.
  • A short page (fewer than the cap) is the last page — no continuation point.
  • NumValuesPerNode == 0 ("all values, no limit") is never paged; the whole window returns in one shot.
  • The resume cursor is tie-safe: the next page resumes from the last returned sample's SourceTimestamp inclusive and drops the boundary samples already emitted, so samples sharing the boundary timestamp are neither duplicated nor skipped.

Oversized tie clusters — within-timestamp paging. When more samples share one SourceTimestamp than the current page cap, the server detects that the cursor has stalled on a tie cluster (the last returned timestamp equals the resume timestamp). It then over-fetches the entire cluster at that single timestamp up to a bounded ceiling controlled by ServerHistorian:MaxTieClusterOverfetch (default 65 536), then serves the cluster NumValuesPerNode samples at a time across successive pages, advancing the cursor one tick past the timestamp once the cluster is fully drained.

Short pages within a cluster still carry a continuation point. A within-cluster page that returns fewer than NumValuesPerNode samples (because the cluster happened to be smaller than the cap, or is the final partial batch) is not the last page if the cluster itself has not been fully emitted — the server retains the continuation point so the client can drain the remainder. Only when the cluster is exhausted and the cursor has advanced past the timestamp does the short-page rule apply.

Cluster larger than MaxTieClusterOverfetch. If the over-fetch itself reaches the ceiling without spanning the full cluster, the node fails loudly with BadHistoryOperationUnsupported and the tag + timestamp + ceiling are logged. Remedies: raise MaxTieClusterOverfetch (or NumValuesPerNode) to cover the full cluster, or investigate the data anomaly (raw samples normally carry strictly increasing distinct timestamps).

For a single tag's raw history a tie cluster larger than the default 65 536 is a severe data anomaly. The ceiling exists to bound server-side memory on pathological data, not to cap normal operation.

Continuation points are bound to the OPC UA session (the SDK's ServerConfiguration.MaxHistoryContinuationPoints cap, default 100, with oldest-eviction; points are disposed when the session closes). Resuming an unknown / evicted / released point returns BadContinuationPointInvalid. releaseContinuationPoints drops the stored cursors without reading data.

Total aggregate

The OPC UA Total aggregate is supported over the HistorianGateway backend. The gateway exposes a native Integral retrieval mode, so Total maps straight to it (HistoryAggregateType.Total → RetrievalMode.Integral) — no client-side scaling. (This replaces the retired Wonderware path, which had no Total column and derived it client-side as time-weighted Average × interval-seconds.) Count is likewise a native gateway mode. Bucket status codes and timestamps are preserved unchanged; empty / null buckets surface as BadNoData.

Known limitations

  • Processed and AtTime are single-shot (no continuation points). Unlike Raw, neither ReadProcessedDetails nor ReadAtTimeDetails carries a client count cap (NumValuesPerNode): the Processed bucket count is deterministic (window / interval) and AtTime returns exactly one sample per requested timestamp, so the single-shot backend returns the complete result in one read and there is no "full page ⇒ maybe more" signal to page on. Returning the full result with no continuation point is spec-conformant.
  • No modified-value history (HistoryReadModified). Requests for modified values return BadHistoryOperationUnsupported. This is infra-gated, not a server-code gap: the HistorianGateway backend (GatewayHistorianDataSource) exposes only a current-value read path — there is no modified/edited-history surface to source the data from. The server-side override is in place (it cleanly rejects modified reads per node) and IsReadModified is honoured; serving real modified-value history is unblocked only once the gateway grows a modified-read RPC. Until then, rejecting is the correct, spec-conformant behaviour.

Redundancy and authorization

History reads are served from any node — there is no Primary gate. Authorization is the standard OPC UA HistoryRead permission enforced by the SDK through the AccessLevels.HistoryRead bit set at materialization. A session without sufficient permissions receives BadUserAccessDenied from the SDK before the dispatch reaches the historian.


Authoring workflow

  1. Open the equipment's Tags tab on /uns/equipment/{id}.
  2. Create or edit the tag.
    • For typed-editor drivers (Modbus, S7, OpcUaClient, etc.): check the Historize this tag checkbox and, if needed, fill in the Historian tagname (override) textbox.
    • For raw-JSON editors (Galaxy): you can check the same first-class checkboxes (they appear below the JSON textarea), or add "isHistorized":true (and optionally "historianTagname":"...") directly in the textarea.
  3. Save and publish. The server rebuilds its address space; the node materialises with Historizing=true and the HistoryRead AccessLevel bit.
  4. Confirm with Client.CLI read that the node's Status is Good and that the value is updating. Then issue a historyread to verify the historian connection returns data.

Native-alarm historian opt-out (alarm.historizeToAveva)

A tag carrying a native "alarm" object has a separate historian opt-out for its alarm transitions (distinct from tag-value historization). On the Tag modal, check or uncheck Historize to AVEVA in the alarm section. This maps to alarm.historizeToAveva (bool?) in the TagConfig JSON:

  • Absent or true (default) — the alarm's transitions are written to AVEVA Historian via HistorianAdapterActor.
  • false — the durable AVEVA write is suppressed for this alarm's transitions. The live /alerts feed and OPC UA condition events are unaffected.

The gate is applied in HistorianAdapterActor using is not false semantics, matching the scripted-alarm HistorizeToAveva posture. See ScriptedAlarms.md §Native driver alarms and AlarmTracking.md §Historian write-back for the full alarm-historian routing.


