Joseph Doherty 52708bff52 fix(address-space): numeric array writes convert (checked) to the node element type; array-to-scalar refusal only for Modbus/S7 (#610 review R6)
MAJOR-1: R4's exact element-type match refused ScadaBridge's CLR-list
writes (its element types are only Boolean/Int32/Float/Double/String/
DateTime) to every Int16/UInt16/Byte/UInt32/Int64/UInt64 array node and a
Double list to a Float array. EvaluateEquipmentWriteStructure now converts
a numeric array of another numeric element type element-wise, CHECKED, into
the node's element type and hands the converted array back through
OnEquipmentTagWrite's ref value, so the node stores and the driver receives
the node's own type. Any out-of-range, fractional-to-integer, NaN/Inf-to-
integer or Float-overflowing element refuses the whole write BadTypeMismatch
(nothing dispatched) - so the UInt32 -> Int32 bit reinterpretation stays
closed. Non-numeric mismatches stay refused. The wrong 'no client relies on
a looser rule' comment is corrected.

MINOR-1: the array-value-to-scalar-node refusal broke writes back to
browse-committed array tags (committed scalar, isArray never set) on
pass-through drivers. It now applies only when the owning driver's scalar
encoder cannot take an array (DriverArrayWriteSupport.
RefusesArrayValueOnScalarTag: Modbus, S7), carried RawTagPlan.
ScalarRefusesArrayValue / UnsReferenceVariable.BackingScalarRefusesArrayValue
-> EnsureVariable(refuseArrayOnScalar) -> a per-node set in the node
manager. OpcUaClient/Galaxy/others keep pre-#610 dispatch. Not on the
classifier whitelist (driver-type edit rebuilds); a mirror whose flag
changes is recreated, not updated in place.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 08:31:46 -04:00
Joseph Doherty 18f8eb5d2f feat(address-space): server-side array writes gated per driver capability (#610)
Array nodes were forced read-only for every driver. A new single authority,
Core.Abstractions DriverArrayWriteSupport, says which (driver, element type)
pairs encode a whole-array write: Modbus (Coils / numeric HoldingRegisters),
S7 (Byte/Int16/UInt16/Int32/UInt32/Float32), OpcUaClient (pass-through) and
Galaxy (Boolean/Int32/Int64/Float/Double/String/DateTime). Everything else
stays read-only, so the server never advertises a write the driver refuses.

- Composer derives RawTagPlan.ArrayWritable + UnsReferenceVariable
  .BackingArrayWritable at compose time (both seams, byte-parity); the
  applier's one writability rule is Writable && (!IsArray || ArrayWritable)
  for materialise and surgical paths, raw and UNS alike.
- ArrayWritable is on the classifier's surgical raw-tag whitelist and
  mirrored on the UNS record (UnsReferenceBackingParityTests updated).
- Node manager refuses a wrong-length / non-array value on an array node
  (BadTypeMismatch) and any IndexRange write (BadWriteNotSupported) inline,
  before dispatch; WriteOperate/ACL gates and the revert are unchanged.
- Per-driver parity tests pin the table against the real Modbus write path,
  S7 EncodeArrayBlock and Galaxy MxValueEncoder (UInt32/UInt64 excluded:
  array covariance reinterprets their bits).
- Over-the-wire proof in OpcUaServer.IntegrationTests (ArrayWriteWireTests).
- ValueRank > 1 documented as out of scope by decision (docs/Uns.md).

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:39:05 -04:00
Joseph Doherty 0bd3ec00e4 fix(address-space): announce surgically-added raw nodes; equipment-with-references removal stays surgical (#599)
- AnnounceAddedNodes raises NodeAdded in the Raw realm for the existing parents of
  added raw containers/tags (ComputeRawAddAnnouncements); Uns side unchanged.
- ApplyPureRemove removes UNS reference variables BEFORE the equipment subtree, so a
  reference the subtree's id-prefix scope reaches no longer ratchets to a full rebuild
  (03/P5). A NotSubsumed filter was not used: in production a reference NodeId is
  Area/Line/Equipment/Name, outside the subtree scope, so filtering would leak it.
  The matching RemoveEquipmentSubtree severing (03/S20) is in the node-manager commit.
- UnsReferenceBackingParityTests: reflection guard discovering the classifier's surgical
  raw-tag whitelist and requiring a same-typed mirror field (03/U11).

