OpcUaClient integration fixture � opc-plc in Docker (#215) #161
Reference in New Issue
Block a user
Delete Branch "opcuaclient-opc-plc-fixture"
Deleting a branch is permanent. Although the deleted branch may continue to exist for a short time before it actually gets removed, it CANNOT be undone in most cases. Continue?
Closes #215. Real Secure Channel + Session + MonitoredItem exchange against mcr.microsoft.com/iotedge/opc-plc:2.14.10 (pinned). Three smoke tests (read, batch typed read, subscribe) verified end-to-end against a live container. Docker IS the launcher (no wrapper script), same skip-when-absent pattern as Modbus/S7 fixtures. Follow-up flagged: open62541/open62541 as second image for fully-independent-stack interop.
docker pssurfaces ready state. Fixture OpcPlcFixture follows the same shape as Snap7ServerFixture + ModbusSimulatorFixture: collection-scoped, parses OPCUA_SIM_ENDPOINT (default opc.tcp://localhost:50000) into host + port, 2-second TCP probe at init,SkipReasonrecords the failure for Assert.Skip. Forced IPv4 on the probe socket for the same reason those two fixtures do — .NET's dual-stack "localhost" resolves IPv6 ::1 first + hangs the full connect timeout when the target binds 0.0.0.0 (IPv4). OpcPlcProfile holds well-known node identifiers opc-plc exposes (ns=3;s=StepUp,FastUInt1,RandomSignedInt32,AlternatingBoolean) + buildsOpcUaClientDriverOptionswith SecurityPolicy.None + AutoAcceptCertificates=true since opc-plc regenerates its server cert on every container spin-up + there's no meaningful chain to validate against in CI. Three smoke tests covering what the unit suite couldn't reach: (1) Client_connects_and_reads_StepUp_node_through_real_OPC_UA_stack — full Secure Channel + Session + Read onns=3;s=StepUp(counter that ticks every 1 s); (2) Client_reads_batch_of_varied_types_from_live_simulator — batch Read of UInt32 / Int32 / Boolean to prove typed Variant decoding, with an explicit ShouldBeOfType<bool> assertion on AlternatingBoolean to catch the common "variant gets stringified" regression; (3) Client_subscribe_receives_StepUp_data_changes_from_live_server — real MonitoredItem subscription on FastUInt1 (100 ms cadence) with a SemaphoreSlim gate + 3 s deadline on the first OnDataChange fire, tolerating container warm-up. Driver ran end-to-end against a live 2.14.10 container: all 3 pass; unit suite 78/78 unchanged. Container lifecycle verified (compose up → tests → compose down) clean, no leaked state. Docker/README.md documents install (Docker Desktop already on the dev box per Phase 1 decision #134), run (compose up / compose up -d / compose down), endpoint override (OPCUA_SIM_ENDPOINT), what opc-plc advertises with the current command flags, what's tunable via compose-file tweaks (--daa for username auth tests; --fn/--fr/--ft for subscription-stress nodes), known limitation that opc-plc shares the OPCFoundation stack with our driver. OpcUaClient-Test-Fixture.md updated — TL;DR flipped from "there is no integration fixture" to the new reality; "What it actually covers" gains an Integration section listing the three smoke tests. Follow-up the doc flags: add open62541/open62541 as a second image for fully-independent-stack interop coverage; once #219 (server-side IAlarmSource/IHistoryProvider integration tests) lands, re-run the client-side suite against opc-plc's --alm nodes to close the alarm gap from the client side too. c985c50a96