Joseph Doherty bac93744ce fix(alarms): #647 re-review — re-statement needs the same message; CNC refusal is not comms loss; worst-of health
R1: NativeAlarmProjector treats Raise-on-Active as a re-statement only when the message matches what
the condition shows; a different alarm appearing during a respawn un-acks and writes its alerts row.
FOCAS condition messages are a deterministic function of the matched set (tested across fresh driver
instances and reordered lists); Runtime E2E now covers both the same alarm and a new one during a
respawn. Residual (source message determinism) documented in AlarmTracking.md.

R2: a non-OK cnc_rdalmmsg2 return is thrown as FocasWireException{Rc} and classified as a CNC
refusal: conditions get a quality-only BadNotSupported once, one Warning, polling continues, and
driver health is untouched (no 90 s watchdog reconnect loop on a production control). Only transport
faults degrade (falsification control in the test).

R3: alarm-path health is tracked apart from the value path and combined in GetHealth: worst state,
later LastSuccessfulRead. A good value read can no longer mask a failing alarm read (no per-poll
/hosts flip) and a good alarm read cannot mask a value Degraded.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 20:45:32 -04:00
Joseph Doherty 482bafdfac feat(focas): CNC alarms reach Part 9 conditions via ALARM: tags (#647)
An ALARM: address (*, <Type>, <Type>/<n>, <Type>/<lo>-<hi>, T<code>, OTHER) on a raw tag that
also carries the cross-driver alarm object is ONE condition with ConditionId == RawPath and a
Kind (Raise / Retrigger / Clear), so DriverHostActor.ForwardNativeAlarm routes it and
NativeAlarmProjector activates it. Fixes all seven triage defects:

1. SubscribeAlarmsAsync treated the host's RawPaths as device hosts -> nothing polled.
2. Decorated "{host}#{Type}:{Number}" ConditionId -> every event dropped.
3. No Kind -> projector kept prior state.
4. WireFocasClient.ReadAlarmsAsync answered [] on failure -> mass clear + un-acked re-raise.
   It now throws; a failed device read keeps every condition's state.
5. Acks lost on reconnect -> told-record dedup (MTConnect #626 pattern) held for the driver's
   lifetime; same-set re-subscribe / re-init re-raise nothing; changed set prunes leavers only.
6. Subscribe threw while AlarmProjection.Enabled=false -> the tag is the opt-in; flag is a no-op.
7. Alarm tags could not be authored -> ALARM: grammar (FocasAlarmSelector, Contracts) backs the
   editor, the address picker, the deploy-time inspector and driver init.

Severity: authored alarm.severity -> exact OpcUaSeverity; else the 16i-era type bucket. The type
table stays the only one (moved to Contracts, documented 16i-era; 30i codes not invented; raw
T<code> selector + raw code in every message). Read-only: ack is server-side. Also clears the
value table on a re-initialise (#630 gap that let a removed/moved tag keep reading).

E2E: Runtime.Tests FocasNativeAlarmEndToEndTests drives the real driver through the real
DriverHostActor and asserts the condition goes Active then inactive.

Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 19:46:48 -04:00
Joseph Doherty 8d916f2af7 feat(focas): coalesce adjacent PMC reads into one pmc_rdpmcrng (#266)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 16:59:07 -04:00
Joseph Doherty 5b36c717de feat(focas): cnc_statinfo status flags as Status/ fixed-tree nodes (#257)
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
2026-10-08 16:53:44 -04:00
Joseph Doherty 1dba46bd7b fix(focas): decode servo/spindle meters by their base/exponent envelope; MaxRpm -> MotorSpeedPct
Servo (0x0056) and spindle (0x0040) meter records are 8 bytes:
[i32 value][u16 base][u16 exponent], the same self-describing envelope as the
position blocks.

Servo: offset 4 was read as a decimal count. It is the BASE (a steady 10), so
every load was divided by 10^10 and published ~0 -- the sister ignitionoee panel
read servo 0% on every axis of a Makino cutting at 20,000 rpm. Loads are now
value / base^exponent, a direct percentage.

Spindle: the raw meter is a 1/16384 fraction of full scale. Settled on the real
Z-34184 by regressing the type-1 meter against cnc_rddynamic2 spindle speed over
596..20,000 rpm (rpm = 1.220749 x meter; 16384 x 1.220749 = 20000.75). So:
- Spindle/{name}/Load publishes % of rated load (Float64; was the raw Int32
  count -- a reading of 9155 meant 55.9%).
- Spindle/{name}/MaxRpm is RENAMED Spindle/{name}/MotorSpeedPct (Float64, % of
  maximum speed) and is polled with Load. The old node was actively wrong: the
  type-1 meter is the live motor speed, and it was read once at bootstrap and
  served forever as if it were a max-RPM constant. Client-visible: FIXED: tags
  on .../MaxRpm must be re-pointed.
- The spindle read no longer stops at the first zero after slot 1 (which dropped
  an idle second spindle and kept non-zero residue); every slot is returned.

