Task #249 — Driver test-client CLIs: shared lib + Modbus CLI first #203

Merged
dohertj2 merged 1 commits from task-249-driver-cli-common-modbus into v2 2026-04-21 08:17:22 -04:00

1 Commits

Author SHA1 Message Date
Joseph Doherty
5dac2e9375 Task #249 — Driver test-client CLIs: shared lib + Modbus CLI first
Mirrors the v1 otopcua-cli value prop (ad-hoc shell-level PLC validation) for
the Modbus-TCP driver, and lays down the shared scaffolding that AB CIP, AB
Legacy, S7, and TwinCAT CLIs will build on.

New projects:
  - src/ZB.MOM.WW.OtOpcUa.Driver.Cli.Common/ — DriverCommandBase (verbose
    flag + Serilog config) + SnapshotFormatter (single-tag + table +
    write-result renders with invariant-culture value formatting + OPC UA
    status-code shortnames + UTC-normalised timestamps).
  - src/ZB.MOM.WW.OtOpcUa.Driver.Modbus.Cli/ — otopcua-modbus-cli executable.
    Commands: probe, read, write, subscribe. ModbusCommandBase carries the
    host/port/unit-id flags + builds ModbusDriverOptions with Probe.Enabled
    =false (CLI runs are one-shot; driver-internal keep-alive would race).

Commands + coverage:
  - probe              single FC03 + GetHealth() + pretty-print
  - read               region × address × type synth into one driver tag
  - write              same shape + --value parsed per --type
  - subscribe          polled-subscription stream until Ctrl+C

Tests (38 total):
  - 16 SnapshotFormatterTests covering: status-code shortnames, unknown
    codes fall back to hex, null value + timestamp placeholders, bool
    lowercase, float invariant culture, string quoting, write-result shape,
    aligned table columns, mismatched-length rejection, UTC normalisation.
  - 22 Modbus CLI tests:
      · ReadCommandTests.SynthesiseTagName (5 theory cases)
      · WriteCommandParseValueTests (17 cases: bool aliases, unknown rejected,
        Int16 bounds, UInt16/Bcd16 type, Float32/64 invariant culture,
        String passthrough, BitInRegister, Int32 MinValue, non-numeric reject)

Wiring:
  - ZB.MOM.WW.OtOpcUa.slnx grew 4 entries (2 src + 2 tests).
  - docs/Driver.Modbus.Cli.md — operator-facing runbook with examples per
    command + output format + typical workflows.

Regression: full-solution build clean; shared-lib tests 16/0, Modbus CLI tests
22/0.

Next up: repeat the pattern for AB CIP (shares ~40% more with Modbus via
libplctag), then AB Legacy, S7, TwinCAT. The shared base stays as-is unless
one of those exposes a gap the Modbus-first pass missed.