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 07:12:29 -04:00
Joseph Doherty d787502d54 fix(opcuaserver): degraded applies re-diff instead of losing nodes; in-place UNS mirror updates; sever inverse edges
C1 — a non-rebuild apply reporting failedNodes > 0 no longer advances _lastApplied.
Pre-delta-materialisation the full passes re-ensured every node on every apply, which
silently repaired any prior swallowed sink fault. The delta path removed that accidental
self-healing: a failed node sat inside _lastApplied, never appeared in a diff set again,
and EnsureVariable early-returns on the ones that landed — so it was lost until an
unrelated change forced a rebuild. The advance also moved to AFTER the materialise
passes, so a throwing pass leaves _lastApplied at the previous composition too. A
rebuild still advances even with failures (the ratchet is its resync path).

I2 — a UnsReferenceDelta whose identity is unchanged (same NodeId, EquipmentId and
BackingRawPath) is now applied in place via UpdateTagAttributes(Uns) instead of
remove+recreate, so the mirror's MonitoredItems survive an operator historizing or
reshaping the raw tag behind them. Remove+recreate stays for identity-changing deltas
(re-point, effective-name edit).

I3 — RemoveVariableNode severs the inverse half of every outgoing Organizes edge, the
variable-node counterpart of UnwireAlarmNotifiers. Rebuilds used to sweep these up;
surgical applies made rebuilds rare, so they accumulated on the raw node for the life of
the process.

I5 — added UNS reference variables are announced (their equipment folder is the parent,
already the Uns realm). Raw adds still are not; the gap comment now says so honestly
rather than calling it neutral and pre-existing.

I4 + M1 — corrected two comments that no longer described the code: the "re-point →
rebuild" claim in ApplyPureRemove, and the "N lock acquisitions" rationale for the delta
passes (Ensure* early-return on a dictionary probe before the lock).
2026-08-15 17:53:26 -04:00
Joseph Doherty 875ec9fe47 fix(opcuaserver): UNS reference nodes repair on backing-tag historian/shape edits
Adversarial review of 9f68f272 (classifier: non-alarm raw-tag deltas became
surgical) found stale UNS inheritance after a surgical raw edit. Editing a raw
tag's IsHistorized / HistorianTagname / IsArray / ArrayLength left every
referencing UNS node STALE: none of those fields were on UnsReferenceVariable,
so no coincident UnsReferenceDelta fired; the applier updated the raw node in
place; and EnsureVariable early-returns on an existing node. Consequences:
HistoryRead through the UNS NodeId served a different series than through the
raw NodeId (breaking the documented dual-registration invariant), a
de-historized tag kept serving history via UNS, and a scalar->array flip left
the UNS mirror scalar AND writable (bypassing the array read-only write gate).

UnsReferenceVariable now carries Backing{IsHistorized,HistorianTagname,IsArray,
ArrayLength}, copied from the backing tag's TagConfigIntent at compose time, so
record equality makes the reference Changed in the SAME plan. Both deltas are
non-rebuild kinds, so the existing machinery repairs the mirror surgically:
remove-previous in Apply, recreate in MaterialiseUnsReferences. That pass now
reads the four values from the RECORD (the single truth the planner diffed)
instead of a rawByPath back-lookup, preserving historian resolution exactly
(blank override => BackingRawPath, which is the backing tag's NodeId).

The artifact-decode seam needs no change: DeploymentArtifact.BuildRawAndUnsSubtrees
drives AddressSpaceComposer.Compose verbatim, which is what guarantees byte-parity.
The classifier needs no change either (a UnsReferenceDelta never forces Rebuild);
its comment now records why.

Also from the same review: a three-place-contract comment on RawTagPlan's
hand-written Equals naming its two downstream consumers, plus classifier pins for
the .Any(!eligible) quantifier, an ArrayLength-only delta, and an
alarm-content-only delta.
2026-08-15 17:11:03 -04:00
Joseph Doherty 9c37330a4c feat(opcuaserver): applier applies raw-tag + UNS-reference deltas surgically
Task 4 (9f68f272) taught AddressSpaceChangeClassifier that a non-alarm
RawTagDelta and any UnsReferenceDelta are surgical-eligible, so such plans
started classifying AttributeOnly/PureAdd instead of Rebuild. The applier's
surgical branch did not know about either delta set, so those deploys fell
through as SILENT NO-OPS (or, on a non-surgical sink, applied nothing at all
where a rebuild was the safe answer). This closes that gap:

