Now that ALMD transitions route, a re-subscribe (every reconnect, every alarm-set change)
started from an empty per-subscription record and re-RAISED every still-faulted alarm,
which the host projects as Active+unacked - un-acknowledging a condition the server had
just carried across the rebuild with its client ack. The record is now driver-owned and
pruned to the new set, mirroring MTConnect's _deliveredConditions.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Found while verifying item 4 of #641. The host routes a native alarm transition
on an exact ConditionId == RawPath match (DriverHostActor.ForwardNativeAlarm),
but AbCipAlarmProjection emitted "{ref}#active" and no Kind, so every ALMD
raise/clear was dropped as "no alarm condition" — and even if routed, an
Unspecified kind projects no state change. It now reports the subscribed
reference (the RawPath) and Raise/Clear. A host test pins that a decorated id
is dropped.
FOCAS has the same id shape plus a device filter keyed by host address (a
RawPath subscription polls nothing); it needs a mapping decision and is
documented in docs/drivers/FOCAS.md rather than patched here.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Ab.Transport.Tests: predecessor-wait counter instead of 300 ms (DeviceSessionPoolTests x2), throttle
queue/interval-park hooks instead of 50/100 ms (ForwardOpenThrottleTests x2), UnobservedTaskProbe with a
must-report control fault instead of N GC cycles (EncapsulationClientTests), re-armed keep-alive timer as
the control for the never-opened keep-alive test.
AbCip.Tests: still-polling sibling / control driver read counts instead of 300-500 ms (subscriptions x4,
alarm projection x5), structural ProbeTask==null + enabled-probe control (host probe x2), predecessor
wait (NativeAbCipLeaseReleaseTests), processed waits in the shutdown/logging tests.
AbLegacy.Tests: sibling-subscription control (Unsubscribe_halts_polling), ProbeCts==null + control.
AbCip.IntegrationTests differential safety: a post-phase control open through the same throttle instead
of 1.5-2.5 s sleeps (via a native tag init, keeping the harness read-only guard green).
Fake tag ReadCount made interlocked; CapturingLogger entries snapshotted under a lock.
Claude-Session: https://claude.ai/code/session_01Ef2ozxS7QPanGT8uoATbTe
Apply the reviewed Modbus exemplar to the AbCip multi-device driver:
- Mapper AbCipEquipmentTagParser -> AbCipTagDefinitionFactory; TryParse -> FromTagConfig(tagConfig, rawPath, out def); drop leading-{ heuristic + the deviceHostAddress key; add inverse ToTagConfig; round-trip arrays/members/safety for coverage.
- Options: Tags (typed) -> RawTags (RawTagEntry list); Devices list kept.
- Driver: byName-only resolver over _tagsByRawPath (Ordinal); table built from RawTags via FromTagConfig, threading entry.DeviceName (device routing key) + entry.WriteIdempotent onto the def. Multi-device routing keys on DeviceName-or-host via a _devicesByRoutingKey index; discovery groups _declaredTags by RoutesToDevice.
- Factory: retire the pre-declared Tags DTO/BuildTag; bind List<RawTagEntry> RawTags.
- Probe: derive probe tag path from RawTags via the mapper.
- Cli BuildOptions projects typed tags -> RawTagEntry (ToTagConfig).
- Tests: AbCipRawTags helper (typed def -> RawTagEntry); parser tests -> FromTagConfig; blob-fallback driver tests rewritten to author via RawTags + read by RawPath. Driver.AbCip.Tests 342/342, Cli.Tests 42/42.
TODO(v3 WaveC): DeviceName becomes a pure logical name once the device connection host moves to the Device row's DeviceConfig.
The owning DriverInstanceActor re-subscribes alarms on every Connected
entry (DetachAlarmSource nulls its cached handle on Connected->Reconnecting
without calling UnsubscribeAlarmsAsync), and the driver object + its alarm
projection are reused across every in-place reconnect. Each SubscribeAsync
started a fresh, never-cancelled Task.Run poll loop and added it to _subs,
so N reconnects leaked N concurrent loops all polling the device and all
firing the same raise/clear transitions => duplicate alarm events + CPU/mem
growth.
