Review r1 N1 (Important): the I1 fix made IsDeviceRefusal default-open and
mapped libplctag's ERR_REMOTE_ERR to an answer. libplctag folds EVERY non-zero
PCCC STS and CIP status into that code, including a routing hop's "unconnected
send timed out" / "connection lost" / "remote node missing", and native
BadReply covers truncated / mismatched / unmapped replies - so a powered-off
PLC behind a bridge read as reachable: Healthy, LastSuccessfulRead advancing,
the comms-loss watchdog unable to fire.
Three classes now, each pinned both ways:
- no reply (Timeout/BadConnection/Abort/Pending/unknown): comms fault;
- answered - an ALLOW-LIST again (NotFound/NotAllowed/OutOfBounds/TooLarge/
TooSmall/TypeMismatch/DeviceStateConflict): proves reachability;
- OPAQUE (BadReply/Partial; ERR_REMOTE_ERR/ERR_BAD_STATUS now translate to the
existing BadReply, OPC UA BadCommunicationError as before r0): per-tag Bad,
handle kept, coalescing fallback, never fail-fast, never an answer. Option
(a): a device whose pass/call produced only opaque outcomes is Degraded with
LastSuccessfulRead not advanced, so the watchdog reaches a dead routed PLC.
The probe and index reads classify the same way.
Minors:
- N2: a mismatched array (type vs data file) READS BadTypeMismatch instead of
decoding the file at the wrong width as Good.
- N3: a swept indirect resolution is never reconnected under a forgotten gate;
that one call answers neutrally.
- N4: an index read answered Unsupported is neutral, not a transport fault.
- N5: ArrayFileMismatch checks indirect addresses (the file letter is static).
- Test nit: the evicted-while-waiting test signals gate arrival via a seam
instead of sleeping.
Live: 51/51 on ab_server (slc500/micrologix/plc5 x both transports), incl. an
opaque-only libplctag device staying Degraded with LastSuccessfulRead frozen.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review r0 I3. The array encoder used the AUTHORED dataType's width while both
runtimes size their buffer from the FILE: an Int array on F8 wrote four shorts
into a 16-byte float buffer and sent it all (garbage neighbours, answered
Good); Long/Float on N overran it.
- The write path resolves the element width from the data file the address
names (N/B/A/I/O/S 16-bit word, L 32-bit, F float) and encodes at THAT width.
- An authored type that does not match its file is refused BadTypeMismatch
before any runtime exists (warned once, no health write).
- The same rule (AbLegacyTagDefinitionFactory.ArrayFileMismatch) backs an
Inspect deploy warning and the AdminUI model's Validate error; FromTagConfig
still accepts the tag so persisted configs keep loading.
- M6: the skipped F1 parity test gains the shapes the write path refuses
(/bit, .sub, indirect, type/file mismatch, PLC-5 native).
Tests: one case per file type, a mismatch per pairing with nothing created,
and a positive control.
Refs #738
Claude-Session: https://claude.ai/code/session_01Ub9hGmYLQvn9XETzw7CMsT
Review 07 U10 (user decision: implement array encode now). Both runtimes
encoded a scalar for an array tag: an int[] threw InvalidCastException into
BadTypeMismatch + Degraded, a scalar wrote element 0 natively, and libplctag's
SetInt32(0, ..) re-sent the stale last-read buffer for elements 1..n-1.
IAbLegacyTagRuntime gains EncodeArray; both runtimes write every element at
the element width (Int/AnalogInt 2 bytes, Long/Float 4). The driver converts
the written value before any runtime exists: each element is converted, not
exact-matched (ScadaBridge writes int[] to Int16 nodes), a length other than
the tag's element count is BadOutOfRange, an overflowing element is
BadOutOfRange, a non-array or non-numeric payload is BadTypeMismatch, and a Bit
array (bit-packed words; an encode would clobber neighbour bits) is
BadNotSupported. None of these touch health or the wire. Adds an env-gated
ab_server round trip for an N-file array write.
Refs #738