  - Raw-tag loop: an eligible ChangedRawTags delta is applied IN PLACE via
    ISurgicalAddressSpaceSink.UpdateTagAttributes in the RAW realm, computing
    writable (`Writable && !IsArray`) and the historian tagname (blank override
    ⇒ the RawPath) exactly as MaterialiseRawSubtree does. A delta whose ONLY
    difference is ReferencingEquipmentPaths is node-inert for a value tag and
    is SKIPPED entirely — that is the shape a single UnsTagReference add/drop
    produces, and it used to rebuild the world.
  - UNS-reference loop: a ChangedUnsReferenceVariables delta removes the
    PREVIOUS node in place (terminal Bad, then RemoveVariableNode, Uns realm).
    Remove+recreate rather than an in-place update because a re-point must move
    the Organizes edge (the sink has no RemoveReference) and a display-name
    edit changes the NodeId itself; the cost is that one node's monitored
    items, versus every subscription server-wide today.
  - The branch trigger now fires for both sets, so a non-surgical sink falls
    back to a full rebuild instead of applying nothing.

Every new operation is inside the existing one-way rebuild ratchet: any false
or throw ⇒ SafeRebuild(). The eligibility filter is defense-in-depth — when
kind != Rebuild the classifier already guarantees every delta is eligible.

The recreate of a changed UNS reference is NOT done here. Until Task 6 the
publish actor still materialises the FULL composition after Apply returns, so
the existing MaterialiseUnsReferences pass recreates it and the system is
correct end to end after this commit; the remove-then-recreate ordering holds
because Apply returns before the materialise passes run. Task 6 narrows those
passes to the plan's delta and keeps the same ordering.

Tests: 7 new applier tests (in-place raw update incl. array/override parity,
reference-only skip, UNS-ref remove, both ratchet fallbacks, non-surgical-sink
rebuild). RecordingSink now captures the realm on surgical / remove / value-write
calls, so the existing UNS-realm assertions are explicit too.
2026-08-15 13:25:33 -04:00
Joseph Doherty 2d20aeb779 fix(opcua,drivers): carry driver status sub-codes to clients (#519) + health-write ordering (#517)
#519 — a driver's OPC UA status code now reaches a client with its sub-code intact.
DriverInstanceActor projected the driver's uint onto a 3-state Good/Uncertain/Bad enum
and OtOpcUaNodeManager re-expanded Bad to a bare 0x80000000, so BadNoCommunication,
BadTypeMismatch and BadNotSupported were indistinguishable on the wire and every
driver's status constants (incl. the 16 #497 had just corrected) were diagnostic in
logs only. Resolved by option (b): the raw uint rides AttributeValuePublished ->
AttributeValueUpdate -> IOpcUaAddressSpaceSink.WriteValue, OpcUaQuality is deleted, and
severity classification is a helper (OpcUaStatus.IsGood/IsUncertain/IsBad).

The surface was wider than the issue costed (41 files, not "the sink and 3
implementations"): OpcUaQuality had non-driver producers with no uint to carry.
Each got its natural code — BadInternalError for a failed virtual-tag script,
BadNoCommunication for driver comms loss — and ScriptedAlarmHostActor's pair of
mutually-inverse uint<->enum mappers is deleted, having round-tripped a code the
engine already held. AddressSpaceApplier's removal writes deliberately keep the
generic Bad: not losing a code the driver had is this issue; inventing one for the
deploy path is a separate call.

Behaviour change: WriteAlarmQuality fires its Part 9 event on a status-code change
rather than a severity-bucket change. While the annotation was 3-state those were the
same predicate; now a move between two Bad reasons changes what a subscriber reads.

New SDK-free named constants live on Commons.OpcUa.OpcUaStatus, and
StatusCodeParityTests is widened to cover them — that guard is reflection-driven, so
it can only see a named constant, never an inline literal.

#517 — the symptom is real but the issue named the wrong path and its fix was unsafe.
ShutdownAsync cannot race: DriverInstanceActor calls it from PostStop, after the
mailbox drains. (Core/Hosting/DriverHost, the one class with a concurrent GetHealth,
has no production call site.) InitializeAsync can: it runs on a fire-and-forget
Task.Run, and MTConnectDriver writes Healthy then starts loops that can throw into a
catch which disposes the client before writing Faulted.