A record whose envelope is undescribable (base not 2/10, exponent > 18 -- e.g.
residue past the configured axis/spindle count) publishes BadNoData, never a Good 0.

Ported from the sister ignitionoee FOCAS driver v0.17.2/v0.17.3 (Focas.Wire-019);
live captures live-spmeter-{load,maxrpm}-0x0040.bin added as fixtures.
2026-10-07 14:07:22 -04:00
Joseph Doherty 69e0a622f3 fix(focas): scale positions from each cnc_rddynamic2 block; delete the fabricated cnc_getfigure
Every 0x0026 position block is self-describing: [i32 raw][u16 base][u16 exponent],
value = raw / base^exponent. The live 31i-B capture (ref-dynamic2-axis1.bin)
reports base 10 / exponent 4 on every block, so axis 1 is 280.1574 mm, not
2801574. The driver ignored the envelope and instead sent 'cnc_getfigure'
(0x00D3) -- a command that does not exist in the FOCAS wire protocol, served only
by the in-tree mock; the real control refuses it with rc=1, so on hardware every
position fell back to PositionDecimalPlaces (default 0) and published raw counts.

- ParsePositionBlock decodes the envelope into FocasPosition; the driver applies
  raw / base^exponent at publish. PositionDecimalPlaces is now only the fallback
  for a scale-less (4-byte) block.
- A block describing no position (0xFFFF vacant marker, base not 2/10, exponent
  > 18 -- raw / 10^400 would read as a Good 0.0) publishes BadNoData on that node
  alone; siblings are untouched.
- ReadPositionFiguresAsync / IFocasClient.GetPositionFiguresAsync and the
  per-axis figure cache are deleted.

Ported from the sister ignitionoee FOCAS driver v0.17.0 (+ Focas.Wire-014);
live axis-scoped captures live-dynamic2-axis{1,2}-0x0026.bin (Z-34184 X 0.0374,
Y 370.177) added as fixtures.
2026-10-07 14:03:08 -04:00
Joseph Doherty 3fcbc70cba feat(focas): add cnc_getfigure per-axis position-figure client binding 2026-06-16 19:38:49 -04:00
Joseph Doherty 5c5aaef609 fix(focas): fail-fast at init on unimplemented backend (operator footgun)
Add IFocasClientFactory.EnsureUsable() — a config-time probe called by
FocasDriver.InitializeAsync before any background loops start. The
UnimplementedFocasClientFactory throws NotSupportedException immediately
(faulting the driver at init), eliminating the footgun where a driver on
the 'unimplemented' backend appeared Healthy then failed every read/write/
subscribe silently. WireFocasClientFactory and FakeFocasClientFactory are
no-ops. Backstop Create() throw remains in place.
2026-06-16 05:24:41 -04:00
Joseph Doherty 64e3fbe035 docs: backfill XML documentation across 756 files
v2-ci / build (push) Failing after 1m43s
v2-ci / unit-tests (tests/Core/ZB.MOM.WW.OtOpcUa.Cluster.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.ControlPlane.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Runtime.Tests) (push) Has been skipped
v2-ci / unit-tests (tests/Server/ZB.MOM.WW.OtOpcUa.Security.Tests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.Host.IntegrationTests) (push) Has been skipped
v2-ci / integration (tests/Server/ZB.MOM.WW.OtOpcUa.OpcUaServer.IntegrationTests) (push) Has been skipped
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
2026-05-28 08:10:17 -04:00
Joseph Doherty a25593a9c6 chore: organize solution into module folders (Core/Server/Drivers/Client/Tooling)
Group all 69 projects into category subfolders under src/ and tests/ so the
Rider Solution Explorer mirrors the module structure. Folders: Core, Server,
Drivers (with a nested Driver CLIs subfolder), Client, Tooling.

- Move every project folder on disk with git mv (history preserved as renames).
- Recompute relative paths in 57 .csproj files: cross-category ProjectReferences,
  the lib/ HintPath+None refs in Driver.Historian.Wonderware, and the external
  mxaccessgw refs in Driver.Galaxy and its test project.
- Rebuild ZB.MOM.WW.OtOpcUa.slnx with nested solution folders.
- Re-prefix project paths in functional scripts (e2e, compliance, smoke SQL,
  integration, install).

Build green (0 errors); unit tests pass. Docs left for a separate pass.

Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>