Client.CLI historyread examples

The historyread command reads historical data from any node. Supply start and end times in ISO 8601 UTC form. See docs/Client.CLI.md for the full flag reference.

# Raw history for a historized Galaxy tag (last 24 hours by default)
otopcua-cli historyread \
  -u opc.tcp://localhost:4840/OtOpcUa \
  -n "ns=2;s=EQ-55297329838d/GalaxyTestTag" \
  --start "2026-06-13T00:00:00Z" --end "2026-06-14T00:00:00Z"

# Limit to 100 values
otopcua-cli historyread \
  -u opc.tcp://localhost:4840/OtOpcUa \
  -n "ns=2;s=EQ-55297329838d/GalaxyTestTag" \
  --start "2026-06-13T00:00:00Z" --end "2026-06-14T00:00:00Z" \
  --max 100

# 1-hour average aggregate
otopcua-cli historyread \
  -u opc.tcp://localhost:4840/OtOpcUa \
  -n "ns=2;s=EQ-55297329838d/GalaxyTestTag" \
  --start "2026-06-13T00:00:00Z" --end "2026-06-14T00:00:00Z" \
  --aggregate Average --interval 3600000

# Authenticated read (ReadOnly role or higher required)
otopcua-cli historyread \
  -u opc.tcp://localhost:4840/OtOpcUa \
  -n "ns=2;s=EQ-55297329838d/GalaxyTestTag" \
  --start "2026-06-13T00:00:00Z" --end "2026-06-14T00:00:00Z" \
  -U reader -P password

Supported --aggregate values: Average, Minimum, Maximum, Count, Start, End, StandardDeviation (aliases: avg, min, max, stddev/stdev, first, last). --interval is the processing interval in milliseconds (default 3600000 = 1 hour). The Total aggregate is served by the server's OPC UA HistoryRead endpoint for any conformant client (derived as time-weighted Average × interval-seconds — see "Total aggregate derivation" above), but is not exposed by this bundled CLI.


Live /run gate

The live read gate requires a reachable ZB.MOM.WW.HistorianGateway (VPN to wonder-sql-vd03) with the AVEVA Historian behind it healthy. Set ServerHistorian:Enabled=true with the correct Endpoint (https://host:5222) and supply ServerHistorian__ApiKey via the environment, then deploy and publish at least one historized Galaxy tag. The gate is operator-driven — it is not part of the local docker-dev rig. The gateway-backed driver also ships an env-gated live suite (Category=LiveIntegration); see the HISTGW_GATEWAY_ENDPOINT / HISTGW_GATEWAY_APIKEY / HISTGW_TEST_TAG / HISTGW_WRITE_SANDBOX_TAG / HISTGW_BOOL_SANDBOX_TAG / HISTGW_ALARM_SOURCE env vars (it skips cleanly when they are absent). HISTGW_BOOL_SANDBOX_TAG (e.g. HistGW.LiveTest.BoolSandbox, a dedicated writable Boolean tag — never the shared Float write sandbox) drives the Boolean historization leg (EnsureTags_boolean_sandbox_provisions_as_Int2) and the retype probe (EnsureTags_type_change_outcome_is_observable) that back the Boolean historization maps to Int2 decision. Running the full suite against the gateway (all six tests, none skipped) also discharges 06/U-2's "full documented run" for the historian suite.

See AlarmHistorian.md for the alarm write path and ServiceHosting.md for the (external) HistorianGateway deployment.



Cross-driver TagConfig key reference

The TagConfig JSON blob is the single extension surface for per-tag server-side behaviours across all drivers. Keys from multiple phases coexist in the same blob; unknown keys are preserved byte-stable on round-trip by all typed editors.

Historian + alarm keys (Phase B / Phase C)

Key Type Phase Description
isHistorized bool C Marks the tag historized (HistoryRead + Historizing=true).
historianTagname string C Explicit historian tagname override (defaults to FullName).
alarm object B Native alarm definition (alarmType, severity, historizeToAveva, …).

Array keys (Phase 4c)

Key Type Phase Description
isArray bool 4c When true and arrayLength >= 1, materialises the node as a 1-D array (ValueRank=OneDimension). Absent or false → scalar.
arrayLength uint (≥1) 4c Element count; sets ArrayDimensions. Required when isArray: true.

Cross-driver array coverage matrix

Driver Read mechanism Live-verify status
Modbus Contiguous FC03/FC04 block; String/BitInRegister modes supported Mac-verifiable (sim 10.100.0.35:5020)
S7 ReadBytesAsync block + per-element decode loop Unit-proven (fixture down)
AB CIP libplctag native array read (atomic + UDT member arrays) Unit-proven (fixture down)
AB Legacy PCCC multi-element file read via libplctag (cap 256 elements) Unit-proven (fixture down)
TwinCAT ADS native array symbol read Unit-proven (fixture down)

Array writes, multi-dimensional arrays (ValueRank>1), and per-element historization are out of scope — see Uns.md §Array tags.


Closed backlog §2 items (Phase 4 / Phase 4b)

The following items from the backlog §2 (archived at docs/plans/2026-06-18-stillpending-backlog-audit.md) were closed by earlier phases and are recorded here so future audits don't re-flag them.

Item Closed by Commit
Modbus Int64 / UInt64 OPC UA node DataType correction Phase 4 bd8fee61
HistoryAggregateType.TotalTotal aggregate Phase 4 (derived client-side as time-weighted Average × interval-seconds) 5e27b5f7
Historian poison alarm-event indefinite retry — dead-letter cap (task #437) Phase 4 fcb38014

See also