Moving the write earlier, as suggested, inverts the terminal state — teardown drains
in-flight loops that write health as they unwind, so a late loop could leave Healthy at
rest with every connection closed. The fix is a bracket (conservative before, terminal
after), applied to MTConnect's init-failure path only; shutdown keeps its single
trailing write, and the rule plus the reachability table are documented on
IDriver.ShutdownAsync.

CalculationDriver.GetHealth returned a hard-coded Healthy that consulted nothing —
Healthy before initialize, after shutdown and after dispose. Now derived from _running.
Its test, named Health_is_always_Connected, asserted the defect and is replaced.

Every new guard was falsified by breaking the production code and watching it go red.
The two sub-code tests each assert two different Bad codes, since a single-code
assertion could pass against a hard-coded constant under the old projection.

Pre-existing failures, verified unchanged on a stashed tree and not chased: 4 in
Driver.AbLegacy.IntegrationTests (slc500/micrologix/plc5 fixtures not up) and 3 in
Host.IntegrationTests.

Closes #517
Closes #519

Claude-Session: https://claude.ai/code/session_015p7wGqy3YpZNCpDzTpGMKo
2026-07-31 05:25:27 -04:00
Joseph Doherty adce27e7fa refactor(drivers): delete the dead discovered-node injection path (§8.2, #507)
#507 was filed as "injection inert in v3, re-migrate onto the raw subtree".
Reading it, the retained code is not revivable: it resolves equipment from
EquipmentNode.DriverInstanceId UNION EquipmentTags, and BOTH are structurally
empty in v3 (AddressSpaceComposer always constructs EquipmentNode with a null
DriverInstanceId; DeploymentArtifact hard-codes an empty EquipmentTags set).
Removing the guard would have changed a log line and injected nothing. So it
is deleted rather than fixed, and #507 closes as superseded by /raw
browse-commit.

Removed: HandleDiscoveredNodes, PartitionDiscoveredByDeviceHost,
ShouldWarnPartition, PlansRoutingEqual, ApplyDiscoveredPlansForDriver,
_discoveredByDriver, the redeploy re-inject tail, DiscoveredNodeMapper,
DiscoveredInjection, AddressSpaceApplier.MaterialiseDiscoveredNodes,
OpcUaPublishActor.MaterialiseDiscoveredNodes, and the Runtime-local copies of
CapturingAddressSpaceBuilder/DiscoveredNode.

The connect-time discovery loop goes too (StartDiscovery, RediscoverTick,
HandleRediscoverAsync, DiscoveredNodesReady, TriggerRediscovery). With
injection gone it had no consumer, and leaving it would either dead-letter or
keep browsing real devices up to ~15x per connect to drop the result.
ITagDiscovery itself stays — the /raw browse picker drives it through
Commons/Browsing/DiscoveryDriverBrowser, which never went through the actor,
so the picker is unaffected.

deferment.md §4.4 called the 18 DiscoveryInjectionDormantV3 tests "Real —
blocked on #507". They are not: they assert an equipment-rooted graft
(EquipmentRootNodeId == "EQ-1") that v3 cannot produce, so they could never
have unskipped as written. Deleted along with DiscoveredNodeMapperTests, the
CapturingAddressSpaceBuilder tests, and the MaterialiseDiscoveredNodes tests
in AddressSpaceApplierTests/OpcUaPublishActorTests. Runtime.Tests skipped:
31 -> 13.

IHostConnectivityProbe is deliberately NOT resolved here. GetHostStatuses()
has no production call site and nothing writes a DriverHostStatus row, but the
table was re-created in the v3 initial migration, so deleting on inference
would be wrong. Split to Gitea #521 with both options costed.

CLAUDE.md, docs/drivers/{Galaxy,TwinCAT,MTConnect}.md updated — they described
the seam as dead.