Mirrors the Galaxy #399 fix (Clear-before-Add) but for live poll loops the
collapse must also CANCEL the superseded loops, not just drop references.
SubscribeAsync now snapshots existing subs under _subsLock, clears _subs,
adds the new sub, starts its loop, then retires each stale sub out-of-band
(RetireAsync: Cancel + await loop + Dispose CTS, fire-and-forget so the new
subscription's return isn't blocked on a poll interval). Snapshot+clear under
the same lock DisposeAsync uses guarantees no double-own / double-dispose.
There is exactly one consumer per driver instance (factory-per-actor), so
retiring all prior subscriptions before starting the new one is faithful.
Regression tests (TDD, fail->pass): subscribe twice then drive one device
raise; assert OnAlarmEvent fires exactly once (was twice with two leaked
loops).
Adds <summary>, <param>, <typeparam>, and <inheritdoc/> tags to public
members surfaced by commentchecker — resolves 5,847 of 5,869 issues
(99.6%) across three /fixdocs passes.
Driver.AbCip-001 — ReinitializeAsync silently discarded its config JSON.
Extracted AbCipDriverFactoryExtensions.ParseOptions; InitializeAsync now
re-parses a content-bearing driverConfigJson and replaces _options (and
recreates the alarm projection), so a reinitialize with a changed config
(new device/tag, changed timeout) actually takes effect. A blank or
empty-object JSON keeps construction-time options for the unit-test seam.
Driver.AbCip-002 — libplctag status mapping used wrong integer constants.
MapLibplctagStatus now switches on the libplctag.NET Status enum members
(Ok/Pending/ErrorTimeout/ErrorNotFound/ErrorNotAllowed/ErrorOutOfBounds/…)
instead of hand-typed natives, so timeout/not-found/not-allowed/out-of-bounds
get their specific OPC UA codes instead of all collapsing to
BadCommunicationError. The int overload casts to Status to stay correct
against the wrapper's contiguous renumbering.
Driver.AbCip-003 — whole-UDT reads decoded members at declaration-order
offsets, which Studio 5000 does not guarantee. Added the opt-in
AbCipDriverOptions.EnableDeclarationOnlyUdtGrouping flag (default false);
AbCipUdtReadPlanner.Build forms no groups when it is off, so by default
every UDT member reads per-tag rather than at possibly-wrong offsets.
Driver.AbCip-008 — probe loops were fire-and-forget and ShutdownAsync raced
them. Each probe Task is stored on DeviceState.ProbeTask; ShutdownAsync now
cancels every CTS, awaits each probe Task (10s timeout), then disposes the
CTS and handles. DeviceState.Runtimes/ParentRuntimes are ConcurrentDictionary
and the Ensure*RuntimeAsync paths use TryAdd, disposing the losing concurrent
creator instead of leaking a native tag handle.
Adds AbCipDriverCodeReviewRegressionTests and updates existing AbCip tests
to the corrected status constants + opt-in grouping flag. AbCip driver +
test project build clean; all 244 AbCip tests pass. (The full-solution
build has pre-existing, unrelated Driver.Galaxy protobuf-generation errors
in this worktree.)
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>
Group all 69 projects into category subfolders under src/ and tests/ so the
Rider Solution Explorer mirrors the module structure. Folders: Core, Server,
Drivers (with a nested Driver CLIs subfolder), Client, Tooling.
- Move every project folder on disk with git mv (history preserved as renames).
- Recompute relative paths in 57 .csproj files: cross-category ProjectReferences,
the lib/ HintPath+None refs in Driver.Historian.Wonderware, and the external
mxaccessgw refs in Driver.Galaxy and its test project.
- Rebuild ZB.MOM.WW.OtOpcUa.slnx with nested solution folders.
- Re-prefix project paths in functional scripts (e2e, compliance, smoke SQL,
integration, install).
Build green (0 errors); unit tests pass. Docs left for a separate pass.
Co-Authored-By: Claude Opus 4.7 (1M context) <noreply@anthropic.com>