Build clean; Runtime.Tests 476 passed / 13 skipped; OpcUaServer.Tests 362
passed / 4 skipped.
2026-07-27 18:57:09 -04:00
Joseph Doherty db751d12a5 feat(alarms): condition Quality tracks source connectivity (#477)
v2-ci / build (pull_request) Successful in 4m49s
v2-ci / unit-tests (pull_request) Failing after 3h11m25s
Part 9 ConditionType.Quality was never assigned; default(StatusCode)==Good
so every native + scripted condition reported Good unconditionally — a
comms-lost device still showed a healthy, inactive, Good condition (a
wrong-VALUE bug, distinct from the null-value #473/#475). Clients (and HMIs
bucketing on IsGood) could not tell "genuinely inactive" from "lost contact".

Layer 1 — make Quality a real, plumbed field:
- AlarmConditionSnapshot gains OpcUaQuality Quality (default Good).
- MaterialiseAlarmCondition sets it (native BadWaitingForInitialData, scripted Good).
- WriteAlarmCondition projects snapshot.Quality; the delta-gate gains a Quality
  member so a quality-bucket change fires a Part 9 event.

Layer 2 — drive native quality from driver connectivity (a comms-lost driver
emits no alarm transitions, and an alarm-bearing raw tag has no value variable,
so quality can't come from either existing channel):
- DriverInstanceActor Tells parent ConnectivityChanged on Connected/Reconnecting.
- DriverHostActor fans it to every native condition the driver owns as
  OpcUaPublishActor.AlarmQualityUpdate (Good on connect, Bad on disconnect).
- New dedicated IOpcUaAddressSpaceSink.WriteAlarmQuality sets ONLY Quality and
  fires only on a bucket change — never touches Active/Acked/Retain (an active
  alarm that loses comms stays active). Not a full-snapshot re-projection, so it
  can't clobber severity/message and works for a never-fired condition.
  Forwarded through DeferredAddressSpaceSink (F10b trap; auto-verified by the
  reflection forwarding guard). Ungated by redundancy role; no /alerts row.

Scripted conditions stay Good; worst-of-input quality deferred to #478 (Layer 3).

Tests: node-level (materialise/project/no-clobber/unknown-node no-op),
NativeAlarmProjector, DriverInstanceActor connectivity emission, DriverHostActor
fan-out, OpcUaPublishActor routing, and the wire-level guard
(Condition_event_Quality_tracks_source_connectivity_on_the_wire) — RED-verified
against a simulated pre-fix always-Good server. Existing DriverInstanceActor
parent probes ignore the new ConnectivityChanged.

Docs: docs/AlarmTracking.md §"Condition source-data Quality (#477)";
design doc docs/plans/2026-07-17-alarm-condition-quality-477-design.md.
2026-07-17 15:10:04 -04:00
Joseph Doherty 8ebc712eff feat(v3-batch4-wp4): multi-notifier native alarms (single ReportEvent → raw + equipment notifiers) + teardown symmetry
Materialize each native alarm ONCE at the raw tag (ConditionId = RawPath, Raw
realm); wire the single condition as an SDK event notifier of each referencing
equipment's UNS folder so one ReportEvent fans to every root without
re-reporting per root (which would break Server-object dedup + Part 9 ack
correlation).

- New sink method WireAlarmNotifiers(alarmNodeId, alarmRealm,
  notifierFolderNodeIds, notifierFolderRealm) on IOpcUaAddressSpaceSink,
  forwarded through DeferredAddressSpaceSink + SdkAddressSpaceSink +
  NullOpcUaAddressSpaceSink (the forwarding-trap guard); auto-covered by the
  DeferredSinkForwardingReflectionTests realm + forwarding guards + a
  hand-written forward test.
- OtOpcUaNodeManager: the normative AddNotifier(isInverse) pair + idempotent
  EnsureFolderIsEventNotifier per equipment folder; tracked per condition in
  _alarmNotifierWiring. Teardown symmetry: RemoveNotifier(bidirectional:true) on
  RebuildAddressSpace, RemoveAlarmConditionNode, and RemoveEquipmentSubtree so no
  inverse-notifier entry leaks across redeploys.
- AddressSpaceApplier.MaterialiseRawSubtree wires notifiers for each native alarm
  tag, resolving its ReferencingEquipmentPaths (Area/Line/Equipment) to the
  EquipmentId folder NodeIds via BuildEquipmentIdByFolderPath.
- AlarmTransitionEvent gains ReferencingEquipmentPaths (empty default); /alerts
  renders the referencing-equipment list as display metadata.
- Un-skipped + rewrote the native-alarm dark tests
  (DriverHostActorNativeAlarmTests x6, DriverHostActorNativeAlarmAckRoutingTests
  x1) for the v3 raw-condition model; new NodeManagerMultiNotifierAlarmTests
  proves multi-notifier wiring + teardown symmetry (no leaked duplicates after a
  re-trip) + applier wiring test.

Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
2026-07-16 12:07:11 -04:00
Joseph Doherty 3efcf8014b feat(v3-batch4-wp3): raw-only binding + UNS fan-out + write routing
Wave B of Batch 4 — the runtime binding seam for the dual namespace.

Applier (both realms, explicit realm at every sink call site):
- MaterialiseRawSubtree: Raw containers as folders + Raw tags as variables
  keyed by RawPath (native-alarm tag → single Part 9 condition at the RawPath),
  all in AddressSpaceRealm.Raw; historian tagname = override else RawPath.
- MaterialiseUnsReferences: each UNS reference Variable under its equipment
  folder (Uns realm) + an Organizes UNS->Raw edge; inherits writable/array/
  historian tagname from the backing raw tag (both NodeIds -> one tagname).
- FeedHistorizedRefs / ProvisionHistorizedTags now source RAW tags (mux ref
  stays single, keyed by RawPath); ApplyPureRemove tears down raw tags + UNS
  refs in place (raw-container removal falls back to rebuild).

DriverHostActor (dual-NodeId, single-source fan-out):
- _nodeIdByDriverRef value gains a realm (NodeRealmRef); rebuilt from
  RawTags UNION UnsReferenceVariables so one (DriverInstanceId, RawPath) fans
  to the raw NodeId AND every referencing UNS NodeId with identical
  value/quality/timestamp. Write inverse map keyed by the bare id; the
  ns-qualified NodeId the write hook passes is normalised (BareNodeId) so a
  write to either NodeId resolves the same driver ref (-> RawPath write).
- Native raw alarm condition routing is realm-tagged (Raw); AttributeValueUpdate
  + AlarmStateUpdate carry the realm through to the sink.

Retire EquipmentNodeIds -> V3NodeIds.Uns (applier/VirtualTagHostActor) and
RawPaths.Combine (DiscoveredNodeMapper, discovered nodes are Raw now).

DeploymentArtifact.ParseComposition emits the Raw + UNS subtrees byte-parity
with the composer (reconstruct entities -> AddressSpaceComposer.Compose).

Sink surface: removed the transitional `= AddressSpaceRealm.Uns` defaults from
IOpcUaAddressSpaceSink / ISurgicalAddressSpaceSink / SdkAddressSpaceSink /
DeferredAddressSpaceSink / NullOpcUaAddressSpaceSink — every call site is now
explicit (realm reordered before the trailing optionals on EnsureVariable +
MaterialiseAlarmCondition). Node-manager convenience methods keep their
defaults (they are not the interface impl; Sdk delegates explicitly).

Tests: rewrote DriverHostActorLiveValueTests (fan-out drift, 1:N) +
DriverHostActorWriteRoutingTests (dual-NodeId raw/uns write routing) to the v3
raw+uns model; new AddressSpaceApplierRawUnsTests; migrated the EquipmentTags
provisioning/feed tests to RawTags; swept EquipmentNodeIds test callers.

Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
2026-07-16 10:56:31 -04:00
Joseph Doherty e95615cef3 fix(v3-batch4-wp2): AddReference sink seam for Organizes UNS→Raw (Wave A review M1)
Close the Wave-A M1 gap: the sink surface had no way to wire the mandated
cross-tree Organizes reference from each UNS reference Variable to its backing
Raw node, forcing WP3 to reopen the frozen surface. Add a dedicated
realm-qualified AddReference method instead.

- IOpcUaAddressSpaceSink.AddReference(sourceNodeId, sourceRealm, targetNodeId,
  targetRealm, referenceType="Organizes"): realm-qualified both ends; idempotent;
  a missing endpoint is a logged no-op (never throws) so a mid-rebuild race can't
  fault a deploy. Base-interface capability (no surgical sniff, no transitional
  default — WP3 wires it explicitly per UNS reference variable).
- SdkAddressSpaceSink forwards to the node manager; DeferredAddressSpaceSink
  forwards unconditionally (like EnsureFolder); NullOpcUaAddressSpaceSink no-ops.
- OtOpcUaNodeManager.AddReference: resolve both nodes by full ns-qualified key
  (variable/folder/condition via ResolveNodeState), guard both-exist, then wire
  the edge bidirectionally (forward Organizes on source, inverse on target) with a
  ReferenceExists idempotency guard + ClearChangeMasks on mutated sides. Reference
  type resolved by ResolveReferenceType (Organizes default). Added internal
  GetNodeReferences test/diagnostic accessor.
- Reflection guard: the exhaustive-forwarding test + the realm-discriminator guard
  auto-cover AddReference (it has two AddressSpaceRealm params) — no edit needed.
- New SdkAddressSpaceSinkTests: Organizes UNS→Raw edge created bidirectionally +
  idempotent; missing endpoint is a safe no-op.
- All 15 IOpcUaAddressSpaceSink test doubles gain the AddReference no-op so the
  solution still builds.

Build: dotnet build ZB.MOM.WW.OtOpcUa.slnx = 0 errors.
Tests: Commons.Tests 310/310; OpcUaServer.Tests 337 passed / 4 pre-existing skips.

Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
2026-07-16 09:52:30 -04:00
Joseph Doherty 5534698d70 feat(v3-batch4-wp2): node manager dual-namespace + realm-aware sink surface
Register both v3 namespaces (Raw first, UNS second) on OtOpcUaNodeManager and
thread an AddressSpaceRealm discriminator through every node-naming sink method
so a bare node id is resolved to the correct namespace by realm — never parsed
out of the id string.

- IOpcUaAddressSpaceSink / ISurgicalAddressSpaceSink: every node-naming method
  gains `AddressSpaceRealm realm = AddressSpaceRealm.Uns` (transitional default so
  un-migrated WP3 call sites still compile; WP3/Wave B makes them explicit and
  removes the default). Null + SdkAddressSpaceSink impls updated; DeferredAddress-
  SpaceSink forwards realm through every method (the forwarding trap).
- DeferredSinkForwardingReflectionTests: existing exhaustive-forwarding guard
  auto-covers the new signatures; added an explicit guard that every node-naming
  sink method carries an AddressSpaceRealm parameter (RebuildAddressSpace exempt).
- OtOpcUaNodeManager: register RawNamespaceUri + UnsNamespaceUri; realm->namespace
  index via NamespaceIndexForRealm; all node maps (_variables/_folders/
  _alarmConditions/_nativeAlarmNodeIds/_historizedTagnames/_eventNotifierSources)
  re-keyed by the full ns-qualified NodeId string so Raw and UNS nodes sharing a
  bare id stay distinct; _notifierFolders already NodeId-keyed. A historized UNS
  reference node registers the SAME historian tagname as its backing raw node
  (both NodeIds -> one tagname). Inbound-write hook routes the full ns-qualified
  NodeId to the write gateway (realm-aware) and reverts by bare id + realm.
  HistoryRead seams resolve via NodeId directly. DefaultNamespaceUri kept as a
  transitional alias to UnsNamespaceUri for the SubscriptionSurvivalTests.
- Test doubles across Commons.Tests / OpcUaServer.Tests / Runtime.Tests updated to
  the new interface signatures; SdkAddressSpaceSinkTests asserts the UNS namespace
  index for default-realm nodes.

Build: dotnet build ZB.MOM.WW.OtOpcUa.slnx = 0 errors.
Tests: Commons.Tests 310/310; OpcUaServer.Tests 335 passed / 4 pre-existing skips.

Claude-Session: https://claude.ai/code/session_01LVneM3eh1UtJxEisFXgmox
2026-07-16 09:33:45 -04:00
Joseph Doherty e2b47638ec feat(opcua): surgical mixed add+remove deploys (R2-07 T13) 2026-07-13 12:22:45 -04:00
Joseph Doherty 502d7650d0 feat(opcua): surgical pure-remove deploys — scoped teardown, no full rebuild (R2-07 T11) 2026-07-13 12:18:08 -04:00
Joseph Doherty 438004e371 feat(commons): add surgical remove members to ISurgicalAddressSpaceSink + deferred forwarding (guard-verified) (R2-07 T7) 2026-07-13 12:07:01 -04:00
Joseph Doherty 9dbc363ef0 feat(opcua): announce pure-add nodes via Part 3 NodeAdded model-change (R2-07 T3) 2026-07-13 11:48:02 -04:00
Joseph Doherty 0d717e4785 feat(opcua): route AddressSpaceApplier through the classifier — pure-add deploys no longer rebuild (R2-07 T2) 2026-07-13 11:46:24 -04:00
Joseph Doherty 598cdfad5a feat(otopcua): applier pass to materialise discovered nodes idempotently 2026-06-26 07:16:36 -04:00
Joseph Doherty 23b42b424d fix(code-review): resolve OpcUaServer-001 — UNS Area/Line rename refreshes folder DisplayName
A rename-only deploy produced an IsEmpty plan that short-circuited before MaterialiseHierarchy,
leaving the OPC UA folder DisplayName stale. AddressSpacePlanner now diffs UnsAreas/UnsLines by
stable id into a RenamedFolders set (counted in IsEmpty); the applier refreshes the folder in
place via a new UpdateFolderDisplayName on ISurgicalAddressSpaceSink (forwarded through
DeferredAddressSpaceSink so it is NOT inert on driver hosts; falls back to rebuild when the sink
is non-surgical). DeploymentArtifact byte-parity untouched (rename rides the existing Name
round-trip). No EF migration, no serialized wire/proto contract change. +13 OpcUaServer tests, Runtime rebuild test.
2026-06-20 23:10:24 -04:00
Joseph Doherty fb094fa566 feat(opcua): FB-7 surgical DataType/array-shape in-place tag writes
Widen the F10b surgical address-space path so a changed equipment tag whose
only differences are DataType / IsArray / ArrayLength (on top of the existing
Writable / Historizing) is applied IN PLACE on the live node instead of forcing
a full RebuildAddressSpace that drops every client's subscriptions server-wide.

ISurgicalAddressSpaceSink.UpdateTagAttributes gains (dataType, isArray,
arrayLength); the DeferredAddressSpaceSink wrapper forwards all six args (the
prod-inertness seam). OtOpcUaNodeManager swaps DataType + ValueRank +
ArrayDimensions in place, and on a real shape change (a) resets the node to
BadWaitingForInitialData so no stale wrong-typed value is exposed (closes the
prior brief-value-type-mismatch objection) and (b) raises a Part 3
GeneralModelChangeEvent (verb=DataTypeChanged) so model-aware clients re-read
the definition. A Writable/Historizing-only change leaves the shape untouched
(no reset, no model event) — original behaviour preserved byte-for-byte.

AddressSpaceApplier.TagDeltaIsSurgicalEligible adds the three shape fields to
its whitelist; FullName/Name/DriverInstanceId/alarm differences still rebuild.

Tests: new NodeManagerSurgicalShapeUpdateTests boots a real server to prove the
in-place swap + value reset + the no-reset backward-compat path + the model-event
builder; AddressSpaceApplierTests invert the two former DataType/IsArray-rebuild
cases to surgical and assert the shape args land; DeferredAddressSpaceSinkTests
assert the shape args forward. 273/273 OpcUaServer.Tests green; full solution builds.
2026-06-19 03:21:03 -04:00
Joseph Doherty 40e8a23e7c refactor(opcuaserver): rename Phase7* address-space pipeline to AddressSpace*
v2-ci / build (push) Failing after 37s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (push) Has been skipped
The OPC UA address-space build pipeline was named after a v2-roadmap
milestone number rather than its domain. Rename the family to describe
what it does (build/diff/apply the OPC UA address space):

  Phase7Composer          -> AddressSpaceComposer
  Phase7CompositionResult -> AddressSpaceComposition
  Phase7Planner           -> AddressSpacePlanner
  Phase7Plan              -> AddressSpacePlan
  Phase7Applier           -> AddressSpaceApplier
  Phase7ApplyOutcome      -> AddressSpaceApplyOutcome

The 9 Phase7*Tests suites follow suit; Phase7ScriptingEntitiesTests ->
ScriptingEntitiesTests (it tests the scripting migration, not the
pipeline). Log-message prefixes move to the new class names.

Pure mechanical rename, no behavioral change. EF migration classes/IDs
(AddPhase7ScriptingTables, ExtendComputeGenerationDiffWithPhase7) are
immutable and left untouched, as are historical design docs.

Build clean; OpcUaServer 261/261, Runtime 272/272, ScriptingEntities
12/12 green.
2026-06-18 19:16:28 -04:00